![](/html/cb/cbe5/cbe5f2bcd21402d273e39ac1b41192f320a8febda52ac24b9773affb8ae467e9/bg1.png)
Automation Components, Inc.
CURRENT | ADJUSTABLE SWITCHES
ADJUSTABLE SWITCHES
ACS2, ACSX2, ASCS2 & ASCSX2 Series
The Adjustable Current Switches are designed for use in any AC current monitoring application
in which you are looking to monitor a particular piece of equipment for equipment failure,
preventative maintenance, status, and electrical load status. The current switches should be
installed on the line side of the power to the electrical equipment. The current switches are
available in both solid and split-core versions which also includes a Patented 35 mm Din Rail
mounting foot for easy installation in panel mount applications. The solid-core versions are a
great choice for new installations or OEM applications in which cost sensitivity, lower trip points
and environmental issues may be of concern. The split-core version of the current switches work
great in retrot applications and for use on service technicians vehicles since one part will work
in most applications and can be easily installed without disconnecting any wires. The adjustable
current switches can be used to determine the run time of your equipment as well as basic load trending applications where you want to know when
how long your piece of equipment runs when logging the contact closures on your building management system or PLC.
Applications: Overload Conditions, Underload Conditions, Normal Operating Conditions, Broken Belts, Belt Slippage, Locked Rotors, Equipment
Failure, Fans, Pumps, Compressors, Motors, Ovens, Industrial Equipment, Lighting Status and Usage, Electrical Load Status, Local Alarms (Strobes
and Audible Alarms), Preventative Maintenance Scheduling
PRODUCT SPECIFICATIONS
Monitored Current Type:
Maximum AC Voltage:
Operating Frequency Range:
Core Style:
Sensor Power:
Amperage Range:
Isolation Voltage:
Trip Point Style | Trip Point:
Hysteresis:
Contact Type:
“Status” Contact Rating:
“Status” Contact “On” Resistance | “O” Resistance:
Response Time:
Status LED Indication :
Aperture Size:
Din Rail Size:
Operating Temperature Range:
Operating Humidity Range:
Recommended Storage Temperature | RH Range:
Enclosure Material | Flammability Rating:
Wiring Connections:
Wire Size:
Terminal Block Torque Rating:
Minimum Mounting Distance:
Agency Approvals:
Product Weight:
Product Dimensions (L x W x H):
Note: The LED should not be used to determine if current is present. At low currents the LED may not be visible
AC Current
600 VAC
40 to 1 kHz
Solid-Core and Split-Core Versions available (See Ordering Grid)
Induced from the Monitored Conductor
See Ordering Grid
2200 VAC
Adjustable Trip Point | See Ordering Grid
10% of trip point, typical
Normally-Open “N/O” or Normally-Closed “N/C” (See ordering Grid)
0.2A @ 200 VAC/VDC
< 10 Ohms (tripped) | > 1 Meg Ohms (Open)
See Response Time Table on back of data sheet
Red LED (Current above Trip Point) | Blue LED (Current Below Trip Point)
0.75” (19.05 mm)
35 mm (U.S. Patent No. 7,416,421)
5 to 104ºF (-15 to 40ºC)
0 to 95%, non-condensing
41 to 95°F (5 to 35°C) | 40% to 85% RH, non-condensing
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
2 Position, Screw Terminal Block (Not Polarity Sensitive)
16 to 22 AWG (1.31 mm to 0.33 mm) Copper Wires only
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
1” (2.6 cm minimum) between current switch (Relays, Contactors, Transformers)
UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723),
CE, RoHS2, WEEE
A/ACS2 and A/ACSX2: 0.216 lbs. (0.097 kg) | A/ASCS2: 0.270 lbs. (0.123 kg)
A/ASCSX2: 0.266 lbs. (0.121 kg) | A/ASCS2-L: 0.280 lbs. (0.127 kg)
Solid Core Versions: 2.760” (70.11 mm) x 3.343” (84.92 mm) x 1.050” (26.67 mm)
Split Core Versions: 2.780” (70.51 mm) x 3.238” (82.25 mm) x 1.120” (28.45 mm)
![](/html/cb/cbe5/cbe5f2bcd21402d273e39ac1b41192f320a8febda52ac24b9773affb8ae467e9/bg2.png)
CURRENT | ADJUSTABLE SWITCHES
DIMENSIONAL DRAWING
Automation Components, Inc.
Solid-Core
Split-Core
2.36” (59.94mm)
2.55” (64.69mm)
3.24” (82.23mm)
Front View Right View Bottom View
RESPONSE TIME
Model #
A/ACS2
A/ACSX2
A/ASCS2
A/ASCSX2
A/ASCS2-L
Note*: ---- unit was not tested (below minimum trip point or for that range)
0.50 Amps
221mS
260mS
----
----
----
0.60 Amps
----
----
----
---400mS
0.75 Amps
144mS
169mS
----
---270mS
2.77”
(70.45mm)
2.77”
(70.35mm)
1.10” (28.02mm)
1.0 Amp
109mS
130mS
----
---183mS
1.50 Amps
----
---248mS
344mS
----
1.03”
(26.16mm)
2.87” (72.80mm)
3.35” (84.99mm)
2.87” (72.77mm)
10 Amps
63mS
82mS
68mS
92mS
62mS
20 Amps
59mS
74mS
65mS
86mS
60mS
STANDARD ORDERING
Model #
A/ACS2
A/ACSX2
A/ASCS2
A/ASCSX2
A/ASCS2-L
The Adjustable Current Switches are not intended to be used in Life / Safety Applications or in Hazardous / Classied Locations
Item #
142355
142354
142353
142370
142352
Trip Point Type
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
N/O
•
•
•
N/C
•
•
Solid-Core
•
•
Split-Core
•
•
•
Amp Range
0 to 250A
0 to 250A
0 to 250A
0 to 250A
0 to 250A
Model # Example:
Trip Point
0.5 to 220A
0.5 to 220A
1.5 to 220A
1.5 to 220A
0.6 to 180A
Contact Rating
0.2A @ 200 VAC/VDC
0.2A @ 200 VAC/VDC
0.2A @ 200 VAC/VDC
0.2A @ 200 VAC/VDC
0.2A @ 200 VAC/VDC
-OR-
142355A/ACS2