Ace Glass temperature controllers Operation Manual

Page 1
Catalog Number Page
□ 12102-12 ............ 4
□ 12103-05
............ 5
□ 12105-14 ............ 6
□ 12106-10 ............ 7
□ 12107-20 ............ 8
□ 12107-46 ............ 9
□ 12108-13 ............ 10
□ 12110-06 ............ 11
□ 12111-15 ............. 8
□ 12111-47 ............. 9
□ 12113-17 ............. 8
□ 12113-50 ............ 9
□ 12125-14 ............. 12
□ 12126-24 ............ 13
□ 12127-30 ............ 14
BULLETIN 0612
IMPORTANT!
or greater than the Temperature Controller
output outlet used.
The sensor circuit  on all ACE Temperature Controllers  has been isolated from the power input lines in order to  protect the operator from electrical shock due to earth   ground return when handling the sensor assembly. This  also protects the sensitive amplier circuit from burnout  due to the same possible short circuit to ground. 
Unfortunately, shock hazard still exists while handling  the output leads when  connecting  the  heater circuits.  It is advisable, therefore, that the power cord be discon­nected from the  120v  source, or at the very least, the  MAIN  POWER  SELECTOR  SWITCH  be  in  the “OFF”  position during setup of the controller system. 
Due to high overall wattage capabilities of the control ler, the only way to obtain total isolation is to incorporate  a line voltage isolation transformer. This would, however, prove to be extremely bulky and 
expensive. 
-
Page 2
SAFETY
and ACE Temperature Controllers
We at  ACE  take  pride  in  producing a  reliable,  rugged and precise line of temperature control  instruments.  These  controllers  are  designed  and constructed utilizing state-of-the-art  com ponents that  are  sized for  long-term  reliability  and safety.
The standard laboratory controller, such as ACE  Models  12102,  12103,  12105, 12106, 12108,  12110, 12125, 12126, 12127 and several of other  manufacturers, has one component —  a Solid  State Relay, a Triac or a Mechanical Relay — that  controls the output to the heated medium. If any  of these or  one  of  many  auxiliary compo were to  fail  and  short-out,  which  is usually case,  thermal  runaway will  occur, creating,  at  the very least, a dangerous situation such as a  re hazard. Therefore, no matter how reliable a  controller might be, it should never be left run ning unattended  for long periods of  time;  e.g.,  1/2 hour to continuous.
If it is necessary to operate for extended periods  of  time,  then  for  SAFETY, a  second  controller  having ON-OFF output should be utilized. This  secondary controller’s limiting output should be adjusted by the setpoint to a temperature above  the primary  controller’s setpoint  (+10°) and  the secondary’s output used as a power source of 120  volts for the primary controller. Thus, using two  controllers with two sensors and two Solid State 
nents 
 the 
Relay components greatly reduces the chance of  thermal runaway since both would have to fail.
ACE Controllers can be set to ON-OFF output 
­by  adjusting  the  proportional  band  to  zero  as 
described in the operating instructions furnished  with the controllers.
Controllers with one temperature probe sensor  that will protect your heated medium from thermal  runaway are available from ACE. Models 12107,  12111 and 12113 have  Alarm  HI and Alarm LO  setpoints providing an  alarm  tracking band  of  ±15°C  (user  adjustable)  around  the  setpoint.  These alarm setpoints shut off the output to the  heater by  an additional relay in  series with the  main control relay. These alarm setpoints, when  properly  adjusted,  provide  over-temperature  protection for a thermal runaway problem. This 
-
includes sensor-out-of-medium protection only  after system does reach setpoint.
In  addition,  these  controllers  have  a  rear  AL2  output that offers a 120 volt source for powering  a sound device, motors, solenoid valve, etc., all  of which may be utilized to react to a runaway  temperature situation. 
We can customize  controllers for your needs.
Knowing the potential  hazards  of  thermal  run­away, we at ACE have designed the safest and  most reliable temperature controllers available.
WARNING:
or endanger personnel, a second redundant limit controller is recommended
In any critical application where failure could cause product loss
All ACE Temperature Control outputs are rated for resistive loads ONLY.
No transformers or autotransformers can be plugged into these outputs.
Damage to the controller could result.
Page 3
HELPFUL HINTS
For Better General Laboratory Temperature Control Operation
1. Temperature medium must be  stirred or  agitated  well  for  close control of temperatures.
2. Immersion  temperature  probe  must  be  at least  1"  into  medium for proper control.
3. Keep  probe  plug  connectors  clean  by  using  ne  emery  paper and/or electrical cleaning uid. Make sure plugs are  fully inserted, especially phone jacks.
4. The  selected  voltage  output of  the  temperature control ler must  heating element.
5. The average temperature rise-time from starting temperature  to setpoint temperature should be in the 2° to 3°C per minute  range. Methods to achieve reduced overshoot:
a) Use controllers with multiple selection output voltages. b) 
NOT exceed the  maximum  voltage  rating  of  the  
In some situations you can use a line voltage autotrans­former to power the input to your temperature controller to  100 volts and even lower without affecting controller per formance, thereby reducing the voltage to your heater.
WARNING!  DO  NOT  plug  autotransformer  into   
the output of your temperature controller to reduce  voltage output. Repeated proportional switching of  the autotransformer can and will cause damage to  your controller circuitry in most cases.
c) Commercially available solid  state line voltage  controls 
such as ACE Cat. No. 13530-10 can be plugged into the  output of a proportional temperature controller to reduce  power to your heater.
d) Generally, properly  sized  heaters  for the  vessel  being 
heated will normally achieve proper temperature rise time,  such as ACE Instatherm
e) In  some  instances,  trying  to  heat  large  vessels  at  low 
temperatures, above yet near room ambient, will neces sitate using some of the previously mentioned voltage-  or  power-reducing  methods.  Controller  Models 12107,  12108, 12110, 12111, 12125, 12126,  and 12127 have  an  automatic rate circuit which helps regulate rise-time, and  the ramp and soak feature on these controllers can also  help. The factory setting for SP1 output high limit is 68%  for 
normal heating conditions. If you encounter a problem  of overshooting the SP1 setpoint or if cycling around the  SP1  setpoint  becomes  a  problem,  it is  usually  due  to  over-powered heaters or low setpoint temperatures. To  adjust for this limited problem, reduce the SP1 output high  limit setting (S1OH). See page 31 of the O.E.M. Manual.  Adjust between 68% (factory setting) to  30% for better  overall controller performance if this problem has been  encountered. 
  A good guideline is to keep the maximum % output to no 
more than four times the power % needed to maintain the  setpoint. Estimate % output by the Demand Light  out of the factory-set ten-second cycle time, or see page  25 of the O.E.M. Manual (PCTO)
®
.
ON time 
.
Please note: Adjustment of (S1OH) could need increas-
ing above  68%  for  high-temperature  use.  Contact  Ace 
-
-
-
Glass Electronics Dept. if difculty arises in making these  changes. Remember, regulating the rise-time helps limit  overshoot and  reduces temperature differentials across  glass vessel walls, which is good safety practice.
f )  A good practice, especially on initial start-ups, is to set 
the setpoint lower  than  the  temperature  needed  (5°  to  25°C less), then increase the setpoint after the lower set temperature  is reached.  This  helps  lessen  overshoot,  yet you still get  good heat-up rate which is  sometimes a necessity. This practice of an initial lower setpoint is almost a must with standard proportional controllers, especially NON-PID units (e.g. 12102, 12103, 12105 and 12106).
  6. Use  of  line  lters  and  surge suppressors to  power  your  temperature controller is recommended.
  7. Keep  controller case  in  a  clean,  vented,  room-ambient  temperature area, if possible.
  8. 
Properly sized fuses for heater and temperature controller protection are a must. Very fast acting fuses are supplied  with  ACE  Controllers  and  replacements  are  available  from  ACE  to  protect  your  equipment  investment;  see  ACE Temperature Controller Bulletin or contact your ACE Salesperson. These fuses are higher cost than the regular blow  fuse  but  they  are worth  it!  Also,  when  constantly  heating  small  vessels  with  less than  10  amperes  drain,  a 10  ampere very  fast acting fuse  would be appropriate.  On most  ACE  Temperature Controllers panel fuse would be the one to change from 15 amperes  to 10 ampere value. The 15 ampere is standard since the  majority  of  heaters used  are  rated so  near  10  amperes  that  false  blows  would  occur. The  top  rear  15 ampere  primary should not be changed.
1
On the ACE Nos. 12107 -20, 12111-15 and 12113 -17  Controllers, the top fuse is the one to change. The bot tom fuse is a three ampere regular blow alarm output  fuse. Check your controller instructions for the  replacement of the output or secondary fuse  proper fuse for the size of the heater amperes
  Since  supplying  these  very  fast  acting  fuses,  we  have
seen a reduction of approximately 90% in Instatherm heater burnout normally due to “over-voltaging.” This is a big sav ings in time, money and product loss.
  9. Temperature control units  with  alarm bands must be set  properly.  The  12107, 12111 and  12113  ACE  Controllers  automatically make the adjustment of the Alarm setpoints.  Factory set at ±15°C; can be changed when necessary.
10. Allow sufcient time for Auto Tune type Controllers to tune  themselves by doing a trial run or by having a Setpoint  perature 25°C or more above the starting temperature.
11.
 Refer  to ACE  Quick  Reference  menu  sheets  to follow  
OEM Manual.
12. Always  read  instructions  rst  and  call  ACE GLASS  INC.  (Electronics Dept.) if any questions arise.
1
 the  bottom  rear  
3
-
proper 
and use 
.
-
Tem-
Page 4
Operating Instructions for
12102-12 Temperature Controllers
(RTD INPUT SENSOR)
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself with the features
of your new ACE Temperature Controller.
FRONT PANEL:
Locate large CONTROL KNOB in upper center   of panel. In lower left corner is  SELECTOR, ON (A.C. Power)/OFF SWITCH.   Above power switch is the  CONNECTION for connecting RTD Sensor.   To the immediate right of the power switch is a  red 
INPUT POWER INDICATING LIGHT indicating   line power to controller. In lower right corner see  the front  Above outlet is the 
LIGHT that indicates power output to heater. 
0-120V OUTLET for connecting heater.  
OUTPUT POWER DEMAND
MAIN POWER
DETECTOR
Control
Knob
Input
Sensor
Jack
REAR PANEL:
Lower left, locate two fuse holders: both are fast   acting 15 amp fuses for input (top) and output  (bottom) circuits.  10 amp for lower current heaters. Bottom center is a  second output outlet for 120 volts, 15 amps maximum  loads such as oil baths, mantles, etc. To the right  bottom is the power cord for 120 volts, 15 amps  maximum power input.
Note! Output can be changed to  
OPERATION
CONTROLS 120 VOLT HEATERS ONLY!
1. Turn MAIN POWER SELECTOR SWITCH  
to “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. Connect 120v heater to front or rear outlet, i.e., 
oil bath, mantle, etc. Watch heater voltage rating!
4. Connect sensor to DETECTOR CONNECTION  
and immerse probe into liquid to be heated.  A convenient method of holding sensor in oil  baths is via 9601-30 Holder Clip.
Main
Power
Selector
Switch
Input Power
Indicating Light
0-120v Outlet
5. Plug POWER CORD into line source.
6. Switch MAIN POWER SELECTOR SWITCH to  A.C. Power. INPUT POWER INDICATING LIGHT  should light.
7. Turn CONTROL KNOB to desired temperature. OUTPUT POWER DEMAND LIGHT will indicate  heating.
Output
Power
Demand
Light
4
Page 5
Operating Instructions for
12103-05 Temperature Controllers
(RTD INPUT SENSOR)
CONTROLS 20, 40 & 120 VOLT HEATERS
Before beginning, take some time to familiarize yourself
with the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate large CONTROL KNOB   in upper center of panel.  In lower left corner is 
MAIN
Control
Knob
POWER SELECTOR, ON (A.C. Power)/OFF SWITCH. Above  
power switch is the 
DETECTOR
CONNECTION for connecting RTD 
Input
Sensor
Jack
Sensor. To the immediate right of  the power switch is a red  POWER INDICATING LIGHT  indicating line power to controller.  In lower right corner see the front 
INPUT
Main
Power
Selector
Switch
0-20V or 0-40V OUTLET for  connecting heater. To the left of  outlet is output voltage selector  switch. Above outlet is the  POWER DEMAND LIGHT that  indicates power output to heater. 
OUTPUT
Input Power
Indicating Light
40v/ Off/ 20v
Selector Switch
OPERATION
FOR 0-20 OR 0-40 VOLTAGE LIMITS FOR 0-120 VOLTAGE LIMITS
1. Turn MAIN POWER SELECTOR SWITCH to “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. Connect FRONT OUTLET to heater, i.e., oil bath, mantle, etc.
4. 
Select desired voltage limit and switch front toggle,  to left of front outlet, to proper position. Watch heater
voltage rating!
5. Connect sensor to DETECTOR CONNECTION and immerse  probe into liquid to be heated. A  sensor in oil baths is
6. Plug POWER CORD into 120v line source. 
7. Switch MAIN POWER SELECTOR SWITCH to “Front Outlet.”  INPUT POWER INDICATING LIGHT should light.  (Note! If switch is accidentally turned to “Rear Outlet,”   the front outlet will not be activated.)
8. Turn CONTROL KNOB to desired temperature.  OUTPUT POWER DEMAND LIGHT will indicate heating,  blinks within proportional band, and goes out when set  temperature is exceeded.
 via 9601-30 Holder Clip.
convenient method of holding 
located  
REAR PANEL:
Lower left, locate two fuse  holders: both are fast acting  15 amp fuses for input (top)  and output (bottom) circuits.  Note! Output can be changed t
o 10 amp for lower current  heaters. Bottom center is an output outlet for 120v, 15 amps maximum loads such as oil  baths, mantles, etc. To the  right bottom is the power  cord for 120 volts, 15 amps  maximum power input.
Output Power Demand Light
0-20v/0-40v Outlet
1. Turn MAIN POWER SELECTOR SWITCH   to “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. Connect REAR OUTLET to heater, i.e., oil bath,  mantle, etc. 120v type heaters, only.
4. Connect sensor to DETECTOR CONNECTION  and immerse probe into liquid to be heated.  A convenient method of holding sensor in oil  baths is via 9601-30 Holder Clip.
  (
IMPORTANT! To avoid damage, never disconnect  sensor while MAIN POWER SELECTOR SWITCH  is energized.)
5. Plug POWER CORD into 120v line source. 
6. Switch MAIN POWER SELECTOR SWITCH  to 
“Rear Outlet.” INPUT POWER INDICATING   LIGHT should light. ( turned to “Front Outlet,” the rear outlet will not  be activated.)
7. Turn CONTROL KNOB to desired temperature.  OUTPUT POWER DEMAND LIGHT will  indicate heating.
Note! If switch is accidentally 
5
Page 6
Operating Instructions for
12105-14 
Temperature Controllers
(RTD INPUT SENSOR)
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself with the features
of your new ACE Temperature Controller.
FRONT PANEL:
Locate  window in upper center.  Immediately below window  is  left corner is 
DIGITAL READOUT 
CONTROL KNOB. In lower  
MAIN POWER SELECTOR, ON (Power)/OFF SWITCH. Above power switch is 
the 
DETECTOR CONNECTION  for connecting RTD Sensor.  To the immediate right of the  power switch is a red 
INPUT
POWER INDICATING LIGHT 
indicating line power to controller.  In lower right corner see the front  0-120V OUTLET for connecting  heater. Above outlet is the 
OUTPUT POWER DEMAND LIGHT that indicates power  
output to heater. 
Digital Readout Window
Control
Knob
Input
Sensor
Jack
Main Power
Selector
Switch
Input Power
Indicating Light
0-120v Outlet
Output Power Demand Light
OPERATION
CONTROLS 120 VOLT HEATERS ONLY!
REAR PANEL:
Upper left, locate two fuse  holders: both are fast acting  15 amp fuses for input (top)  and output (bottom) circuits.  Note! Output can be changed  to 10 amp for lower current  heaters. Upper center is a  secondary output outlet for  120 volts, 15 amps maximum  loads such as oil baths,  mantles, etc. To the right is the power cord for 120 volts, 15  amps maximum power input.
1. Turn MAIN POWER SELECTOR SWITCH   to “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. Connect 120v heater to front or rear outlet, i.e.,  oil bath, mantle, etc. 120 volt type heaters, only.
4. Connect sensor to DETECTOR CONNECTION  and immerse probe into liquid to be heated.  A convenient method of holding sensor in  oil baths is via 9601-30 Holder Clip.
5. Plug POWER CORD into line source.
6. Switch MAIN POWER SELECTOR SWITCH  to A.C. Power. INPUT POWER INDICATING  LIGHT should light.
7. Turn CONTROL KNOB to desired temperature. OUTPUT POWER DEMAND LIGHT will indicate  heating, blinks within proportional band, and  goes out when set temperature is exceeded.
6
Page 7
Operating Instructions for
12106-10 
Temperature Controllers
(RTD INPUT SENSOR)
Digital
Readout
Window
CONTROLS 20, 40 & 120 VOLT HEATERS
Before beginning, take some time to familiarize yourself
with the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate DIGITAL READOUT WINDOW in upper center. Immediately below  window is  center of panel. In lower left corner  is 
(A.C. Power)/OFF
Above power switch is the  SENSOR JACK for connecting RTD  Sensor. To the immediate right of the  power switch is a red  INDICATING LIGHT indicating line  power to controller. In lower right  corner see the front  OUTLET for connecting heater.   To the left of outlet is 40V/OFF/20V
SELECTOR SWITCH. 
CONTROL KNOB in upper 
MAIN POWER
SELECTOR, ON
SWITCH.  
INPUT
INPUT POWER
0-20V/0-40V
Above outlet is the  POWER DEMAND LIGHT that  indicates power output to heater. 
REAR PANEL:
Lower left, locate two fuse   holders: both are fast acting  15 amp fuses for input (top)  and output (bottom) circuits.  Note! Output can be changed   to 10 amp for lower current heaters.  Bottom center is an output outlet  for 120 volts, 15 amps maximum  loads such as oil baths, mantles,  etc. To the right bottom is the  power cord for 120 volts, 15 amps  maximum power input.
OUTPUT
Main
Power
Selector
Switch
Control
Knob
Input
Sensor
Jack
Input Power
Indicating
Light
OPERATION
FOR 0-20 OR 0-40 VOLTAGE LIMITS FOR 0-120 VOLTAGE LIMITS
Selector
Switch
Output
Power
Demand
Light40v/Off/20v
0-20v/0-40v
Outlet
1. Turn MAIN POWER SELECTOR SWITCH to “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. 
Connect FRONT OUTLET to heater, i.e., oil bath, mantle, etc.
4. S
elect desired voltage limit and switch front toggle,
to left of front outlet, to proper position.
5. Connect sensor to DETECTOR CONNECTION and immerse  probe into liquid to be heated. A  holding sensor in oil baths is
6. Plug POWER CORD into 120v line source. 
7. Switch MAIN POWER SELECTOR SWITCH to  INPUT POWER INDICATING LIGHT (Note! If switch is accidentally turned to “Rear Outlet,”   the front outlet will not be activated.)
8. Turn CONTROL KNOB to desired temperature.  OUTPUT POWER DEMAND LIGHT will indicate heating,  blinks within proportional band, and goes out when  set temperature is exceeded.
convenient method of 
 via 9601-30 Holder Clip.
 should light.  
 located 
“Front Outlet.” 
1. Turn MAIN POWER SELECTOR SWITCH to   “Off” position.
2. Turn the CONTROL KNOB to position “0.”
3. Connect REAR OUTLET to heater, i.e., oil bath,  mantle, etc. 120v type heaters, only.
4. Connect sensor to DETECTOR CONNECTION  and immerse probe into liquid to be heated.  A convenient method of holding sensor in oil baths  is via 9601-30 Holder Clip.
(IMPORTANT! To avoid damage, never disconnect 
sensor while MAIN POWER SELECTOR SWITCH  is energized.)
5. Plug POWER CORD into 120v line source. 
6. Switch MAIN POWER SELECTOR SWITCH to  “Rear Outlet.” INPUT POWER INDICATING LIGHT should light. ( “Front Outlet,” the rear outlet will not be activated.)
7. Turn CONTROL KNOB to desired temperature.  OUTPUT POWER DEMAND LIGHT will indicate  heating, blinks within proportional band, and goes  out when set temperature is exceeded.
Note! If switch is accidentally turned to 
7
Page 8
Operating Instructions for
12107-20, 12111-15, 12113-17 
Temperature Controllers
(RTD SENSOR or TYPE “J” OR “K” THERMOCOUPLE)
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself
with the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate the square module at top   with digital display (lighted only when  power is on) that has two sets of  four digits: the Process Temperature  (PV) value above and the Setpoint  Temperature (SV) value below;  this is the MAIN DISPLAY of the Display, locate small square  lights 
labeled SP1, SP2, AL, °F., °C. These lights will be on or blinking  when their functions are active.  Below the display are four keypads  labeled 
buttons labeled 
module is the INPUT SENSOR JACK and below the Jack is the 
1. 
  2. 
  3. 
  4. 
  5. 
  6. 
  7. 
 (INDEXAL),  , AL, and 
 (ENTER). Above these, find two 
. Below and to the left of the 
Plug appropriate sensor plug into the Controller Jack  labeled for Types RTD, “J” or “K,” and insert probe into  medium to be heated. 
Plug controller power cord into 120v source. 
Flip main power switch up to ON position.   Controller Module will light up on main display.
Main display shows PROCESS TEMPERATURE (top);  bottom shows SETPOINT TEMPERATURE (SP1).  (Wait for self test to complete.)
Press INDEX key once and using up ( ) and down ( )  arrows, adjust SP1 value in top display to desired  setpoint temperature. Then push ENTER key to enter 
(Note that lower display identifies SP1 value.)
value. 
Press INDEX key again and appearing is the SP2 factory­set value of 5°C and identified in display. This value is the  tracking band for over-temperature cutoff back-up with  an additional series S.S.R. Push INDEX once again for  main display. When there is output, the larger orange  demand light will light. SP2 of 5.0° should not be changed.
If Diagnostic Error Message appears, see OEM Manual  (pages 38 and 39). Correct condition: reset by cycling  main power switch or pressing Index and Enter keys  simultaneously for 5.0 seconds.
 MAN and HLD 
. T
o the top 
Input
Sensor
Jack
SP1, AL,
etc.
Main
Display
Main Power
Selector Switch
OPERATION
  8. 
Plug heater into front outlet only.  Note! The top display PV value should be increasing.
 9.  Plug buzzer, valve, motor, etc. into rear outlet. This outlet  will energize only when an alarm condition happens, such  as a bad sensor, fuse, heater, S.S.R., or if any parameters are out of factory-set limits. Alarm band is automatically  set for ±15°C track of SP1 setpoint and when exceeded  will cut off both SP1 and SP2 solid state relay outputs.
10.
  Sixteen segment ramp and soak feature, see manual. 
Fuzzy logic feature is factory set.
Note: Controller is  factory  programmed  for  normal  heating  situations  for  controlling  resistive  type  heaters  and should  not need any further programming. See OEM Manual for any  additional  options  which  are  available  to  you to  make  the  controller match your needs. Contact ACE GLASS Electron ics Dept. for consultation in programming changes for your  situation. The OEM Manual  is  a  valuable guide and  lists  all  menu choices  used by  ACE in programming. Refer to  ACE  Quick Reference sheets to follow OEM Manual.
8
Index,
Enter
etc.
Output
Power
Demand
Light
0-120v Outlet
MAIN POWER SWITCH. To the   far right of the Switch is the  OUTPUT OUTLET (15 amps max.)  Above the Output Outlet is a large  orange DEMAND LIGHT which will  blink around setpoint, is off above  setpoint and full on below setpoint.
120V
REAR PANEL:
Top left fuse holder is a main fast  acting 15 amp fuse for heater; below is a three amp regular blow fuse for  the alarm output and control circuits. Bottom center is the alarm outlet  for 120 volts, three amps maximum  loads such as buzzers, valves,  motors, etc. To the right is the  power cord for 120 volts, 15 amps  maximum power input.
-
Page 9
Operating Instructions for
Main Display
12107-46, 12111-47, 12113-50 
Temperature Controllers
(RTD SENSOR or TYPE “J” OR “K” THERMOCOUPLE)
CONTROLS 20, 40 & 120 VOLT HEATERS
Before beginning, take some time to familiarize yourself
with the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate the square module at top   with digital display (lighted only when power is on) that has two sets of  four digits: the Process Temperature  (PV) value above and the Setpoint  Temperature (SV) value below; this   is the MAIN DISPLAY. To the top of   the Display, locate small square  lights labeled SP1, SP2, AL, °F., °C. These lights will be on or blinking  when their functions are active.  Below the display are four keypads  labeled   (INDEXAL),  , AL, and 
 (ENTER). Above these, find   two buttons labeled   MAN and   HLD  . Below and to the left of  the module is the INPUT SENSOR
JACK and below the Jack is the  MAIN POWER SWITCH. To the right  of the Switch is a 40V/OFF/20V SWITCH that controls Front Output 
Outlet (15 amps max.) only,   located to the far right. Between   the two switches is a red pilot  MAIN ON LIGHT. Above the   Output Outlet is a large orange  OUTPUT POWER DEMAND   LIGHT which will blink around  setpoint, is off above setpoint   and full on below setpoint.
REAR PANEL:
Top left fuse holder is a three   amp regular blow fuse for the alarm  control circuits and alarm 120v  output. Bottom left, find two fuse  holders. Top fuse is primary   (15 amp fast acting), bottom fuse is  secondary (fast acting 10A or 15A).  To the right is a 120v output outlet.  To the far right is the power cord for  120 volts, 50/60 Hz., 15 amps  maximum power input.
SP1,
AL,
etc.
Input
Sensor
Jack
Main
Power
Selector
Switch
Input Power
Indicating Light
Note: Controller is factory  programmed for 
normal  heating  situations  for  controlling   resistive type  heaters  and  should  not need  any further programming. See OEM Manual  for any additional options which are available to  you  to  make  the  controller  match your needs. Contact ACE GLASS Electronics Dept. for consultation in programming changes for  your situation. The OEM Manual is a valuable guide and lists all menu choices used by ACE  in programming. Refer to ACE Quick Refer­ence sheets to follow OEM Manual.
Index,
Enter,
etc.
Output Power
Demand
Light
0-20v/0-40v
Outlet
40v/OFF/20v
Selector
Switch
OPERATION
1. Plug appropriate sensor plug into the Controller Jack 
labeled for Types RTD, “J” or “K,” and insert probe into  medium to be heated. 
2. Plug controller power cord into 120v source. 
3. 
FOR 0-20 and 0-40 VOLTAGE LIMIT:  Switch MAIN POWER SELECTOR SWITCH to   “Front Outlet.” INPUT POWER INDICATING LIGHT   should light. (Note! If switch is accidentally turned to   “Rear Outlet,” the front outlet will not be activated.)
FOR 0-120 VOLTAGE LIMIT: Switch MAIN POWER 
SELECTOR SWITCH to “Rear Outlet.” INPUT POWER  INDICATING LIGHT should light. (Note! If switch is  accidentally turned to “Front Outlet,” the bottom rear  heater outlet will not be activated.)
4. Main display shows PROCESS TEMPERATURE (top); 
bottom shows SETPOINT TEMPERATURE (SP1). 
(Wait for self test to complete.)
5. Press INDEX key once and using up ( ) and down ( ) 
arrows, adjust SP1 value in top display to desired setpoint temperature. Then push ENTER key to enter value.  
(Note that lower display identifies SP1 value.)
6.  Press INDEX key again and appearing is the SP2 factory-  set value of 5°C and identified in display. This value is the  tracking band for over-temperature cutoff back-up with an  additional series S.S.R. Push INDEX once again for main  display. When there is output, the larger orange demand   light will light. SP2 of 5.0°C should not be changed.
  7. If Diagnostic Error Message appears, see OEM Manual  (pages 38 and 39). Correct condition: reset by cycling   main power switch or pressing Index and Enter keys  simultaneously for 5.0 seconds.
  8. Plug heater into appropriate outlet.  Note! The top display PV value should be increasing.
  9.  Plug buzzer, valve, motor, etc., into top rear alarm outlet.   This outlet will energize only when an alarm condition  happens, such as a bad sensor, fuse, heater, S.S.R.,   or if any parameters are out of factory-set limits.   Alarm band is automatically set for ±15°C track of SP1  setpoint and when exceeded will cut off both SP1 and   SP2 solid state relay outputs.
10. Sixteen segment ramp and soak feature, see O.E.M.  Manual, pages 25-26. Fuzzy logic feature is factory set.
9
Page 10
Operating Instructions for
12108-13 
Temperature Controllers
(TYPE “J” THERMOCOUPLE )
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself
with the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate the square module at top   with digital display (lighted only   when power is on) that has two   sets of four digits: the Process  Temperature (PV) value above and  the Setpoint Temperature (SV) value  below; this is the MAIN DISPLAY.   To the left of the Display, locate   small square lights labeled SP1,   AL, SP2, °F., °C. These lights will be  on or blinking when their functions  are active. Below the display are  keypads labeled   (INDEXAL),  
, AL, and   (ENTER). Below and  to the left of the module is the INPUT SENSOR JACK and below the Jack  is the MAIN POWER SWITCH.
SP1, Al,
etc.
Input
Sensor
Jack
Main Power
Selector Switch
OPERATION
CONTROLS 120 VOLT HEATERS ONLY!
1. Plug sensor plug into the Controller Jack labeled for  
Type “J” and insert probe into medium to be heated. 
2. Plug controller power cord into 120v source. 
3. Switch MAIN POWER SELECTOR SWITCH to  
AC Power. Control module should light. 
(Wait for self test to complete.)
4. Main display shows PROCESS TEMPERATURE (top); 
bottom shows SETPOINT TEMPERATURE (SP1).
5. Press INDEX key once and using up ( ) and down ( ) 
arrows, adjust SP1 value in top display to desired  setpoint temperature. Then push ENTER key to enter  value. (Note that lower display identifies SP1 value.)
6. Press INDEX key again and appearing is the SP2.  
This function is not used. Push again. You are back to  main display.
Main Display
Index, Enter,
etc.
To the far right is the 0-120V OUTLET. Above the Output Outlet  is a large orange OUTPUT POWER DEMAND LIGHT that is full on 
indicating heating, blinks within  proportional band, and goes out  when set temperature is exceeded.
REAR PANEL:
Output
Power
Demand
Light
0-120v
Outlet
7. If Diagnostic Error Message appears, see OEM Manual  (pages 38 and 39). Correct condition: reset by cycling  main power switch or pressing Index and Enter keys  simultaneously for 5.0 seconds.
8. Plug heater into a convenient front or rear outlet.   The top display PV value should be increasing. 
Watch heater voltage rating!
Note: Controller is  factory  programmed  for  normal  heating  situations  for  controlling  resistive  type  heaters  and should  not need any further programming. See OEM Manual for any  additional  options  which  are  available  to  you to  make  the  controller match your needs. Contact ACE GLASS Electron ics Dept. for consultation in programming changes for your  situation. The OEM Manual  is  a  valuable guide and  lists  all  menu choices  used by  ACE in programming. Refer to  ACE  Quick Reference sheets to follow OEM Manual.
Top left, nd two fuse holders.   Top fuse is primary (15 amp fast  acting); bottom fuse is secondary  (fast acting 10A or 15A). 
To the right is a 120v output outlet.   To the far right is the power cord  for 120 volts, 50/60 Hz., 15 amps  maximum power input.
-
10
Page 11
Operating Instructions for
12110-06 
Temperature Controller
(TYPE “J” THERMOCOUPLE )
CONTROLS 20, 40 & 120 VOLT HEATERS
Before beginning, take some time to familiarize yourself with
the features of your new ACE Temperature Controller.
FRONT PANEL:
Locate the square module at top   with digital display (lighted only   when power is on) that has two   sets of four digits: the Process   Temperature (PV) value above   and the Setpoint Temperature   (SV) value below; this is the   MAIN DISPLAY. To the left of the  Display, locate small square lights  labeled SP1, AL, SP2, °F, °C.   These lights will be on or blinking  when their functions are active.   Below the display are keypads   labeled   (INDEXAL),  , AL,   and   (ENTER). Below and to   the left of the module is the INPUT SENSOR JACK and  Jack is the MAIN POWER To the right of the Switch is a   40V/OFF/20V SELECTOR SWITCH  that controls front 0-20V/ OUTLET (15 amps max.) only, to the far right. Between the two 
below the  
SWITCH.
0-40V
 located 
switches is a red pilot  LIGHT. Above the Output Outlet is   a large orange OUTPUT POWER DEMAND LIGHT which will blink  around setpoint, is off above  setpoint and full on below setpoint.
REAR PANEL:
Bottom left, nd two fuse holders.  Top fuse is primary (15 amp fast  acting): bottom fuse is secondary  (fast acting 10A or 15A). To the   right is a 120v output outlet.  To the far right is the power cord   for 120 volts, 50/60 Hz., 15 amps  maximum power input.
Note: Controller is factory programmed for normal heating situations for con­trolling resistive type heaters and should not need any further programming.  See OEM Manual for any additional options which are available to you to make  the controller match your needs. Contact ACE GLASS Electronics Dept. for  consultation in programming changes for your situation. The OEM Manual  is a valuable guide and lists all menu choices used by ACE in programming.  Refer to ACE Quick Reference sheets to follow OEM Manual.
MAIN ON
Input
Sensor
Jack
Main
Power
Selector
Switch
SP1, Al,
etc.
Input Power
Indicating Light
Main Display
Index, Enter,
etc.
Output
Power
Demand
Light
0-20v/0-40v
Outlet
40v/Off/20v
Selector
Switch
OPERATION
1. Plug sensor plug into the Controller Jack labeled for  Type “J” and insert probe into medium to be heated. 
2. Plug controller power cord into 120v source. 
3. FOR 0-20 and 0-40 VOLTAGE LIMIT:  Switch MAIN POWER SELECTOR SWITCH to   “Front Outlet.” INPUT POWER INDICATING LIGHT   should light. (Note! If switch is accidentally turned to  “Rear Outlet,” the front outlet will not be activated.)
FOR 0-120 VOLTAGE LIMIT:  
Switch MAIN POWER SELECTOR SWITCH to   “Rear Outlet.” INPUT POWER INDICATING LIGHT   should light. (Note! If switch is accidentally turned to  “Front Outlet,” the rear outlet will not be activated.)
4. Main display shows PROCESS TEMPERATURE (top);  bottom display shows SETPOINT TEMPERATURE (SP1). 
(Wait for self test to complete.)
5. Press INDEX key once and using up ( ) and down ( )  arrows, adjust SP1 value in top display to desired setpoint  temperature. Then push ENTER key to enter value.  
(Note that lower display identifies SP1 value.)
6. Press INDEX key again and appearing is the SP2.   This function is not used. Push again. You are back to  main display.
7. If Diagnostic Error Message appears, see OEM Manual  (pages 38 and 39). Correct condition: reset by cycling  main power switch or pressing Index and Enter keys  simultaneously for 5.0 seconds.
8. Plug heater into appropriate outlet.  Note! The top display PV value should be increasing. 
Watch heater voltage rating!
11
Page 12
Operating Instructions for
12125-14 Temperature Controllers
(TYPE “J” THERMOCOUPLE )
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself with the features
of your new ACE Temperature Controller.
3"
Mounting
Bar
Main Power
Selector Switch
Main
Display
Input
Sensor
Jack
CONTROLS 120 VOLT HEATERS ONLY!
Plug sensor plug into the Controller Jack  
1.  labeled for Type “J” TC. 
2. Plug controller power cord into 120v source. 
3. Insert sensor sheath into heated medium.
4. Plug 120v heater system into rear outlet.
5. Turn front POWER SWITCH “ON.”
6. Main display appears:  
PROCESS TEMPERATURE (PV), top value;  SETPOINT TEMPERATURE (SV), bottom value.
FRONT PANEL:
Locate the control module at right   with digital display (lighted only when  power is on) that has two sets of   four digits: the Process Temperature   (PV) value above and the Setpoint  Temperature (SV) value below; this is  the MAIN DISPLAY. To the left of the  digits, locate four prompt lights labeled SP1 (lights when there is an output),  SP2 and AL (not used), and MAN  (lights when in manual % of output  mode; CAUTION!Controls output without using sensor). Below the  digits are four keypads labeled     for INDEX,   Increase,  Decrease,  and   for ENTER. Left of module  locate “J” TC INPUT JACK (for “Mini”  type plug). This input is polarized  
OPERATION
7. To change Setpoint Temperature (SP1 in °C):
  a.  Press INDEX   Button momentarily.
  b. Press UP ( ) or ( ) DOWN Button to adjust 
SP1 Temperature. 
  c.  Press ENTER   Button momentarily.
  d. Press INDEX   Button momentarily. 
    Auto ON for normal control      Auto OFF for manual % control
  e.  Press INDEX   Button again for main display.
(do not force in reversed polarity).   To the far left of the module locate  MAIN POWER ROCKER SWITCH  labeled ON and OFF. Left side of case,  locate metal plate for screwing 3"  mounting bar supplied.
REAR PANEL: 
Locate fuse holder, far left, for 15A   fuse (fast acting type). Note: A 10-amp  or lower fuse can be used for added  protection if using lower ampere  heaters. To right of fuse holder locate  6-foot power cord for 15A 120v power  source, NEMA USA standard plug.   To far right, locate square black 120v  output outlet, 15 amp max. See label  on top of controller for convenient  operating instructions.
Note: Controller is factory programmed for normal heating situations for con­trolling resistive type heaters and should not need any further programming.  See OEM Manual for any additional options which are available to you to make  the controller match your needs. Contact ACE GLASS Electronics Dept. for  consultation in programming changes for your situation. The OEM Manual  is a valuable guide and lists all menu choices used by ACE in programming.  Refer to ACE Quick Reference sheets to follow OEM Manual.
12
Page 13
Operating Instructions for
12126-24 Temperature Controllers
(TYPE “J” THERMOCOUPLE )
CONTROLS 120 VOLT HEATERS ONLY!
Before beginning, take some time to familiarize yourself with the features
of your new ACE Temperature Controller.
FRONT PANEL:
Locate the control module at top  center with digital display (lighted only  when power is on) that has two sets of   four digits: the Process Temperature   (PV) value above and the Setpoint   Temperature (SV) value below; this   is the MAIN DISPLAY. To the left of the  digits, locate four prompt lights labeled  SP1 (lights when there is an output),  SP2 and AL (not used), and MAN  (lights when in manual % of output  mode; CAUTION!Controls output without using sensor). Below the  digits are four keypads labeled     for INDEX,   Increase,  Decrease,  and   for ENTER. To the left of the  module are two square black 120v  output outlets. Both outlets are   available heat zone mantles, etc.  
 for heating one and two  
CONTROLS 120 VOLT HEATERS ONLY!
1. 
Plug sensor plug into the Controller Jack   labeled for Type “J” TC. 
2. Plug controller power cord into 120v source. 
3. Insert sensor sheath into heated medium.
4. Plug 120v heater circuit(s) into front outlet(s).
5. Turn front POWER SWITCH “ON.”
6. Main display appears:  
PROCESS TEMPERATURE (PV), top value;  SETPOINT TEMPERATURE (SV), bottom value.
Below the module locate INPUT UNIVERSAL JACK:  for “Standard” type plug, bottom “Mini” type plug. These inputs are  polarized (do not force in reversed  polarity). To the right of the module  locate MAIN POWER ROCKER SWITCH labeled ON and OFF. Left  side of case, locate metal plate for  screwing 3" mounting bar supplied.
“J” TC
on top  
 for 
REAR PANEL: 
Locate fuse holder for 15A fuse   (fast acting type). Note: A 10-amp or  lower fuse can be used for added   protection if using lower ampere  heaters. Below fuse holder locate  6-foot power cord for 15A 120v power  source, NEMA USA standard plug.  See label on top of controller for   convenient operating instructions.
OPERATION
7. To change Setpoint Temperature (SP1 in °C):   a.  Press INDEX    b. Press UP (
SP1 Temperature.    c.  Press ENTER    d. Press INDEX 
    Auto ON for normal control 
    Auto OFF for manual % control   e.  Press INDEX 
3"
Mounting
Bar
0-120v
Outlets
Input
Sensor
Jack
 Button momentarily.
) or ( ) DOWN Button to adjust 
 Button momentarily.
 Button momentarily. 
 Button again for main display.
Control Module
Main
Power
Selector
Switch
Note: Controller is factory programmed for normal heating situations for con­trolling resistive type heaters and should not need any further programming.  See OEM Manual for any additional options which are available to you to make  the controller match your needs. Contact ACE GLASS Electronics Dept. for  consultation in programming changes for your situation. The OEM Manual  is a valuable guide and lists all menu choices used by ACE in programming.  Refer to ACE Quick Reference sheets to follow OEM Manual.
13
Page 14
Control Module
3"
Mounting
Bar
Main
Power
Selector
Switch
40/20 volt
Input Sensor
Jack
Selector Switch
Rear/Front Outlet
Selector Switch
FRONT PANEL: 
Locate the control module at top left  with digital display (lighted only when  power is on) that has two sets of   four digits: the Process Temperature   (PV) value above and the Setpoint   Temperature (SV) value below; this is  the MAIN DISPLAY. To the left of the  digits, locate four prompt lights labeled  SP1, (lights when there is an output),  SP2 and AL (not used), and MAN  (lights when in manual % of output  mode; CAUTION!Controls output without using sensor). Below the  digits are four keypad buttons   labeled   for INDEX,  Increase,  
Decrease, and   for ENTER.   To the left of the module is the MAIN  POWER ROCKER SWITCH labeled   ON and OFF. Below the module locate  “J” TC INPUT UNIVERSAL JACK: on  top for “Standard” type plug, bottom 
Operating Instructions for
12127-30 
Temperature Controllers
(TYPE “J” THERMOCOUPLE )
CONTROLS 20, 40 & 120 VOLT HEATERS
Before beginning, take some time to familiarize yourself with
the features of your new ACE Temperature Controller.
0-20/40v
Outlet
REAR VIEW
0-120v
Outlet (2)
for “Mini” type plug.  These inputs are polarized   (do not force in reversed polarity).   To the right of the module locate   OUTPUT DEMAND LED LIGHT.   Below the demand light locate   40 VOLT/ 20 VOLT rocker switch   for selecting maximum output of the  front output outlet to its right, labeled 
0 TO 20/40V. The OUTLET SELECTOR ROCKER SWITCH below these selects 
which outlets are energized, labeled  REAR, FRONT OUTLETS. Left side of  case, locate metal plate for screwing   3" mounting bar supplied.
REAR PANEL: 
Locate two 120 volt controlled outlets  for one- or two-zone heating mantles, etc. Note: “D” nine pin connector, far left  (non-functioning ), for communications  is a special option. To the right of the 
Sensitivity
Control
outlets is a SENSITIVITY adjustment,  factory set at 2/3 CW. This nger- or  small-screwdriver-adjustable  potentiometer “tunes” speed to  setpoint to eliminate over- or  undershoot, full CW fastest response  to setpoint. This adjusts all outputs’  sensitivity: 20, 40 or 120v. Locate 15  amp fuse holder to the far right top.  Note: Fuse is 15 amp fast acting type.  A lower current fuse, 10 amp or even  lower, is recommended for added  protection if using lower power or  ampere heaters. Below fuse holder  locate 6-foot power cord for 15 amp,  120 volt, 50/60 Hz power source,  NEMA USA standard plug. See label  on top of controller for convenient  operating instructions.
1. 
Plug sensor plug into the Controller Jack   labeled for Type “J” TC. 
2. Plug controller power cord into 120v source. 
3. Insert sensor sheath into heated medium.
4. Select heater voltage limit via SW and 20/40 SW.
5. Plug heater into appropriate outlet/outlets; 
be attentive to heater voltage rating maximums.
6. Flip MAIN POWER SWITCH “ON” (upper front left).
7. Main display appears:  
PROCESS TEMPERATURE (PV), top value;  SETPOINT TEMPERATURE (SV), bottom value.
OPERATION
  8.  To change Setpoint Temperature (SP1 in °C):    a.  Press INDEX   Button momentarily.    b.  Press UP ( ) or ( ) DOWN Button to adjust 
SP1 Temperature.     c.  Press ENTER   Button momentarily.    d.  Press INDEX   Button momentarily. 
    Auto ON for normal control 
    Auto OFF for manual % control    e.  Press INDEX   Button again for main display.
  9. 
Adjust REAR SENSITIVITY CONTROL to tune speed to Setpoint
to eliminate overshoot, if necessary. Full CW, fastest response.
 10. IMPORTANT! Read statement in box at bottom of page 13.
14
Page 15
IMPORTANT
For replacement  fuses,  use only ACE No. 12117 VERY FAST  ACTING (VFA) or FAST ACTING (FA) RECTIFIER FUSE. 
This fuse protects sensitive equipment, like ACE Temperature  Controllers, that utilize silicon solid state devices. Fits Type 3AG standard fuse holder found on most ACE instruments. 
Blow time at 100% current rating, four hours minimum; at 250%  current rating, less than one second.
Fuses measure 1
¼" x ¼" and are offered in two current ratings.
Supplied ve per package.
Temperature Controller Fuses
FOR 12107-20, 12111-15, 12113-17
 Rating  Type  Use  Ordering Code    3 amp  FA 3AG-312  Control & Alarm (Bottom Fuse) 
 15 amp  FA ABC or 3AB-314  Primary Heater (Top Fuse)   15 amp  VFA GBB  Primary Heater (Top Fuse) 
or
 10 amp  VFA GBB or 3AG-322  Primary Heater (Top Fuse)  10 amp  FA ABC or 3AB-314  Primary Heater (Top Fuse) 
FOR 12107-46, 12111-47, 12113-50
 Rating  Type  Use  Ordering Code    3 amp   FA 3AG-312  Control & Alarm (Top Fuse, only) 
 15 amp  VFA GBB  Secondary (Bottom Fuse, only) 
or
10 amp  VFA GBB or 3AG-322  Secondary (Bottom Fuse, only)   15 amp  FA ABC or 3AB-314  Primary (Middle Fuse) 
12117-23 12117-31 12117-15 12117-10 12117-29
12117-23 12117-15  12117-10 12117-31
FOR 12102-12, 12103-05, 12105-14, 12106-10, 12108-13, 12110-06
 Rating  Type  Use  Ordering Code  10 amp  VFA GBB or 3AG-322  Secondary (Bottom Fuse, only) 
or
 15 amp  VFA GBB  Secondary (Bottom Fuse, only)   15 amp  FA ABC or 3AB-314  Primary (Top Fuse) 
12117-10 12117-15 12117-31
FOR 12125-14, 12126-24, 12127-30
 Rating  Type  Use  Ordering Code  10 amp  FA ABC or 3AB-314  Primary  Fuse 
 10 amp  VFA GBB or 3AG-322  Primary  Fuse 
or
 15 amp  FA ABC or 3AB-314  Primary  Fuse   15 amp  VFA GBB  Primary  Fuse 
12117-29 12117-10 12117-31 12117-15
15
Page 16
WARRANTY
For Catalog Nos. 12102, 12103, 12105, 12106, 12107, 12108,
12110, 12111, 12113, 12125, 12126, 12127
ACE Proportional Temperature Controllers carry a conditional two-year warranty against defects in material and workmanship from date of shipment. ACE’s  obligation under this warranty is expressly limited to the repair or replacing of  returned equipment provided that (a) ACE is promptly notied by phone or in  writing by the Purchaser of a defect; (b) upon receipt of authorization, verbal  or written, from ACE, said defective equipment is returned as directed, with  transportation charges prepaid by the Purchaser; and, (c) ACE’s examination of such equipment discloses, to our satisfaction, that the defect exists and  was not the result of negligence (operated in corrosive atmosphere or from  chemical or water damage), misuse, physical damage (dropping), or unau thorized repair or alteration by the customer.
If repair is required, phone ACE for a Return Authorization Number (RA). The  complete instrument should be adequately packed. Do not send the electronic  assembly without its case. Include a brief note describing the observed problem include the end user’s name and phone number, and ship prepaid to:
ACE GLASS INCORPORATED  1430 N.W. Boulevard Vineland, NJ Attn.: Electronics Dept.
ACE Catalog Nos. 12102, 12103, 12105, 12106, 12107, 12108, 12110, 12111,  12113, 12125, 12126,  and 12127 are covered  under  a  conditional two-year  warranty from date of shipment; see above. Beyond  this  warranty  period,  ACE can  make  any and all repairs, including refurbishing. (Repairs carry a  one-year conditional warranty.)
To arrange for repairs, call ACE Customer Service at 800/223-4524 for ship ping instructions before returning. You will receive a quotation before repairs  are made.
P.S. You may save  the expense of  our repair by contacting the  Electronics  Dept. at ACE for consultation in making your own repairs.
 08360 
-
, 
-
Loading...