ACI-Automation Components A/CO2 SERIES Data Sheet

Automation Components, Inc.
GAS
A/CO2 SERIES
A/CO2-R2
A/CO2-DUCT
A/CO2 SERIES
ACI Carbon Dioxide Sensor
The A/CO2 room and duct transmitters monitor the carbon dioxide (CO2) levels in industrial, school, and office-type environments. The concentration of CO2 is a strong indication of the overall indoor air quality. The A/CO2 Series is based on a single beam, non-dispersive infrared technology and is a cost-efficient solution for measuring CO2 levels for building climate control. In addition, ABC software eliminates the need for manual calibration. Carbon Dioxide concentration is measured up to 2,000 ppm and is converted into proportional analog outputs. The factory default output is 4-20 mA, whereas 0-5 VDC and 0-10 VDC outputs are able to be field selected via integral dip switches. Thermistor temperature outputs, along with setpoint and override, are available as options for room configurations. The A/CO2 Series provides data which can be used in conjunction with a Building Automation System or Demand Control Ventilation to decrease energy consumption while creating a healthier indoor climate.
Automation Components, Inc.
89
GAS
/
A
CO2 SERIES
Automation Components, Inc.
SPECIFICATIONS
Supply Voltage Power Consumption Sensing Technology/Sensing Method Measurement Range Default CO2 Output Signal Fail Safe CO2 Accuracy Pressure Dependence Response Time Warm Up Time Temperature Output Temperature Accuracy Operating Temperature/Relative Humidity Range Sensor Coverage Area Life Expectancy Product Dimesions (Room Mount) Product Dimesions (Duct Mount)
24 VAC +/-20%, 50/60 Hz (half-wave rectifier); 16.5-40 VDC Max. 3VA for 24VAC, 3W for 24VDC (peak); <0.9W (average) Single beam infrared sensing technology (NDIR); Diffusion 0 to 2,000 ppm Out 1: 0-5 VDC or 0-10 VDC (Default) | Out 2: 4-20 mA (500 Ohm Load Max.) Polarity protected +/- 40 ppm +/- 3% of reading (@ 15-35°C; 20-70% RH and 101.3 kPa) + 1.6% reading per kPa (deviation from standard pressure 101.3 kPa)
≤ 2 minutes, diffusion
< 1 minute (@ full specs < 15 minutes) Various (see order grid) +/- 1°F (+/- 0.6°C) 32 to 122 7,500 sq. ft. maximum > 15 years (typical) (H) 4.5” (W) 2.75” (D) 1.12” (H) 5.98” (W) 3.33” (D) 1.85”
o
F (0 to 50oC)/0 to 95%, non-condensing
ORDERING
Select one Configuration (A). If a Room Configuration is selected, please follow direction to choose either (B), (C), (D) or (E). Pot Value & Setpoint Offset are only applicable when a setpoint is specified and the values listed represent ohms. If a Duct configuration is selected, your part number is complete. Duct models are not available in conjunction with Thermistors. NOTE: not be displayed in your final part number.
Selections (C) through (E) are for internal references and will
Configuration Pot Value Setpoint Offset
R2 (Room) (Only Complete B)
(Room, Setpoint) (Complete B, C, D & E)
R2S
(Room, Override) (Only Complete B)
R2O
(Room, Setpt & Override) (Complete B, C, D & E)
R2SO
(Duct) (Part Number is finished)
DUCT
(Duct with Conduit) (Part Number is finished)
DUCT-C
Thermistor
---- (None) (Type II)
CP
(Type III)
AN 20K 3K
1.8K
10K-E 100KS CSI (Dale)
None 400 1K 2K 5K
8.5K 10K 20K 100K
None 0 (Default)
51.1 499 806 910 1K
2K
4.99K
6.19K
7.32K
8.25K 10K 20K
Pot Action
None DA (Direct)
(Reverse)
RA
BUILD PART NUMBER
After completing (A), (B), (C), (D) & (E) from the above table, fill in the Part Number Table below. The “Sensor Series” is a factory default.
A/CO2
SENSOR SERIES
EXAMPLE: A/CO2-R2SO-CP-100K-0-DA