aci A/CTE2-50, A/CTE2-150, A/SCTE2-150, A/SCTE2-250, A/SCTE2-50 General Information Manual

...
Page 1
VOLTAGE OUTPUT CURRENT SENSOR SERIES
Installation & Operation Instructions
Phone: 1-888-967-5224
Website: workaci.com
PRECAUTIONS
• This product is not intended to be used for Life or Safety applications.
FIGURE 1: DIMENSIONS
Solid-Core
2.36” (59.94mm)
• This product is not intended for use in any hazardous or classified locations.
• The A/CTE2, A/CTV2, A/SCTE2 and A/SCTV2 Series Current Sensors must be used on
2.77” (70.45mm)
Insulated Conductors Only.
HIGH VOLTAGE
• Disconnect and lock out all power sources before installation as severe injury or death may result from electrical shock due to contact with high voltage wires.
GENERAL INFORMATION
The Voltage Output Analog Current Sensors are designed for use in any AC current monitoring application in which
1.03” (26.16mm)
Split-Core
2.55” (64.69mm)
2.87” (72.80mm)
3.35” (84.99mm)
you are looking to monitor a particular piece of equipment for proper operation. All voltage output current sensors use an “Average” current measuring method and should be used in applications where a pure
2.77” (70.35mm)
Sinusoidal AC waveform that has very little or no distortion/noise on the conductor being monitored. Applications may include monitoring a resistive type load such as an incandescent light bulb or heating element as well as any single speed linear load. Voltage Output current sensors are available in both solid and split-core
3.24” (82.23mm)
2.87” (72.77mm)
1.10” (28.02mm)
versions which also includes a Patented 35 mm Din Rail mounting foot for easy installation in panel mount applications. The solid-core versions are a great choice for new installations or OEM applications in which cost sensitivity, lower trip points and environmental issues like dust and moisture may be of concern. The split-core version of the current sensors work great in retrot applications and for use on service technicians vehicles since one or two parts will work in most applications and can be easily installed without disconnecting any wires. For best results, the voltage output current sensors should not be used in applications with switching power supplies or variable speed drives due to the limited operating frequency range. In applications where variable speed drives or waveforms include distortion/noise, ACI recommends the use of the A/CTA2-RMS or A/SCTA2-RMS Series sensors where you need to supply 24 VDC power to the current sensors with a 4-20 mA signal. A 249 Ohm or 499 Ohm 1 Watt resistor can be used to convert the 4-20 mA signal into a useable 1-5 or 2-10 VDC output signal at your building management system or PLC.
Page 1
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Page 2
INSTALLATION
Make sure that all installations are in compliance with all national and local electrical codes. Only qualied individuals that are familiar with codes, standards, and
FIGURE 2: OPENING A/SCTV2-50 SERIES
A/SCTV2-50
proper safety procedures for high-voltage installations should attempt installation. The current sensor will not require external power, since the power for the current sensor is induced from the conductor being monitored.
The current sensor may be mounted in any position using the two #8 x ¾” Tek screws and the mounting holes in the base, or snapped directly on to the 35mm DIN rail (See Figure 3). Leave a minimum distance of 1” (3 cm) between the current sensor and any other magnetic devices such as contactors and transformers.
A/SCTV2-50
Latch Operation for A/SCTE2 and A/SCTV2 Series
Press down on the side tab and swing the top of the unit up to open the split core current sensor as shown in Figure 2. Press down rmly on the cover to close the current sensor. An audible “click” will be heard as the tab slides over the tongue on the base.
CAUTION: Mating surfaces of the magnetic core are exposed when the sensor is open. Electrical contact grease, present on the cores to prevent corrosion, can capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good contact between pole pieces. Visually check the mating parts of the core before closing the current sensor.
Current Sensor Setup
The amperage range selected represents the maximum current that can be applied to the conductor being monitored, Do not exceed! All current sensors with selectable ranges will have the range selection jumper factory set on the high range. For models with eld selectable amperage ranges, select the correct amperage range using the range selection jumper.
Note: An extra jumper shunt is included. It can be discarded if not needed.
Note: In applications where high vibrations are encountered, ACI recommends to use the jumper shunt
without tab. A pliers can help with jumper shunt installation onto the pins.
FIGURE 3: DIN RAIL INSTALLATION
Page 2
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Page 3
FIGURE 4: WIRING
(-) Signal Common
+ 0-5 or 0-10 VDC Analog Input
GND (Shield)
COM
0-5 VDC
SHIELDED CABLE
PLC, DDC or DATA Acquiation System
WIRING INSTRUCTIONS
ACI recommends the use of a two conductor 16 to 22 AWG shielded cable, copper wire only, for all Analog current sensor installations. A maximum wire length of less than 30 meters (98.4 feet) should be used between the current sensors and the Building Management System or controller. All wiring must comply with all local and National Electric Codes.
Note: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop.
When removing the shield from the sensor end, make sure to properly trim the shield to prevent any chance of shorting. The current sensor terminals are polarity sensitive and represent a linear 0 to 5 or 0 to 10 VDC output signal. Tighten the screws at the terminal block connections to the recommended torque of 0.5 to 0.6 Nm (4.43 to 5.31 in-lbs.). The aperture (hole) size of the current sensor is 0.75” (1.90 cm).
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 8.0
I0000790
Page 4
TROUBLESHOOTING
PROBLEM
No reading
Erratic readings
Inaccurate readings
Current Sensor is operating at a
low-level current or failing to operate
within the accuracy specifications.
STANDARD ORDERING
Model #
A/CTE2-50
A/CTE2-150
A/SCTE2-50
A/SCTE2-150
A/SCTE2-250
A/CTV2-50
A/CTV2-150
A/SCTV2-50
A/SCTV2-150
A/SCTV2-250
Item #
142389
142388
142385
142384
142383
142387
142386
142382
142381
142380
Selectable Ranges
0 to 10/20/50A
0 to 50/100/150A
0 to 10/20/50A
0 to 50/100/150A
0 to 100/200/250A
0 to 10/20/50A
0 to 50/100/150A
0 to 10/20/50A
0 to 50/100/150A
0 to 100/200/250A
SOLUTION(S)
- Verify that there is current owing through the conductor being monitored with a
clamp-on current probe. The power for the current sensor is induced from the conductor
being monitored.
- Check the polarity of the circuit.
- Verify that the terminals are screwed down, wires are rmly in place.
- Disconnect the wires from the current sensor output. Measure the voltage across the
current sensor output with a Voltmeter to verify that the sensor is working properly.
- Verify that the wires are terminated properly.
- In areas of high RF interference, shielded cable may be necessary to stabilize signal.
- If you suspect that the current sensor is not reading within the accuracy specications,
please contact the factory for assistance.
-Visually check the mating parts of the core to ensure there is no debris between the split
contacts. See Figure 2.
-Remove all debris or dust manually and close the current sensor.
-Continue to retest the sensor in your application.
Measurement
Average
Average
Average
Average
Average
Average
Average
Average
Average
Average
AC Waveform
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Solid-Core
Split-Core
Output Signal
0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 8.0
I0000790
Page 5
PRODUCT SPECIFICATIONS
SENSOR NON-SPECIFIC INFORMATION
Monitored Current Type:
Maximum AC Voltage:
Isolation Voltage:
Operating Frequency Range:
Core Style:
Supply Voltage:
Sensor Amperage Range:
Output Signal | Number of Wires:
Accuracy:
Response Time:
Aperture Size:
Din Rail Size:
Operating Temperature Range:
Operating Humidity Range:
Recommended Storage Temperature |
RH Range:
Enclosure Material | Flammability
Rating:
Wiring Connections:
Wire Recommendations:
Wire Size:
Terminal Block Torque Rating:
Minimum Mounting Distance:
Note:
All current output sensors are calibrated at an ambient room temperature of 71ºF (21.5ºC)
AC Current
600 VAC
2200 VAC
50 to 600 Hz
Solid-Core and Split-Core Versions available (See Ordering Grid)
Induced from the Monitored Conductor (Insulated Conductors only)
See Ordering Grid (Field Selectable)
A/CTE2 & A/SCTE2 Series: 0 to 5 VDC | A/CTV2 & A/SCTV2 Series: 0 to 10 VDC | 2-Wires
A/CTE2 & A/SCTE2 Series: (0-10A Range Only): +/- 1% from 5-100% of Selected Range
A/CTE2 & A/SCTE2 Series: (All Other Ranges): +/- 1% from 2-100% of Selected Range
A/CTV2: +/- 1% from 5-100% of Selected Range
A/SCTV2 Series: (0 to 10A Range Only): +/- 2% from 5 to 100% of Selected Range
A/SCTV2 Series: (All Other Ranges): +/- 1% from 5 to 100% of Selected Range
< 300 mS (Rise and Fall Times)
0.75” (19.05 mm)
35 mm (U.S. Patent No. 7,416,421)
5 to 104ºF (-15 to 40ºC)
0 to 95%, non-condensing
41 to 95ºF (5 to 35ºC) | 40% to 85% RH, non-condensing
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
2 Position, Screw Terminal Block (Polarity Sensitive)
2 Conductor (Shielded Cable)
18 to 24 AWG (0.823 mm to 0.205 mm) Copper Wires only
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
1” (2.6 cm) between current sensor & other magnetic devices (Relays, Contactors,
Transformers)
WARRANTY
The ACI Voltage Output Sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with household waste. Do not burn.
Page 5
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Page 6
NOTES
Page 6
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Page 7
NOTES
Page 7
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Page 8
Automation Components, Inc.
2305 Pleasant View Road Middleton, WI 53562
Phone: 1-888-967-5224 Website: workaci.com
Page 8
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
Loading...