aci A/DLP-001-W-U-N-A-3, A/DLP-040-W-U-N-A-0, A/DLP-001-W-U-N-A-0, A/DLP-040-W-U-N-A-3, A/DLP-001-W-U-D-A-0 Installation & Operation Instructions

...
DLP SERIES
Phone: 1-888-967-5224
Website: workaci.com
PRECAUTIONS
• Do not switch pressure range and output mode when power is on. Make sure to power off the unit first, then set the DIP Switches to the correct positions and then power on the
FIGURE 1: DLP DIMENSIONS
4.35"
(110.43 mm)
2.48"
(62.99 mm)
2.23"
(56.52 mm)
transmitter.
GENERAL INFORMATION
The DLP Series is based on a piezoresistive, silicon sensing element which senses Dierential Pressure and provides an analog output. Field selectable analog outputs include 0-5 and 0-10 VDC, or 4-20 mA which correlate to a uni or bi-directional pressure range from 0-0.1” up to 0-40” of water column, depending on your model selection. Each unit has up to 8 eld selectable, uni or bi-directional ranges (see Figure 6 p. 3).
CORDGRIP / 1/2 “ CONDUIT FITTING
MEDIA
The DLP can be used to monitor the dierential pressure in any application that uses dry air or inert gas.
Mounting
Find a suitable location for the enclosure. The DLP has 2 two mounting holes located on the top and bottom anges. Drill pilot holes for the (2) #8 x 3/4” self-drilling screws(supplied). Use the enclosure ange as a guide, or use the dimensions listed in Figure 1. Mount the unit vertically with the brass ttings pointing towards the ground. This ensures that any condensation that may form in the tubing does not have an eect on the pressure sensor. If mounting the unit horizontally, a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor.
5.56"
(141.29 mm)
6.02"
(152.82 mm)
HIGH PRESSURE PORT
-H
-L
LOW PRESSURE PORT
FIGURE 2: DIN RAIL MOUNTING
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
DIN RAIL
DIN RAIL
DIN RAIL CLIP
Version: 15.0
Version: 15.0
I0000777
I0000777
DIN RAIL MOUNTING (Optional)
Attach the DIN Rail Mounting accessory to the back of the enclosure using the two screws provided. To mount the sensor on the DIN Rail, place the bottom of the DIN Rail Clip into the 35mm DIN Rail and push the unit upward to engage the spring clip. Now press the top of the unit back until it locks into place - see
FIGURE 2 (p.1).
PITOT TUBE INSTALLATION
(Optional)
Slip the rubber washer over the threaded end of the pitot tube, keeping the washer as close to the threaded end as possible. Fasten the pitot into the threaded insert on the back of the enclosure. Press the rubber washer against the enclosure - see FIGURE 3.
Tubing Setup When Pitot Tube is Installed
Units will be shipped with silicone tubing attached to the high and low pressure barb ttings. The silicone tubing will need to be removed from the High Pressure (H) barb tting and secured onto the pitot tube barb tting. This will leave the high pressure barb tting open to atmosphere, and the Low pressure barb tting remaining at default setup.
Pressure Connections
The recommended connection tubing is ¼” O.D push-on tubing (1/8” to 3/16” I.D.). For best results, all tubing lengths should be limited to a maximum length of 75 feet (23 meters). Longer runs will aect the response time.
FIGURE 3: PITOT TUBE INSTALLATION
Move Tubing from High port to Pitot tube
HIGH PRESSURE PORT
LOW PRESSURE PORT
FIGURE 5: MEASURING DIFFERENTIAL PRESSURE ACROSS FILTER
FIGURE 4: DUCT STATIC INSTALLATION
DRILL Ø 7/16” (11.1125 mm) HOLE
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
LOW
A/SPT A/VPT
POLY TUBING
HIGH
FILTER
DIRECTION OF AIR FLOW
Version: 15.0
I0000777
WIRING
PRECAUTIONS
FIGURE 6: SW1 and SW3 OUTPUT
SWITCHES
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in
Vout
mA
SW1
5V
SW3
BI
Pa
A
1 2 3 4 5
1
ON
OFF
UNI
10V
inWC
B
2
O
damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply. Without these snubbers, coils produce very large voltage spikes when de-energizing that can cause malfunction or destruction of electronic circuits.
TABLE 1: WIRING CONNECTIONS
OUTPUT SIGNAL
0-5 VDC 0-10 VDC 4-20 mA 4-20 mA
N/A = Not Applicable N/C = No Connection
OUTPUT MODE (SW1)
Vout Vout mA mA
OUTPUT SIGNAL (SW3 Position 4)
5 V 10 V N/A N/A
SUPPLY VOLTAGE
VAC/VDC VAC/VDC VDC VAC
WIRE CONNECTIONS
BLACK
RED
COM
V+
COM
V+
N/C
V+
COM
V+
WHITE
VOUT VOUT N/C N/C
YELLOW
N/C N/C IOUT IOUT
FIGURE 7: WIRING CONNECTIONS
2-Wire, 4-20 mA
DLP
YELLOW
WHITE
VOUT
BLACK
COM
Digital Controller
AI1
V+
RED
V+ IOUT
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
3-Wire, 0-5 V / 0-10 V
DLP
YELLOW
WHITE
RED
VOUT
COM
V+ IOUT
Page 3
BLACK
Digital Controller
24 VAC/DC POWER
AI1
COM
SUPPLY
-
+
Version: 15.0
I0000777
Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters. Twisted pair may be used for 2-wire current output transmitters or 3-wire for voltage output. Connect the wires to the unit’s nger push-button terminal blocks. Each DLP unit can be congured to three output signals: 4-20 mA, 0-5 V or 0-10 V. Use the Wiring Connections and diagrams to determine the proper wiring for your application. See TABLE 1 (p.3) for Output Mode and Output Signal switch positions.
Note: When using 1/2” conduit, the strain relief tting must be removed from the enclosure.
Note: Make sure that any conduit or metal ttings do not come in contact with the circuit board.
TABLE 2: STANDARD MODEL NUMBERS
OUTPUT SIGNAL
A/DLP-001-W-U-N-A-0 A/DLP-010-W-U-N-A-0 A/DLP-040-W-U-N-A-0 A/DLP-001-W-U-N-A-3 A/DLP-010-W-U-N-A-3 A/DLP-040-W-U-N-A-3 A/DLP-001-W-U-D-A-0 A/DLP-010-W-U-D-A-0 A/DLP-040-W-U-D-A-0 A/DLP-001-W-U-D-A-3 A/DLP-010-W-U-D-A-3 A/DLP-040-W-U-D-A-3
ITEM #
140769 140774 140777 141072 141074 141076 140773 140776 140778 141073 141075 141077
DESCRIPTION
0-0.1", 0.2", 0.5", 1", Without Display 0-1", 2", 5", 10", Without Display 0-10", 20", 30", 40", Without Display 0-0.1", 0.2", 0.5", 1", Without Display, With Pitot Tube and DIN Rail Clip 0-1", 2", 5", 10", Without Display, With Pitot Tube and DIN Rail Clip 0-10", 20", 30", 40", Without Display, With Pitot Tube and DIN Rail Clip 0-0.1", 0.2", 0.5", 1", With Display 0-1", 2", 5", 10", With Display 0-10", 20", 30", 40", With Display 0-0.1", 0.2", 0.5", 1", With Display, Pitot Tube, and DIN Rail Clip 0-1", 2", 5", 10", With Display, Pitot Tube, and DIN Rail Clip 0-10", 20", 30", 40", With Display, Pitot Tube, and DIN Rail Clip
ZERO FUNCTION
FIGURE 8: AUTO ZERO BUTON - SW2
The DLP unit should be “ZEROED” before pressure is applied to the unit. The zero button is used to cancel out any osets caused by installation and sensor drift. The Zero adjustment must be performed with NO pressure applied to either side of the sensor.
AUTO
ZERO
SW2
Remove the tubing connected to the H(High) and/or L(Low) pressure ttings. Push “ZERO” button for more than three seconds before installation or whenever necessary.
For units with LCD display, “AUTOZERO” icon will be on when the unit enters zero mode. If zeroing process is successful, the “AUTOZERO” icon will ash twice.
PRESSURE RANGE SELECTION
If a custom calibrated pressure range is ordered, DO NOT change the Pressure Range Selection DIP switch settings. Table 2 lists ACI’s 12 standard model #’s.
Page 4
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 15.0
I0000777
UNIDIRECTIONAL AND BIDIRECTIONAL MODE
The DLP can operate in either unidirectional mode (0 – X inWC) or bidirectional mode (± X inWC). Each unit could have up to eight eld selectable, uni or bidirectional ranges.
TABLE 3: MAXIMUM PRESSURE
ACI Part #
Maximum Pressure
(inWC)
DLP-001-W DLP-010-W DLP-040-W
1
10
40
CAUTION
See TABLE 3 for your DLP model’s maximum pressure.
DO NOT switch pressure range or output mode when POWER is ON. Make sure POWER to the
unit is OFF. Failure to do so WILL NOT ALLOW any new switch settings to take place.
Choose differential pressure range based on the expected differential pressure in your
application. Move switches to the correct positions and THEN POWER ON the transmitter.
FIGURE 9: SWITCH SETTINGS
[UNIDIRECTIONAL] DLP-001-W
0 to 1 inWC
BI
5V
Po
A 1
[UNIDIRECTIONAL] DLP-010-W
0 to 10 inWC
BI
5V
Po
A 1
[UNIDIRECTIONAL] DLP-040-W
0 to 40 inWC
BI
5V
Po
A 1
[BIDIRECTIONAL] DLP-001-W
-1 to 1 inWC
BI
5V
Po
A 1
[BIDIRECTIONAL] DLP-010-W
-10 to 10 inWC
BI
5V
Po
A 1
[BIDIRECTIONAL] DLP-040-W
-40 to 40 inWC
BI
5V
Po
A 1
UNI 10V inWC B
1 2 3 4 5
2
ON
UNI 10V inWC B
1 2 3 4 5
2
ON
UNI 10V inWC B
1 2 3 4 5
2
ON
UNI 10V inWC B
1 2 3 4 5
2
ON
UNI 10V inWC B
1 2 3 4 5
2
ON
UNI 10V inWC B
1 2 3 4 5
2
ON
0 to 0.5 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 5 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 30 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-0.5 to 0.5 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-5 to 5 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-30 to 30 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
0 to 0.2 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 2 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 20 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-0.2 to 0.2 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-2 to 2 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-20 to 20 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
0 to 0.1 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 1 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
0 to 10 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-0.1 to 0.1 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-1 to 1 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
-10 to 10 inWC
BI 5V Po
A
1 2 3 4 5
1
ON
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
UNI 10V inWC B 2
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 5
Version: 15.0
I0000777
Unidirectional Mode
DIP switch SW3 position ve set at UNI side.
DIP switch SW3 positions one and two are for Pressure Range Selection
Bidrectional Mode
DIP switch SW3 position ve set at BI side.
DIP switch SW3 positions one and two are for Pressure Range Selection.
Note: In Bidirectional mode, a value of 0 inWC will have an output equal to 50% of the output signal range
(12mA, 2.5V, 5V).
ADDITIONAL LCD FEATURES
LCD Engineering Units Adjustment
This option is ONLY for units with LCD display. Switch DIP switch SW3 position three to select Pa or inWC. If switched with power on, unit change will not take place until power is cycled.
“Out Of Range”
“OUT OF RANGE” icon will be on when dierential pressure is over or under the minimum or maximum pressure range selected. If a DLP unit is outputting “OUT OF RANGE”, please turn o the unit immediately, and check the pressure input with a gauge or other test instrument. Once the pressure has been veried, set the Pressure Range Selection DIP switch to the proper positions based upon your maximum expected dierential pressure.
CALIBRATION
DLP utilizes a digital pot for Span calibration and is factory set. There is no Span potentiometer for adjustment. In the event you require Span calibration, the unit must be sent back to ACI.
The Oset can be adjusted using the Auto Zero function discussed on pg 4. Drift is a function of stress relaxation over time and this results in the oset shifting, and not the span . Periodically re-zeroing the device will eliminate the eect of drift.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 6
Version: 15.0
I0000777
PRODUCT SPECIFICATIONS
SPECIFICATIONS
Supply Voltage:
Supply Current: Output Signals:
Response Time (0-100% FSO): Output Update Rate: Accuracy¹: Zero Function: Thermal Effects²: Proof Pressure / Burst Pressure³:
Operating Temperature Range: Compensated Temperature Range: Storage Temperature Range: Operating Humidity Range: Media Types: Enclosure Material / Flammability Rating: Wiring Connections: Conduit Knockouts: Pressure Fitting Material: Tubing Size Accepted:
Note: Accuracy includes linearity, hysteresis & repeatability @ 71°F (21.5°C) Note: Shift is relative to 71°F (21.5°C)
4-20 mA Output: 16-36 VDC (250 Ω Load max.) / 22-36 VDC (500 Ω Load max.) 0-5 VDC / 0-10 VDC Output: 16-36 VDC / 24 VAC (+/- 10%)
4-20 mA Output: 24 mA minimum | 0-5 VDC / 0-10 VDC Output: 6 mA maximum
Current Output: 4-20 mA, 2-Wire (Standard); (Current limited to 21.4 mA max) Voltage Signals: 0-5 VDC / 0-10 VDC, 3-Wire; Output limited @ 5.25 & 10.5 VDC)
8 seconds
1 second
+/- 0.5% FSO; +/- 0.25% (Only for Specied Range)
Pushbutton Zero Function
+/- 0.067% FSO / °F (0.12% FSO / °C)
A/DLP-001: Proof: 270 inWC (67.2 kPa) | Burst: 415 inWC (103.3 kPa) for 1 inWC (249.8 Pa) A/DLP-010: Proof: 350 inWC (87.12 kPa) | Burst: 550 inWC (136.9 kPa) for 10 inWC (2490.8 Pa) A/DLP-040: Proof: 562 inWC (140 kPa) | Burst: 1004.7 inWC (250 kPa) for 40 inWC (9963.6 Pa)
-4 to 185 °F (-20 to 85 °C)
32 to 122 °F (0 to 50 °C)
-22 to 185 °F (-30 to 85 °C)
10 to 95% RH, non-condensing
Dry air or inert non-conductive gases
Flame Retardant Polycarbonate; UL94-5VA
Finger Pushbutton (Spring) Terminal Blocks; accepts 16-24 AWG wires
Watertight Cordgrip Installed (1/2" NPT Conduit ttings accepted when Cordgrip removed)
Nickel Plated Brass or Stainless Steel
1/4" O.D. x 0.170" I.D. Poly Tubing
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with household waste. Do not burn.
WARRANTY
The ACI DLP is covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
Page 7
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 15.0
I0000777
Loading...