ACI-Automation Components A/BN1110-R2, A/BN1120-R2, A/BN1130-R2 Data Sheet

Automation Components, Inc.
BACNET™ | ROOM
ROOM
BACnet™ Communicating Room Sensor
The BN Series Room Temperature and Humidity networked sensors are a cost eective, single or dual point native BACnet™ sensing solution designed to reduce the need for additional input modules or building management controllers when a limited number of input points are available. The BTL Certication provides condence that these sensors may be used in any new or retrot installation using a BACnet™ MS/TP controller with third party BACnet™ devices. The reduced number of BACnet™ objects helps to reduce the sensor cost and simplies your installation and programming time. Please contact ACI for more information regarding the BN Series communicating sensors.
Applications: Ambient Air Temperature/Humidity Sensing, Oce Buildings, Schools, Clean Rooms, Pharmaceutical Labs, Hospitals, Data Centers & Retail Stores
PRODUCT SPECIFICATIONS
Supply Voltage:
Current Consumption:
Temperature Measurement Range:
Temperature Measurement Accuracy @ 77ºF (25ºC):
Temperature Calibration Oset:
Temperature Units:
RH Measurement Range:
RH Measurement Accuracy 77ºF (25ºC):
Resolution:
Temperature / RH Update Rate:
Communication Protocol:
Sensor Addresses:
Supported Baud Rates:
Maximum Distance:
End of Line Termination Resistance:
Tri-Color Status LED:
Connections | Wire Size:
Operating Temperature Range:
Storage Temperature Range:
Operating Humidity Range:
Enclosure Color:
Enclosure Material | UL Flammability Rating:
Product Dimensions (L x W x D):
Product Weight:
Recommended Mounting Height:
Agency Approvals:
12 to 36 VDC | 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
25 mA maximum (0.67 VA)
35 to 122ºF (1.5 to 50ºC)
+/- 1.0ºF (+/- 0.5ºC)
+/- 9ºF (+/- 5ºC) (Field Congurable)
ºF (Factory Default), ºC, ºK (Field Congurable)
0 to 100%
+/- 2% from 10 to 90% RH
+/- 10% RH (Field Congurable)
+/- 0.1º | +/- 0.1%
4 seconds
BACnet™ MS/TP; EIA RS-485
0 = Factory Default | 1-127 = Field Selectable
Auto Baud (Factory Default) | 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable)
4000 ft (1219 m)
120 Ohms Termination Resistance (Field Selectable)
Connection Status
Screw Terminal Blocks | 16 AWG (1.31 mm) to 22 AWG (0.33 mm)
35 to 122ºF (1.5 to 50ºC)
-40 to 185ºF (-40 to 85ºC)
10 to 95% RH, non-condensing
White
ABS Plastic | UL94-HB
4.50” (114.3 mm) x 2.78” (70.6 mm) x 1.40” (35.6 mm)
0.21 lbs. (0.095 kg)
4 to 5 ft (1.2 to 1.5 m) above oor
BTL Certied, CE, RoHS2, WEEE, China RoHS
BACNET | ##
BACNET™ | ROOM
DIMENSIONAL DRAWING
2.75” (69.85mm)
Automation Components, Inc.
4.50”
(114.30mm)
1.12” (28.55mm)
Front & Right Views Bottom View
STANDARD ORDERING
Model #
A/BN1110-R2 A/BN1120-R2 A/BN1130-R2
ACCESSORIES ORDERING
Model #
A/MOUNTING PLATE WHITE R2 A/LOCKING COVER A/ROOM-FOAM-PAD
Item #
143517 143518 143519
Item #
143369 107370 125690
Description
BACnet™, Temperature, Room BACnet™, Relative Humidity, (+/- 2%), Room BACnet™, Relative Humidity, (+/- 2%), Temperature, Room
Description
Plastic Wall Plate, White (R2) Clear Thermostat Guard Locking Cover (Low Prole) 1/8” Foam Insulation Pad with Adhesive, 3” x 2”, Black
Model # Example:
Model # Example:
-OR-
-OR-
143517A/BN1110-R2
107370A/LOCKING COVER
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.
BACNET | ##
Loading...