ACI-Automation Components A/20K-DO-12-10CL2P Data Sheet

Automation Components, Inc.
TEMPERATURE | THERMISTORS | DUCT WITHOUT BOX
DUCT WITHOUT BOX
Flange Mounted Duct Sensor, Thermistor
The ACI Thermistor Duct without Box Series features a stainless steel probe with two 22 AWG Etched Teon colored lead wires to dierentiate the dierent sensor types. The sensors in this series are manufactured using ACI’s proven double encapsulation process to eliminate the eects of moisture upon the sensors and increased response times using our high quality, thermally conductive epoxy. The duct style sensor is designed to be used in smaller duct applications and includes an insulation pad for sealing your duct as well as to dampen vibration. For best results, the sensor length should be determined by the actual width or diameter of your duct such that the tip of the probe is in the approximate center of the duct. On
larger ducts, you may want to refer to our Rigid or Bendable Copper Averaging sensor for increased sensing points and better temperature control. The Duct without Box Series can be ordered with optional plenum rated cables and NIST Certicates. Please contact ACI for more information regarding this sensor or to discuss your application in further detail. Other options may be available upon request.
Applications: Roof Top Units, Air Handlers, Monitoring Supply/Discharge/Return/Mixed Air Temperatures
PRODUCT SPECIFICATIONS
Sensor Type | Sensor Curve:
Number Sensing Points | Number Wires:
Sensor Output @ 25ºC (77ºF) |
(Lead Wire Colors):
Accuracy 0-70ºC (32-158ºF):
Stability:
Response Time (63% Step Change):
Power Dissipation Constant:
Operating Humidity Range:
Probe Material | Flange Material:
Fitting Material | Flammability Rating:
Foam Pad Material | Flammability Rating:
Lead Length | Conductor Size:
Lead Wire Insulation | Wire Rating:
Conductor Material:
Product Dimensions | Probe Diameter:
Product Weight:
Agency Approvals:
Thermistor | Non-Linear, NTC (Negative Temperature Coecient)
One | Two (Non-Polarity Sensitive)
A/1.8K: 1.8KΩ nominal | (Red/Yellow)
A/3K: 3KΩ nominal | (White/Brown)
A/AN (Type III): 10KΩ nominal | (White/White)
A/AN-BC: 5.238KΩ nominal | (White/Yellow)
A/CP (Type II): 10KΩ nominal | (White/Green)
+/-0.2ºC (+/-0.36ºF) except A/10K-E1 Series: +/- 0.3ºC (+/-0.54ºF)
A/1.8K Series: +/- 0.5ºC @ 25ºC (77ºF) and (+/-1.0ºC) (+/-1.8ºF)
Sensor Dependent; Contact ACI for more information on the sensor in question.
10 Seconds nominal
3 mW/ºC except A/1.8K Series: 1 mW/ºC | A/10K-E1 Series: 2 mW/ºC
-40 to 115ºC (-40 to 239ºF) | -40 to 85ºC (-40 to 185ºF)
10 to 95% RH, non-condensing
304 Stainless Steel | Galvanized Steel
Polyamide 66 (High Performance Nylon) | UL94-HB
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
4”, 6” and 8” Probes: 14” (35.6 cm) | 12” and 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Etched Teon (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Silver Plated Copper
See table on back of Product Data sheet | 0.250” (6.35mm)
See table on back of Product Data sheet
CE, RoHS2, WEEE
A/CSI: 10KΩ nominal | (Green/Yellow)
A/10KS: 10KΩ nominal | (White/Blue)
A/10K-E1: 10KΩ nominal | (Gray/Orange)
A/20K: 20KΩ nominal | (Brown/Blue)
A/100KS: 100KΩ nominal | (Black/Yellow)
Call: 1-888-967-5224 | Web: www.workaci.com
TEMPERATURE | ##
TEMPERATURE | THERMISTORS | DUCT WITHOUT BOX
DIMENSIONAL DRAWING, WEIGHTS
Automation Components, Inc.
.31” (7.98mm)
Available in 4”, 6”, 8”, 12”, and 18” Probe Lengths
.92” (23.47mm)
.98”
(24.89mm)
3.88”
(98.60mm)
1.13”
(28.74mm)
Standard Views Product Weights
CUSTOM ORDERING
A. Sensor Series
B. Model Series
C. Conguration
Note*: All 20’ Sensors are not CE compliant, but are RoHS2 compliant
Select One (1)
No Selection Required
Select One (1)
No Selection Required
Select One (1)
Select One (1)
Select One (1)
A/
1.8K | 3K | AN | AN-BC | CP | CSI | 10KS | 10K-E1 | 20K | 100KS
DO = Duct without Box (Mounting Flange Only)
4” = 4” Probe | 6” = 6” Probe | 8” = 8” Probe | 12” = 12” Probe | 18” = 18” ProbeD. Probe Length
---- = Standard 14” or 24” Lead Length | 10’ = 10 Feet (3.05m) | 20’ = 20 Feet* (6.10m)E. Lead Length
---- = Standard Etched PTFE Colored Leads | CL2P = 2 Conductor Plenum Rated Cable F. Lead Wire Type
---- = No NIST Certicate | NIST = NIST Certicate (Must Specify 1, 3 or 5 Points)G. NIST
Duct Without Box [DO] Weights
ACI Model #
A/xx-DO-yy A/xx-DO-yy-10’-CL2P A/xx-DO-yy-20’-CL2P
ACI Model #
A/xx-DO-yy A/xx-DO-yy-10’-CL2P A/xx-DO-yy-20’-CL2P
Model # Example:
4”
(Probe Length)
0.10 lbs. (0.045 kg)
0.20 lbs. (0.091 kg)
0.27 lbs. (0.122 kg)
12”
(Insertion Length)
0.19 lbs. (0.086 kg)
0.24 lbs. (0.108 kg)
0.31 lbs. (0.141 kg)
1.8K
A/
B.
A.
DOC.4”
xx = Sensor Type | yy = Insertion Length
6”
(Probe Length)
0.11 lbs. (0.050 kg)
0.21 lbs. (0.095 kg)
0.28 lbs. (0.127 kg)
18”
(Insertion Length)
0.21 lbs. (0.095 kg)
0.27 lbs. (0.122 kg)
0.34 lbs. (0.154 kg)
D. E.
8”
(Insertion Length)
0.17 lbs. (0.077 kg)
0.22 lbs. (0.100 kg)
0.29 lbs. (0.132 kg)
NIST
F.
G.
MODEL #
A/
DO
TEMPERATURE | ##
Revision C0000002 | Rev 1.0