aci A/CTE2-50, A/CTE2-150, A/SCTE2-150, A/SCTE2-250, A/SCTE2-50 General Information Manual

...
VOLTAGE OUTPUT CURRENT SENSOR SERIES
Installation & Operation Instructions
Phone: 1-888-967-5224
Website: workaci.com
PRECAUTIONS
• This product is not intended to be used for Life or Safety applications.
FIGURE 1: DIMENSIONS
Solid-Core
2.36” (59.94mm)
• This product is not intended for use in any hazardous or classified locations.
• The A/CTE2, A/CTV2, A/SCTE2 and A/SCTV2 Series Current Sensors must be used on
2.77” (70.45mm)
Insulated Conductors Only.
HIGH VOLTAGE
• Disconnect and lock out all power sources before installation as severe injury or death may result from electrical shock due to contact with high voltage wires.
GENERAL INFORMATION
The Voltage Output Analog Current Sensors are designed for use in any AC current monitoring application in which
1.03” (26.16mm)
Split-Core
2.55” (64.69mm)
2.87” (72.80mm)
3.35” (84.99mm)
you are looking to monitor a particular piece of equipment for proper operation. All voltage output current sensors use an “Average” current measuring method and should be used in applications where a pure
2.77” (70.35mm)
Sinusoidal AC waveform that has very little or no distortion/noise on the conductor being monitored. Applications may include monitoring a resistive type load such as an incandescent light bulb or heating element as well as any single speed linear load. Voltage Output current sensors are available in both solid and split-core
3.24” (82.23mm)
2.87” (72.77mm)
1.10” (28.02mm)
versions which also includes a Patented 35 mm Din Rail mounting foot for easy installation in panel mount applications. The solid-core versions are a great choice for new installations or OEM applications in which cost sensitivity, lower trip points and environmental issues like dust and moisture may be of concern. The split-core version of the current sensors work great in retrot applications and for use on service technicians vehicles since one or two parts will work in most applications and can be easily installed without disconnecting any wires. For best results, the voltage output current sensors should not be used in applications with switching power supplies or variable speed drives due to the limited operating frequency range. In applications where variable speed drives or waveforms include distortion/noise, ACI recommends the use of the A/CTA2-RMS or A/SCTA2-RMS Series sensors where you need to supply 24 VDC power to the current sensors with a 4-20 mA signal. A 249 Ohm or 499 Ohm 1 Watt resistor can be used to convert the 4-20 mA signal into a useable 1-5 or 2-10 VDC output signal at your building management system or PLC.
Page 1
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
INSTALLATION
Make sure that all installations are in compliance with all national and local electrical codes. Only qualied individuals that are familiar with codes, standards, and
FIGURE 2: OPENING A/SCTV2-50 SERIES
A/SCTV2-50
proper safety procedures for high-voltage installations should attempt installation. The current sensor will not require external power, since the power for the current sensor is induced from the conductor being monitored.
The current sensor may be mounted in any position using the two #8 x ¾” Tek screws and the mounting holes in the base, or snapped directly on to the 35mm DIN rail (See Figure 3). Leave a minimum distance of 1” (3 cm) between the current sensor and any other magnetic devices such as contactors and transformers.
A/SCTV2-50
Latch Operation for A/SCTE2 and A/SCTV2 Series
Press down on the side tab and swing the top of the unit up to open the split core current sensor as shown in Figure 2. Press down rmly on the cover to close the current sensor. An audible “click” will be heard as the tab slides over the tongue on the base.
CAUTION: Mating surfaces of the magnetic core are exposed when the sensor is open. Electrical contact grease, present on the cores to prevent corrosion, can capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good contact between pole pieces. Visually check the mating parts of the core before closing the current sensor.
Current Sensor Setup
The amperage range selected represents the maximum current that can be applied to the conductor being monitored, Do not exceed! All current sensors with selectable ranges will have the range selection jumper factory set on the high range. For models with eld selectable amperage ranges, select the correct amperage range using the range selection jumper.
Note: An extra jumper shunt is included. It can be discarded if not needed.
Note: In applications where high vibrations are encountered, ACI recommends to use the jumper shunt
without tab. A pliers can help with jumper shunt installation onto the pins.
FIGURE 3: DIN RAIL INSTALLATION
Page 2
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 8.0
I0000790
FIGURE 4: WIRING
(-) Signal Common
+ 0-5 or 0-10 VDC Analog Input
GND (Shield)
COM
0-5 VDC
SHIELDED CABLE
PLC, DDC or DATA Acquiation System
WIRING INSTRUCTIONS
ACI recommends the use of a two conductor 16 to 22 AWG shielded cable, copper wire only, for all Analog current sensor installations. A maximum wire length of less than 30 meters (98.4 feet) should be used between the current sensors and the Building Management System or controller. All wiring must comply with all local and National Electric Codes.
Note: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop.
When removing the shield from the sensor end, make sure to properly trim the shield to prevent any chance of shorting. The current sensor terminals are polarity sensitive and represent a linear 0 to 5 or 0 to 10 VDC output signal. Tighten the screws at the terminal block connections to the recommended torque of 0.5 to 0.6 Nm (4.43 to 5.31 in-lbs.). The aperture (hole) size of the current sensor is 0.75” (1.90 cm).