
DLP SERIES
Installation & Operation Instructions
Phone: 1-888-967-5224
Website: workaci.com
PRECAUTIONS
• Do not switch pressure range and output
mode when power is on. Make sure to power off
the unit first, then set the DIP Switches to the
correct positions and then power on the
FIGURE 1: DLP DIMENSIONS
4.35"
(110.43 mm)
2.48"
(62.99 mm)
2.23"
(56.52 mm)
transmitter.
GENERAL INFORMATION
The DLP Series is based on a piezoresistive, silicon
sensing element which senses Dierential Pressure
and provides an analog output. Field selectable
analog outputs include 0-5 and 0-10 VDC, or 4-20
mA which correlate to a uni or bi-directional
pressure range from 0-0.1” up to 0-40” of water
column, depending on your model selection. Each
unit has up to 8 eld selectable, uni or bi-directional
ranges (see Figure 6 p. 3).
CORDGRIP /
1/2 “ CONDUIT FITTING
MEDIA
The DLP can be used to monitor the dierential
pressure in any application that uses dry air or inert
gas.
Mounting
Find a suitable location for the enclosure. The DLP
has 2 two mounting holes located on the top and
bottom anges. Drill pilot holes for the (2) #8 x 3/4”
self-drilling screws(supplied). Use the enclosure ange as a guide, or use the dimensions listed in Figure 1.
Mount the unit vertically with the brass ttings pointing towards the ground. This ensures that any
condensation that may form in the tubing does not have an eect on the pressure sensor. If mounting the
unit horizontally, a slight zero shift may occur and care must be taken to prevent moisture from building
up in the sensor.
5.56"
(141.29 mm)
6.02"
(152.82 mm)
HIGH PRESSURE PORT
-H
-L
LOW PRESSURE PORT
FIGURE 2: DIN RAIL MOUNTING
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
DIN RAIL
DIN RAIL
DIN RAIL
CLIP
Version: 15.0
Version: 15.0
I0000777
I0000777

DIN RAIL MOUNTING (Optional)
Attach the DIN Rail Mounting accessory to the
back of the enclosure using the two screws
provided. To mount the sensor on the DIN Rail,
place the bottom of the DIN Rail Clip into the
35mm DIN Rail and push the unit upward to
engage the spring clip. Now press the top of
the unit back until it locks into place - see
FIGURE 2 (p.1).
PITOT TUBE INSTALLATION
(Optional)
Slip the rubber washer over the threaded end
of the pitot tube, keeping the washer as close
to the threaded end as possible. Fasten the
pitot into the threaded insert on the back of
the enclosure. Press the rubber washer against
the enclosure - see FIGURE 3.
Tubing Setup When Pitot Tube is Installed
Units will be shipped with silicone tubing
attached to the high and low pressure barb
ttings. The silicone tubing will need to be
removed from the High Pressure (H) barb
tting and secured onto the pitot tube barb
tting. This will leave the high pressure barb
tting open to atmosphere, and the Low
pressure barb tting remaining at default
setup.
Pressure Connections
The recommended connection tubing is ¼”
O.D push-on tubing (1/8” to 3/16” I.D.). For best
results, all tubing lengths should be limited to
a maximum length of 75 feet (23 meters).
Longer runs will aect the response time.
FIGURE 3: PITOT TUBE INSTALLATION
Move Tubing
from High port to
Pitot tube
HIGH PRESSURE PORT
LOW PRESSURE PORT
FIGURE 5: MEASURING DIFFERENTIAL
PRESSURE ACROSS FILTER
FIGURE 4: DUCT STATIC INSTALLATION
DRILL Ø 7/16”
(11.1125 mm)
HOLE
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
LOW
A/SPT
A/VPT
POLY TUBING
HIGH
FILTER
DIRECTION
OF AIR FLOW
Version: 15.0
I0000777

WIRING
PRECAUTIONS
FIGURE 6: SW1 and SW3 OUTPUT
SWITCHES
• Remove power before wiring. Never
connect or disconnect wiring with
power applied.
• When using a shielded cable, ground the
shield only at the controller end.
Grounding both ends can cause a ground
loop.
• It is recommended you use an isolated
UL-listed class 2 transformer when
powering the unit with 24 VAC. Failure to
wire the devices with the correct polarity
when sharing transformers may result in
Vout
mA
SW1
5V
SW3
BI
Pa
A
1 2 3 4 5
1
ON
OFF
UNI
10V
inWC
B
2
O
damage to any device powered by the
shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
TABLE 1: WIRING CONNECTIONS
OUTPUT SIGNAL
0-5 VDC
0-10 VDC
4-20 mA
4-20 mA
N/A = Not Applicable
N/C = No Connection
OUTPUT MODE
(SW1)
Vout
Vout
mA
mA
OUTPUT SIGNAL
(SW3 Position 4)
5 V
10 V
N/A
N/A
SUPPLY VOLTAGE
VAC/VDC
VAC/VDC
VDC
VAC
WIRE CONNECTIONS
BLACK
RED
COM
V+
COM
V+
N/C
V+
COM
V+
WHITE
VOUT
VOUT
N/C
N/C
YELLOW
N/C
N/C
IOUT
IOUT
FIGURE 7: WIRING CONNECTIONS
2-Wire, 4-20 mA
DLP
YELLOW
WHITE
VOUT
BLACK
COM
Digital Controller
AI1
V+
RED
V+ IOUT
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
3-Wire, 0-5 V / 0-10 V
DLP
YELLOW
WHITE
RED
VOUT
COM
V+ IOUT
Page 3
BLACK
Digital Controller
24 VAC/DC POWER
AI1
COM
SUPPLY
-
+
Version: 15.0
I0000777