TEMPERATURE | PLATINUM RTDS | DUCT WITHOUT BOX
DUCT WITHOUT BOX
Flange Mounted Duct Sensor, Platinum RTD
The ACI Platinum Duct without Box Series features a 1/4" diameter stainless steel sensing
element with two, 14 or 24 inch, 22 AWG Etched Teon colored lead wires to dierentiate the
dierent sensor types. The three-wire “-3W” option should be ordered if using with a 3-Wire
temperature transmitter or sensor conguration on your building management system or PLC
(Programmable Logic Controller). The purpose of the 3rd wire is to compensate for any
external lead wire resistance that will aect the accuracy of your sensors output signal. ACI
recommends the use of 18 AWG lead wires to reduce the external lead wire resistance when
using a Platinum RTD sensor and its lower sensor resolution. The sensors in this series are
manufactured using ACI’s proven double encapsulation process to eliminate the eects of
moisture upon the sensors as well as increased response times using our high quality, thermally conductive epoxy. The duct style sensor is a single
point sensor designed to be used in smaller duct applications and includes an insulation pad for properly sealing your duct as well as to dampen
vibration. Sensor length should be determined by the actual width or diameter of your duct such that the tip of the probe is in the approximate
center of the duct. On larger ducts, you may want to refer to our Rigid or Bendable Copper Averaging sensor for increased sensing points and better
temperature control. The Duct without Box Series can be ordered with optional plenum rated cables, jacket materials and standard lead lengths.
Applications: Roof Top Units, Air Handlers, Monitoring Supply/Discharge/Return/Mixed Air Temperatures
PRODUCT SPECIFICATIONS
Sensor Type | Sensor Curve:
Number Sensing Points:
Number Wires:
Sensor Output @ 0ºC (32ºF):
Sensor Accuracy @ 0ºC (32ºF):
Din Standard | Temperature Coecient:
Sensor Stability:
Response Time (63% Step Change):
Self-Heating | Maximum Operating Current:
Operating | Storage Temperature Range:
Operating Humidity Range:
Probe Material | Flange Material:
Fitting Material | Flammability Rating:
Foam Pad Material | Flammability Rating:
Lead Length | Conductor Size:
Lead Wire Insulation | Wire Rating:
Conductor Material:
Probe Diameter:
Product Dimensions | Product Weight:
Agency Approvals:
Platinum RTD | PTC (Positive Temperature Coecient)
One
A/100-2W-DO Series and A/1K-2W-DO Series: Two (Non-Polarity Sensitive)
A/100-3W-DO Series and A/1K-3W-DO Series: Three (Polarity Sensitive)
A/100-xW-DO Series: 100 Ohms nominal | A/1K-xW-DO Series: 1000 Ohms nominal
+/- 0.06% Class A (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|))
where |t| is the absolute value of Temperature above or below 0ºC in ºC)
-40ºC (-40ºF): +/- 0.23ºC (+/- 0.414ºF) | 0ºC (32ºF): +/- 0.15ºC (+/- 0.27ºF)
115ºC (239ºF): +/- 0.38ºC (+/- 0.69ºF)
DIN EN 60751(IEC 751) | 3850 ppm / ºC
+/- 0.03% after 1000 Hours @ 300ºC (572ºF)
8 Seconds nominal
100 Ohm RTD: 7 mW/ºC (Still Air) | 5 mA | 1K Ohm RTD: 4 mW/ºC (Still Air) | 3 mA
-40 to 115ºC (-40 to 239ºF) | -40 to 85ºC (-40 to 185ºF)
10 to 95% RH, non-condensing
304 Stainless Steel | Galvanized Steel
Polyamide 66 (High Performance Nylon) | UL94-HB
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
4”, 6” and 8” Probes: 14” (35.6 cm) | 12” and 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Etched Teon (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Silver Plated Copper
0.250” (6.35mm)
See table on back of Product Data sheet
CE, RoHS2, WEEE
Call: 1-888-967-5224 | Web: www.workaci.com
TEMPERATURE | ##
TEMPERATURE | PLATINUM RTDS | DUCT WITHOUT BOX
DIMENSIONAL DRAWING, WEIGHTS
Automation Components, Inc.
3.88”
(98.60mm)
1.13”
(28.74mm)
.98”
(24.89mm)
Standard Views Product Weights
STANDARD ORDERING
Model #
A/100-2W-DO-4”
A/100-2W-DO-6”
A/100-2W-DO-8”
A/100-2W-DO-12”
A/100-2W-DO-18”
A/1K-2W-DO-4”
A/1K-2W-DO-6”
A/1K-2W-DO-8”
A/1K-2W-DO-12”
A/1K-2W-DO-18”
Item #
119951
133370
119952
142486
133019
120290
133175
120291
120289
142487
.31” (7.98mm)
xx = Sensor Type | yy = Insertion Length
Duct Without Box [DO] Weights
Available in 4”, 6”, 8”,
12”, and 18” Probe
Lengths
.92” (23.47mm)
ACI Model #
A/xx-DO-yy
A/xx-DO-yy-10’-CL2P
A/xx-DO-yy-20’-CL2P
ACI Model #
A/xx-DO-yy
A/xx-DO-yy-10’-CL2P
A/xx-DO-yy-20’-CL2P
4”
(Probe Length)
0.10 lbs. (0.045 kg)
0.20 lbs. (0.091 kg)
0.27 lbs. (0.122 kg)
12”
(Insertion Length)
0.19 lbs. (0.086 kg)
0.24 lbs. (0.108 kg)
0.31 lbs. (0.141 kg)
6”
(Probe Length)
0.11 lbs. (0.050 kg)
0.21 lbs. (0.095 kg)
0.28 lbs. (0.127 kg)
18”
(Insertion Length)
0.21 lbs. (0.095 kg)
0.27 lbs. (0.122 kg)
0.34 lbs. (0.154 kg)
Model # Example:
Description
100 Ohm RTD, 2-Wire, Duct 4” w/o Box, Flange Only, 14” Brown/Brown Leads
100 Ohm RTD, 2-Wire, Duct 6” w/o Box, Flange Only, 14” Brown/Brown Leads
100 Ohm RTD, 2-Wire, Duct 8” w/o Box, Flange Only, 14” Brown/Brown Leads
100 Ohm RTD, 2-Wire, Duct 12” w/o Box, Flange Only, 24” Brown/Brown Leads
100 Ohm RTD, 2-Wire, Duct 18” w/o Box, Flange Only, 24” Brown/Brown Leads
1K Ohm RTD, 2-Wire, Duct 4” w/o Box, Flange Only, 14” Black/Black Leads
1K Ohm RTD, 2-Wire, Duct 6” w/o Box, Flange Only, 14” Black/Black Leads
1K Ohm RTD, 2-Wire, Duct 8” w/o Box, Flange Only, 14” Black/Black Leads
1K Ohm RTD, 2-Wire, Duct 12” w/o Box, Flange Only, 24” Black/Black Leads
1K Ohm RTD, 2-Wire, Duct 18” w/o Box, Flange Only, 24” Black/Black Leads
8”
(Insertion Length)
0.17 lbs. (0.077 kg)
0.22 lbs. (0.100 kg)
0.29 lbs. (0.132 kg)
A/100-2W-DO-4”
-OR-
119951
CUSTOM ORDERING
A. Sensor Series
B. Model Series
D. Conguration
Note*: All 20’ Sensors are not CE compliant, but are RoHS2 compliant
Select One (1)
No Selection Required
Select One (1)
Select One (1)
No Selection Required
Select One (1)
Select One (1)
Select One (1)
A/
100 = 100 Ohm Platinum RTD | 1K = 1K Ohm Platinum RTD
2W = Two Wires | 3W = Three WiresC. Number of Wires
DO = Duct without Box (Mounting Flange Only)
4” = 4” Probe | 6” = 6” Probe | 8” = 8” Probe | 12” = 12” Probe | 18” = 18” ProbeE. Probe Length
---- = Standard 14” or 24” Lead Length | 10’ = 10 Feet (3.05m) | 20’ = 20 Feet* (6.10m)F. Lead Length
---- = Standard Etched PTFE Colored Leads | CL2P = 2 Conductor Plenum Rated Cable G. Lead Wire Type
---- = No NIST Certicate | NIST = NIST Certicate (Must Specify 1, 3 or 5 Points)H. NIST
Model # Example:
A/
B.
A.
DOD.6” 10’
C.
E. F.
CL2P
NIST
H.
MODEL #
G.
2W
1K
A/
DO
TEMPERATURE | ##
Revision C0000002 | Rev 1.0