SERVICE MANUAL
SERIAL NUMBERS 25384 AND UP
ACCUTEMP PRODUCTS, INC.
8415 NORTH CLINTON PARK - FORT WAYNE, IN 46825 - 800.480.0415 - www.accutemp.net
2
MP5006-1001 Rev A
TABLE OF CONTENTS
CONNECTIONLESS MODELS
Introduction____________________________________________________ 4
Sequence of Operation___________________________________________ 4
Trouble Shooting Guide__________________________________________ 5-7
Removal and Installation – 6 Pan Models
Removal from Stand________________________________________ 8
Removal of Legs___________________________________________ 8
Gast Vacuum Pump________________________________________ 8
Thermostat________________________________________________ 9
Temperature Probe_________________________________________ 9
Timer_____________________________________________________ 9
Vacuum and Temperature Gauges_____________________________ 10
Contactor__________________________________________________ 10
Vacuum Hoses and Tees_____________________________________ 10
Solid State Relays___________________________________________ 11
Lamps_____________________________________________________11
Fuses_____________________________________________________ 11
Water Sensor Control Board__________________________________ 12
Water Sensors______________________________________________ 12
Control Relays______________________________________________12
Fast Cook / Thermostat Toggle Switch__________________________ 12
On/Off Switches_____________________________________________13
Cord and Plug Assy._________________________________________ 13
Drain Valve_________________________________________________13
Gutters____________________________________________________ 13
Pressure Switch____________________________________________ 14
Dual Pressure Switch________________________________________ 14
Firebar Heater Replacement___________________________________14-15
Cast Heater________________________________________________ 15
Door Removal______________________________________________ 16
Inner Door Removal_________________________________________ 16
Floating Inner Door Removal__________________________________ 16
Gasket Replacement_________________________________________16
Inner Door Valve Cup Replacement_____________________________16
Door Latch Replacement______________________________________17
Removal and Installation – 3 Pan Model
Light Board_________________________________________________17
3
MP5006-1001 Rev A
AUTOFILL MODELS
Introduction & Sequence of Events– 3 & 6 Pan Models________________ 18
Trouble Shooting Guide___________________________________________ 19
Removal and Installation
Water Fill / Sensor Control Board______________________________ 20
Water Fill Valve_____________________________________________ 20
Overfill Sensor Switch_______________________________________ 21
Schematics – 6 Pan Models________________________________________ 22-28
Schematics – 3 Pan Models________________________________________ 29-35
Parts___________________________________________________________ 36 - 39
4
MP5006-1001 Rev A
INTRODUCTION-CONNECTIONLESS 3 & 6 PAN MODELS
The AccuTemp Steam ‘N’ Hold steamer takes time-proven method of cooking with steam
and adds the advantage of control. This is accomplished by reducing the internal
atmospheric pressure of the Steam ‘N’ Hold cooking chamber, thereby lowering the
temperature at which water begins to boil. This allows the operator to control the temperature
of the steam for cooking. Controlling the steam temperature gives the operator the ability to
cook the food to the desired temperature without over-cooking, resulting in a more tender,
juicier, nutritious product with less shrinkage than was previously possible. Once the cooking
time expires, the steamer automatically enters the “Hold” mode. In this mode, the thermostat
regulates the internal temperature, but vacuum is released, returning the cooking chamber to
normal atmospheric pressure. At this time, steam is no longer generated and the cooking
chamber is held at the desired temperature at a relative humidity of 100%. This eliminates
food from drying out by suppressing the evaporation of the products’ natural moisture. As a
result, most food products can be held in a ready to serve state for several hours after
cooking, with no appreciable loss in taste, appearance or consistency.
SEQUENCE OF OPERATION
MAIN ON / OFF SWITCHES
Power is supplied through the power cord to the main contactor. Power comes off the back
side of the contactor to the water board. While power is supplied to the water board, current
is conducted thru the water sensors in the cooking chamber which must sense that water is
in the unit to allow it to come on. The over-temp and water board are in series. Both must be
satisfied before the unit can turn on. When the ON button is pressed it completes the circuit.
The main contactor will pull in and will send power to the solid state heater relays at the
same time latching the CR1 and CR2 control relays. Power is also sent to the timer and
thermostat. The timer has 3 settings: HOLD, TIME and CONTINUOUS. When the timer is
engaged power will be sent to the control relay on the top of the pump and the pump will
start.
5
MP5006-1001 Rev A
TROUBLE SHOOTING GUIDE
STEAMER TROUBLE SHOOTING GUIDE
Fill with up to 3 gallons of water. Make sure
the water level is above the sensors.
Scrub and clean with a scotch brite pad.
Incoming power supply
Check breakers, reset if required. Check the
power plug to be sure it is firmly in the
receptacle. Measure incoming power, call
the Power Co., if necessary.
Check and or replace
Fuse holder
Check and or replace
On switch and contacts
Check for continuity
Control Relays
Check continuity of the coil. Check for
power to relay coil. Visually check for
contact pull in and contact condition. Check
for voltage across relay terminals.
Check to see if the LED on the water board
is on when the unit is powered up. Clean the
sensors and re-inspect. Check for incoming
power and check to make sure the ground is
correct. If the LED light does not come on,
replace the board. Boards with a 10 second
delay is just the opposite
Hi Limit
NOTE
: Serial No. 3865 to 19117 have a
resetable Hi-Limit.
Unplug
the unit and
locate the access panel on the rear of the
unit. Push the button in until it clicks. If this
fails to start the unit after plugging back in,
check the control relay and/or the off
contact. These units also have a auto- reset
hi-limit (purple and brown wires). If this is
open while the unit goes to low water it
needs to be replaced.
Low vacuum pressure, Vacuum
pump.
Remove the top left pan rail in the steaming
chamber. There will be 1 or two holes. If
there are two holes, the one towards the
front is for the pressure switch and does not
need to be plugged. There may be a third
hole located on the lower left side of the
chamber and this must be plugged in
addition to the top hole. From a cold start,
plug all the holes with your fingers, turn the
unit on and observe the reading on the
vacuum gauge. The correct reading should
be between 20 to 25 inches of pressure.
0 to 5 inches of pressure denotes a faulty
pump.
Check all the hoses and connections for any
leaks. If the pump does not run at all, give
the fan blade a push start through the grill. If
the pump starts, it has a bad run capacitor.
Replace as needed.
Unit is cooking slow (cont)
In the FAST cook mode, the pressure switch
will close once the steam chamber reaches
the thermostat setting. As the temperature
rises, the vacuum pressure falls. Once the
unit reaches 210 to 212 degrees, the
pressure will be at zero. Cycle times when
the unit is calling for heat should be around
8 to 10 seconds on and 60 to 90 seconds
off. Replace the pressure switch if the cycle
times are off or if you can suck air through
the switch.
Unit is cooking slow (cont)
Check for cuts or cracks. Replace as
needed
With the unit on and the pump running,
perform the Dollar Bill test on the door.
Close the door on a Dollar Bill. (all four
sides of the door) There should be
resistance when pulling the bill out. If the
bills comes out easily, remove the hinge
covers. Loosen all of the screws, turn the
thermostat to150 degrees, enable the timer,
shut the door and turn the unit on so it
creates a vacuum and draws the door in
and then retighten the screws.
Door Sealing
If the door alignment process does not fix
the problem, remove the inner door and
place it on a flat surface and check for any
warpage. Also check that the suctions cups
are sealing. If they have turned gray or
white then replace. Use one of the pan rails
as a straight edge. Straighten and re-bend
the inner door until it is flat and re-install
using the door alignment procedure.
Quick Release Door
On the inner door, check that the four
suction cups are sealing and that the spring
is functioning properly. Replace as needed.
Check the cycle times as stated above.
Check the voltage between T1 and L1. If the
LED light is on, there should be 0 voltage. If
the unit does not cycle, and the LED stays
on, replace the relay.
Ohm out the Hi-limit to see if it is good.
Clean the sensors and check the water
board. If the low water light comes on while
the unit is heating up, refer to the Hi-limit
procedure.
Check that the thermocouple is wired
correctly to the thermostat. White is positive
(Terminal 6) and Red is negative (terminal
7). Reversing the terminals will result in a
run-away condition. See attached chart for
DC-milli volt readings.
Unit is over-temping (cont)
When a unit is at an altitude of 2,500ft+
water boils at this altitude at about 207
degree's. In thermostat mode unit starts
blowing steam out the door just after heat
light goes out. (It will do this because of
extra heat in the element when it shuts off
at about 205 degree's, drift point is at least 2
degree's). If you have the tech set
thermostat at 190 degree's and put in fast
cook it will run at the point customer wants
to cook at
Check resistance between terminals 4 & 5.
AC thermostats should read line voltage and
DC thermostats should be between 3 to 34
DC volts.
Thermocouple (type J)
Unit is not coming up to
proper temperature
Check for resistance between the two
outside double white wires on the terminal
block. On 17kW units check to terminals 1 &
6, 2 & 5, and 3 & 4 on the terminal block.
See attached chart for resistance readings.
TYPE J THERMOCOUPLE READINGS - THERMOELECTRIC VOLTAGE IN DC MILLIVOLTS
8
MP5006-1001 Rev A
REMOVAL AND INSTALLATION 6 PAN MODEL
REMOVAL FROM STAND
Using a 7/16” wrench, remove the 4 ¼’-20 x ½” bolts and lock washers located on the
mounting brackets going into the bottom of the unit. When reinstalling, make sure the “L”
brackets that hold the drip pan are facing inward.
REMOVAL OF LEGS
Units with legs use the same “L” brackets used on the stand but are held on by 8 ¼”-20 X ½”
bolts and lock washers. Use a 7/16” wrench to remove these to access the bottom panel.
GAST VACUUM PUMP
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Disconnect the wires to the relay and mark the locations.
4. Remove the hoses from the pump head.
5. Remove the two 3/8” nuts holding the muffler on and pull out of the way.
6. Remove the bolts on the pump bracket and pull the whole assembly out.
7. Remove the 4 Phillips screws washers and spacers on the bracket.
8. Remove the brass fittings on the head of the pump.
9. Reassemble in reverse order.
9
MP5006-1001 Rev A
THERMOSTAT
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the knob and the seal nut with a ½” nut driver on the front of the unit.
4. Disconnect the wires and mark the pin locations.
5. Reassemble in reverse order.
Note: AC thermostats have 6 pins and DC thermostats have 7 pins.
TEMPERATURE PROBE
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the white wire from terminal # 6 and the red wire from terminal # 7.
4. Follow the red and white wire down to the bottom of the unit.
5. Peel the insulation aside and remove the retaining nut with a 3/8” nut driver.
6. Reassemble in reverse order.
TIMER
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the knob and retaining nut with a ½” nut driver on the front of the unit.
4. Disconnect the wires and mark the pin locations.
5. Reassemble in reverse order.
Note: Don’t remove jumper wires.
10
MP5006-1001 Rev A
VACUUM AND TEMPERATURE GAUGES
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit.
3. On the vacuum gauge, remove the hose form the inlet connection.
4. Remove the two 10/24 nuts.
5. On the temperature gauge, remove the retaining nut on the inlet connection.
6. Follow the capillary leads down to where the probe is mounted to the unit.
7. Remove the two 3/8” nuts.
8. Reassemble in reverse order.
CONTACTOR
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the red, black and white leads on both sides of the contactor.
4. Remove coil wires.
5. Remove the 6/32” nyloc nuts that secure the contactor.
6. Reassemble in reverse order.
VACUUM HOSES AND TEES
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Check all hoses and Tees for cracks or leakage.
4. Remove clamps and replace.
11
MP5006-1001 Rev A
SOLID STATE RELAYS
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the wires attached to the relay and mark their locations.
4. Remove the two mounting screws.
5. Reassemble in reverse order.
Note. Relays not mounted on a heat sink should use a heat pad or thermal paste.
LAMPS
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit.
3. Remove the two wires on the lamp terminals.
4. With a pair of pliers, depress the locking ears on the switch and push the lamp thru
the front.
5. Push new lamp in the mounting hole. Make sure locking ears engage.
6. Reattach the wires.
FUSES
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit.
3. Pry the fuses out of the fuse block with a pocket screw driver.
12
MP5006-1001 Rev A
WATER SENSOR CONTROL BOARD
1. Unplug the unit
2. Remove the sheet metal screws on the left side panel of the unit
3. Disconnect the wires and mark the pin locations.
4. Remove the nylon mounting pins.
5. Reassemble in reverse order.
WATER SENSORS
1. Unplug the unit.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Open the door and drain all the water from the chamber.
4. Remove the 8/32” hex nut from the back side of the sensor with an 11/32” wrench and
remove the sensor lead.
5. Use a ¾” wrench to remove the nut on the sensor.
6. Push the sensor thru the hole from the backside.
7. Reassemble in reverse order.
Note: Do not exceed 15 inch pounds when tightening the sensor mounting nut.
CONTROL RELAYS
1. Unplug the unit
.
2. Remove the sheet metal screws on the left side panel of the unit.
3. Disconnect the wires and mark the pin connections.
4. Remove the 6/32” nyloc nuts.
5. Reassemble in reverse order.