This manual may not be altered or reproduced in whole or in part by any means
without the expressed written consent of Accuenergy.
II
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 3
The information contained in this document is believed to be accurate at the time of
publication, however, Accuenergy assumes no responsibility for any errors which may appear
here and reserves the right to make changes without notice. Please ask the local representative
for latest product specications before ordering.
Please read this manual carefully before installation, operation and maintenance of the Acuvim
II series meter. The following symbols in this manual are used to provide warning of danger or
risk during the installation and operation of the meters.
Electric Shock Symbol: Carries information about procedures which must be
followed to reduce the risk of electric shock and danger to personal health.
Safety Alert Symbol: Carries information about circumstances which if not
considered may result in injury or death.
Prior to maintenance and repair, the equipment must be de-energized and grounded. All
maintenance work must be performed by qualied, competent accredited professionals who
have received formal training and have experience with high voltage and current devices.
Accuenergy shall not be responsible or liable for any damages or injuries caused by improper
meter installation and/or operation.
V: 1.11 Revised: May 2020
www.accuenergy.com
1
Page 4
Table of Contents
Chapter 1: Introduction to Ethernet ....................................................................6
1.1 Introduction to Ethernet .........................................................................................6
The AXM-WEB2 module provides a dual Ethernet and WiFi communication channel for Acuvim II
series power meters. Users will be able to use both Ethernet ports and WiFi simultaneously with
dierent networks and data acquisition systems.
This communications module provides users with an industry leading 100ms and 40ms response rate via Modbus TCP that allows users to attain real time updates to key parameters
such as voltage, current and power from the Acuvim II Series meter.
1.1 Introduction to Ethernet
Ethernet was originally developed by Xerox and then further developed by DEC and Intel. This
networking technology uses Carrier Sense Multiple Access with Collision Detection (CDSM/CD)
protocol and provides transmission speeds up to 100Mbps.
Ethernet is a not a network but more of a standard. It is the most current communication stan-
dard Local Area Network(LAN). This standard denes the type of cable that is used and the
method of Signal Processing. The AXM-WEB2 module supports two Ethernet channels.
1.1.1 IPv6
The AXM-WEB2 module also supports IPv6 which is the latest version for the internet protocol.
The protocol uses 128-bit addressing in comparison to IPv4 which uses 32-bit addressing. The
dierence for addressing allows for more devices to be connected using IPv6 as opposed to the
IPv4 protocol. The protocol is more ecient and provides more secure routing over the inter-
net.
Chapter 2: Functional Description of the Ethernet module
The AXM-WEB2 module supports a wide range of communication protocols. Some of the more
commonly used protocols are briey explained below.
This module supports the Modbus-TCP protocol. When connected to the Acuvim II series meter,
it is a slave device that can only respond to queries. The default value for the Modbus Port is
502. The user dened range is 2000~5999.
The AXM-WEB2 grants users the ability to send emails based on a time interval or when there is
a triggered event using the SMPT protocol. It can send mail from encrypted servers and servers
that use dierent SMTP ports.
The AXM-WEB2 protocol supports HTTPS protocol. It is used as an HTTPS server and where the
default value of the protocol port is 443. Using the HTTPS protocol, the AXM-WEB2 can send
post requests to both HTTP and HTTPS servers.
6
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 9
Chapter 3: Appearance and Dimensions
22.00 (0.866)
The following are all the protocols supported by the AXM-WEB2 module:
• Modbus TCP
• IPv6
• RSTP
• BACnet-IP
• SNMP V3
• DNP 3.0 V2
• IEC 61850 2nd Edition
• SMTP, NTP, SNTP
• HTTP/HTTPs
• FTP
• sFTP
• WiFi WPA, WPA2 Enterprise
• Ethernet/IP
• MQTT
Chapter 3: Appearance and Dimensions
The dimensions in the following diagram are in millimeters.
Dimensions listed in the brackets are inches.
www.accuenergy.com
90.00 (3.543)
55.60 (2.189)
22.00 (0.866)
V: 1.11 Revised: May 2020
7
Page 10
AXM-WEB2 for Acuvim II Series Power Meter
Chapter 4: Installation Method
The AXM-WEB2 module is linked to the Acuvim II series meter by a communication plug. Other
extended modules such as the IO modules can be linked to the Acuvim II series meter through
the AXM-WEB2.
1) Remove cover from the back of the Acuvim II series meter which will expose the socket.
2) Insert the installation clips to the grooves in the Acuvim II series meter and then press the
AXM-WEB2 module lightly to establish a linking between meter and module.
3) Tighten the installation screws.
NOTE: Installation with power to the meter is forbidden. The module must be installed/unin-
stalled while the meter is powered o.
8
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 11
Chapter 4: Installation Method
4.1 Denition of RJ45
The AXM-WEB2 uses two standard RJ45 connectors to access the Ethernet network. The
mechanical and electrical characteristics of the connector are consistent with the requirements of IEC 603-7.
LED_L (Yellow): Displays the speed status. When the LED is on it indicates 100Mpbs,
whiles an o LED represents a speed of 10Mbps.
LED_R (Green): Displays the link and activity status. When the LED is on it indicates
the link status. When the LED is ashing it indicates that there is activity.
V: 1.11 Revised: May 2020
www.accuenergy.com
9
Page 12
AXM-WEB2 for Acuvim II Series Power Meter
Chapter 5: Initializing the Ethernet module
The default settings in the Acuvim II series meter are as followed:
Ethernet 1 (Static IP address)
IP Address (192.168.1.254)
Subnet Mask (255.255.255.0)
Gateway (192.168.1.1)
DNS Server 1 (8.8.8.8)
DNS Server 2 (8.8.4.4)
Modbus Port 502
Ethernet 2 (Dynamic IP address)
By default Ethernet 2 is con gured for DHCP, meaning the network will dynamically
assign its network properties. In order to view the Ethernet 2 IP address from the meters display the Acuvim II meter must be con gured to the WEB2 protocol. The following
explains how to change the meters protocol settings to work with the WEB2 module:
• Press the 'H' and 'V/A' buttons simultaneously on the Acuvim II series. Release the buttons
and the meter will enter the meter selecting mode, as indicated by the ashing 'Meter' cursor.
10
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 13
Chapter 5: Initializing the Ethernet module
• Press the 'P' or 'E' button to move the cursor to 'Setting'. Press 'V/A' button to enter the pa-
rameter setting mode. The device address page is the rst page of the 'Setting' mode. It will
show the Modbus address of the meter for a second before prompting for the password of the
device.
• You will be required to type in a password in the ‘PASSWORD’ screen. Leave the password as
default ‘0000’ and press ‘V/A’ to enter the parameter selection Mode.
www.accuenergy.com
V: 1.11 Revised: May 2020
11
Page 14
AXM-WEB2 for Acuvim II Series Power Meter
• The cursor will be on ‘SYS’. Press ‘V/A’ on this screen to get to the system settings. This will
show screen ‘S01 ADDR’.
• Press the 'E' button until you get to 'S34 PROTOCOL 2'. Select the 'WEB2' protocol.
• Press ‘V/A’ to modify the setting; the cursor should now ash.
• Press ‘P’ or ‘E’ to select 'WEB2'.
• Press ‘V/A’ to con rm the change.
Once the protocol 2 setting of the Acuvim II meter is con gured for WEB2, users can now view
all necessary settings in the meters NET settings.
Press the 'H' button to exit the system setting, you will be directed to the parameter selection
screen.
Press the 'P' or 'E' button to move the cursor to 'NET' and press the 'V/A' button to enter the
Ethernet module settings.
12
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 15
Chapter 5: Initializing the Ethernet module
• The rst page of the NET Settings will be the N01 DHCP setting. By default this is con gured to Manual. Setting this con guration to Auto will allow the router to assign the meter
with an IP address, whiles Manual will allow the user to con gure the IP address. Press the
'V/A' button to enter edit mode. Press 'P' or 'E' to change the setting and press 'V/A' to con-
r m
.
NOTE: If the DHCP is selected as Auto, the Ethernet module needs to be rebooted before it can
be assigned with the new IP address.
• Press 'P' to get to "N02 IP address" This is the IP address for Ethernet 1 and can be used to
access the web interface of the module. Users can con gured the IP address if the DHCP
is con gured to Manual. Press 'V/A' to con gure the IP address. The cursor of the rst digit
will begin to ash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to
change the value of the ashing cursor and press 'V/A' to con rm.
www.accuenergy.com
V: 1.11 Revised: May 2020
13
Page 16
AXM-WEB2 for Acuvim II Series Power Meter
• Press 'P' to get to "N03 Subnet Mask". Press 'V/A' to con gure the subnet address. The cursor of the rst digit will begin to ash. Press the 'H' button to scroll through the digits, press
the 'P' or 'E' to change the value of the ashing cursor and press 'V/A' to con rm.
• Press 'P' to get to "N04 Gateway". Press 'V/A' to con gure the gateway IP address. The cursor of the rst digit will begin to ash. Press the 'H' button to scroll through the digits, press
the 'P' or 'E' to change the value of the ashing cursor and press 'V/A' to con rm.
14
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 17
Chapter 5: Initializing the Ethernet module
• Press 'P' to get to "N05 DNS Primary Server". Press 'V/A' to con gure the DNS address. The
cursor of the rst digit will begin to ash. Press the 'H' button to scroll through the digits,
press the 'P' or 'E' to change the value of the ashing cursor and press 'V/A' to con rm. The
DNS parameters must be set correctly to use the SMTP, FTP/HTTP Post and AcuCloud func-
tions.
• Press 'P' to get to "N06 DNS Secondary Server". Press 'V/A' to con gure the DNS address.
The cursor of the rst digit will begin to ash. Press the 'H' button to scroll through the digits, press the 'P' or 'E' to change the value of the ashing cursor and press 'V/A' to con rm.
www.accuenergy.com
V: 1.11 Revised: May 2020
15
Page 18
AXM-WEB2 for Acuvim II Series Power Meter
• Press 'P' to get to "N07 Modbus Port". Press 'V/A' to con gure the Modbus Port. The cursor
of the rst digit will begin to ash. Press the 'H' button to scroll through the digits, press
the 'P' or 'E' to change the value of the ashing cursor and press 'V/A' to con rm.
• Press 'P' to get to "N08 HTTP Port". Press 'V/A' to con gure the HTTP Port. The cursor of the
rst digit will begin to ash. Press the 'H' button to scroll through the digits, press the 'P'
or 'E' to change the value of the ashing cursor and press 'V/A' to con rm.
16
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 19
Chapter 5: Initializing the Ethernet module
• Press 'P' to get to "N09 NET REST". After making any changes to the NET settings, users
must reboot the Ethernet module from this page for the settings to take e ect. Press 'V/A'
to reboot the module, the cursor will begin to ash. Press the 'P' or 'E' button to change
the setting to 'Reset' and press 'V/A' to con rm. The cursor will return to 'No' once the mod-
ule has successfully reset.
• Press 'P' to get to "N10 PASSREST". Press 'V/A' to con gure the password reset. The cursor
of the rst digit will begin to ash. Press the 'P' or 'E' button to change the setting to 'Reset' and press 'V/A' to con rm. The cursor will return to 'No' once successful.
www.accuenergy.com
V: 1.11 Revised: May 2020
17
Page 20
AXM-WEB2 for Acuvim II Series Power Meter
• Press 'P' to get to "N11 WiFi" This is the IP address of WiFi and will be the IP address to ac-
cess the web interface of the module by using WiFi connection. This IP address cannot be
modi ed from the meters display, it can only be con gured on the meters web server.
• Press 'P' to get to 'N12 IP2'. This is the IP address for Ethernet port 2, it is preset as dynamic
DHCP. A new IP address will be assigned to it when it is connected to the internet via Ethernet port 2.
5.1 Cable
An RJ45 cable is needed to connect the meter to the network.
A shielded twisted pair cable(standard 568A or standard 568B) is recommended as reference to
the EIA/TIA standard.
18
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 21
Chapter 6: Connection Method
Chapter 6: Connection Method
6.1 Direct Connect to a Computer
The AXM-WEB2 can be connected to a computer using a crossover cable(standard 568A). The
AXM-WEB2 module supports Modbus-TCP and HTTPS Functions for this method of connection.
To connect meter directly to the computer, the computers IP must be within the same subnet
as the meters IP address. The following steps outline how to change the computers IP using a
computer running the Windows OS:
• Manually connect the meter via Ethernet cable to the computer
• Right click on the connection icon
• Select "Open Network Sharing Center"
www.accuenergy.com
V: 1.11 Revised: May 2020
19
Page 22
AXM-WEB2 for Acuvim II Series Power Meter
• Click on Change adapter options
• Once there, right click on the local area connection icon and select properties.
20
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 23
Chapter 6: Connection Method
• Select the icon that says Internet Protocol Version 4 TCP/IP
• The Internet Protocol Version 4(TCP/IP) Properties box will pop up
www.accuenergy.com
V: 1.11 Revised: May 2020
21
Page 24
AXM-WEB2 for Acuvim II Series Power Meter
• Click on ''Use the following IP address'' and enter in an IP number so that meter
and computer are in the same local network range. For example, if the meter
has IP address of 192.168.1.254, then the computer must be assigned with an IP
192.168.1.xxx, where xxx can be any number but cannot be the same as the val-
ue the meter has.
• Once you have entered in the IP address, press the Tab key on your keyboard
until you hit the bottom and click OK
• Before selecting the OK button make note of the IP address you have assigned
to the meter and then press OK.
NOTE: The meter and computer cannot have the same IP address, they must be
di erent.
22
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 25
Chapter 6: Connection Method
6.2 Direct Connect to a Router/Switch
The AXM-WEB2 can be connected to a router or switch using a patch cable. The
DHCP can be congured to Auto to have the router assign the meter with an IP
address or the DHCP can be congured to Manual to set an IP address and net-
work settings manually.
AXM-WEB 2 has two Ethernet ports, Ethernet 1 is set to have the static DHCP,
and Ethernet 2 is set to have the dynamic DHCP. Both of the Ethernet ports
have the same functionalities, you can use either of them according to the requirement.
6.3 Connect through WiFi
The AXM-WEB2 can be connected through WiFi network.
By default the AXM-WEB2 will be in Access Point mode with default IP address
of 192.168.100.1. Ensure the device connecting to the AXM-WEB2 has DHCP
enabled or it should be in the same subnet as the AXM-WEB2. The module will
appear in the WiFi network as AXM-WEB2-WIFI-(serial number of module) as
the SSID or name of the wireless network. By default, the network key or pass-
word will be ''accuenergy''.
• Once connected to the network, open an internet browser and type in the
IP address of the WIFI module:
• Log in at Admin access level, using the default password of
192.168.100.1
'admin'
6.4 Description of Modbus-TCP Protocol
The Modbus-TCP protocol is used as one of the communication protocols in
the AXM-WEB2. The protocol establishes a master and slave connection in
Ethernet. The master device(client) rst sets up a TCP-IP link with slave device(server). The master device then sends a request to the slave device and
the slave device in return sends a response to the master device. Figure below
shows how the Modbus-TCP protocol works.
V: 1.11 Revised: May 2020
www.accuenergy.com
.
23
Page 26
AXM-WEB2 for Acuvim II Series Power Meter
6.4.1 Protocol
a. Data Frame Format
MBAP HeaderFunctionData
7x8 bits8-bitsNx8 bits
b. Modbus Application Header (MBA Header) Field
Modbus application header eld is the start of the data frame, and consists of seven bytes.
Request
Modbus Client
Conrmation
FieldLengthDescription
Transaction Identi er2 Bytes
Protocol Identi er2 BytesModbus Protocol = 0
Length2 BytesNumber of following bytes
Unit Identi er1 ByteSlave address, in the range of 0-247 decimal
Indication
Modbus Server
Response
Identi cation of a Modbus
Request/Response transaction
24
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 27
Chapter 6: Connection Method
c. Function Field
The function code eld of a message frame contains eight bits. Valid codes are in the range of
1-255. When a message is sent from a client to a server device, the function code eld tells the
server what kinds of action to perform.
CodeMeaningData
01Read Relay Output StatusObtain current status of Relay Output
02Read Digital Input (DI) StatusObtain current status of Digital Input
03Read Data
Obtain current binary value in one or more
registers
05Control Single Relay OutputForce Relay to a state of ON or OFF
16Write Multiple Registers
Place specic value into a series of consecutive
multiple registers
d. Data Field
The data eld is constructed using sets of two hexadecimal digits, in the range of 00 to FF. The
data eld of messages sent from a master to slave contains additional information which the
slave must use to take the action dened by the function code. This can include information
such as the register addresses, the quantity of registers to query and the count of the actual
number of data bytes. For example, if the master requests a slave to read a group of holding reg-
isters(function code 03), the data eld species the starting register and how many registers are
to be read.
If the master needs to write data(function code 10 hexadecimal) to a group of registers in the
slave, the data eld species the starting register, how many registers to write, the count of data
bytes to follow in the data eld and the data to be written into the registers.
www.accuenergy.com
V: 1.11 Revised: May 2020
25
Page 28
AXM-WEB2 for Acuvim II Series Power Meter
6.4.2 Format of communication
Explanation of frame
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
00H00H00H00H00H06H01H
Function
Code
Data start
register hi
Data start
register lo
Data # of
registers hi
Data # of
registers lo
03H40H00H00H48H
The meaning of each abbreviated eld above is:
Transaction identier hi: High byte of transaction identier
Transaction identier lo: Low byte of transaction identier
Protocol identier hi: High byte of protocol identier
Protocol identier low: Low byte of protocol identier
Length hi: High byte of length
Length lo: Low byte of length
Unit identier: Slave address
Unit
identier
Fun: Function code
Data start register hi: High byte of starting register address
Data start register lo: Low byte of starting register address
Data #of registers hi: High byte of number of registers
Data #of registers lo: Low byte of number of registers
26
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 29
Chapter 6: Connection Method
1) Read Status of Relay (Function code 01)
Function Code 1
This function code is used to read the relay output status in the Acuvim II series meter.
1=On 0=O
There are 8 relay outputs in the Acuvim II series meter and they start at address 0000H.
The following query is to read 2 relay output status of the Acuvim II series address 1.
Query
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
Unit
identier
00H00H00H00H00H06H01H
Fun
01H00H00H00H02H
Data start
register hi
Data start
register lo
Data # of
registers hi
Data # of
registers lo
Response
The Acuvim II series meter responds back with the MBAP header, function code, quantity
of data bytes and the data.
An example of response to read the status of the rst 2 relay outputs starting at 0000H is
shown below. The status of relay output 1 and 2 is corresponds to the last 2 bits of data.
Relay 1: bit0 Relay 2: bit1
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
Unit
identier
00H00H00H00H00H04H01H
FunByte countData
01H01H02H
www.accuenergy.com
V: 1.11 Revised: May 2020
27
Page 30
AXM-WEB2 for Acuvim II Series Power Meter
The content of the data is,
76543210
00000010
MSB LSB
(Relay 1 = OFF, Relay 2 = ON)
2) Read Status of DI (Function Code 02)
Function Code 2
1=On 0=O
There are 28 DIs in the Acuvim II series meter starting at address 0000H.
The following query is to read 4 DI statuses of AXM-IO1 module with logic address of 1 in
the Acuvim II series meter.
Query
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
identier
00H00H00H00H00H06H01H
Fun
02H00H00H00H04H
Data start
register hi
Data start
register lo
Data # of
registers hi
Data # of
registers lo
Response
The response includes the MBAP header, function code, quantity of data characters and the
data.
An example response from the meter to read the status of 4 DIs(DI1-On, DI2=On, DI3=On,
DI4=On) is shown below. The status of each corresponds to the last 4 bits of the data.
28
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Unit
Page 31
Chapter 6: Connection Method
DI1: bit0 DI2: bit1 DI3: bit2 DI4: bit3
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
Unit
identier
00H00H00H00H00H04H01H
FunByte countData
02H01H0FH
The content of the data is,
76543210
00001111
MSB LSB
3) Read Data (Function Code 03)
Function Code 3
Query
This function allows the user to obtain the measurement results of the Acuvim II series meter.
Below is an example to read 6 registers corresponding to the device clock of the meter, starting
at 1040H.
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
Unit
identier
00H00H00H00H00H06H01H
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
reg lo
03H10H40H00H06H
An example response is provided to read the time (2006-12-18 14:15:20).
This function code enables the control of a single relay output in the Acuvim II series me-
ter. Any relay output in the Acuvim II series meter can be controlled on or o starting at
0000H.
Sending the data 'FF00H' will set they relay output on and sending '0000H' will turn it o;
all other values are illegal and will not aect they relay output status.
The example below is a request to a Acuvim II series meter to turn on relay output 1.
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
00H00H00H00H00H06H01H
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
reg lo
05H00H00HFFH00H
Response
Unit
identier
The normal response to the command request is to retransmit the message as received
after the relay output status has been altered.
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hiLength lo
00H00H00H00H00H06H01H
Fun
Data start
reg hi
Data start
reg lo
Value hiValue lo
05H00H00HFFH00H
30
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Unit
identier
Page 33
Chapter 6: Connection Method
5) Preset/Reset Multi-Register (Function Code 16)
Function Code 16
Query
This function code allows the user to modify the contents of a register. The example below is
a request to an Acuvim II series meter with device address 1 to preset the CT1(500) and CT2(5)
registers. The CT1 data address is 1008H and CT2 is at 1009H.
Transaction
identier hi
00H00H00H00H00H0BH01H
Fun
Transaction
identier lo
Data
start
reg hi
Data
start
reg lo
Protocol
identier hi
Data #of
reg hi
Protocol
identier lo
Data #of
reg lo
Length hiLength lo
Byte
Value1 hiValue1 loValue2 hiValue2
count
Unit
identier
lo
10H10H08H00H02H04H01HF4H00H05H
Response
The normal response to a preset Multi-Register request including the MBAP Header, function
code, data start register and the number of registers is shown below.
Transaction
identier hi
Transaction
identier lo
Protoco-
lidentier hi
Protocol
identier lo
Length hiLength lo
Unit
identier
00H00H00H00H00H06H01H
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
reg lo
10H10H08H00H02H
www.accuenergy.com
V: 1.11 Revised: May 2020
31
Page 34
AXM-WEB2 for Acuvim II Series Power Meter
Chapter 7: Web Interface Readings and Parameter Settings
The AXM-WEB2 module supports the HTTPS protocol to allow for the use of a web interface.
The user will need to access the AXM-WEB2 web interface to congure the module and use its
functions. The web interface allows for remote initial setup of the Acuvim II meter.
The AXM-WEB2 web interface allows for dierent user access levels.
To access the web interface the IP address for the WEB2 either Ethernet 1, Ethernet 2 or a WiFi
IP address must be known.
7.1 User Access Login
Enter the correct IP address of the module in the search bar of the internet browser to access
the web interface of the AXM-WEB2
The user will be redirected to a web page prompting to select the Access Level and enter
appropriate password for that level.
User
The
level is ideal for users who need only to take readings and view status from the meter.
The default password for the User level is
It is recommended that no more than 5 users are logged in at the same time for this level to
ensure optimal performance of web interface.
Admin
The
interface and to view readings.
The default password for the Admin level is
32
level is ideal for users who need access to congurations on the meter or the web
V: 1.12 Revised: Dec 2020
view
admin
.
.
www.accuenergy.com
Page 35
Chapter 7: Web Interface Readings and Parameter Settings
The two dierent access levels are summarized below:
In the dashboard, the user will nd the tabs to access dierent pages in the web interface
such as '
once they have entered the correct password for the appropriate access level and is the
same for both access levels.
The dashboard displays selected parameters from the dierent groups of metering param-
eters such as '
on "Full report" under any one of these four metering parameter groups the user will be
redirected to the web page which contains all the parameters supported by that metering
parameter group.
The dashboard also displays how long the AXM-WEB2 module has been connected to the
network since the last reboot of the module in the bottom left corner of the page.
Metering
Basic Metering
', '
Logs
', and '
Settings
', '
Power & Energy
'. The dashboard is the rst page the user will see
', '
THD
' and '
Max Demand
'. By clicking
The parameters on this page are updated every 5 sec.
www.accuenergy.com
V: 1.11 Revised: May 2020
33
Page 36
AXM-WEB2 for Acuvim II Series Power Meter
7.3 Metering web page
Click on the 'Metering' tab to visit the metering data web pages. There are eight kinds of
metering parameter web pages. They are "Basic Metering", "Power & Energy", "Min/Max",
'THD', 'Harmonics', "Phase Angles", ''Sequence'' and ''I/O''. Each web page shows data
from the Acuvim II series meter.
7.3.1 Basic Metering
The Basic Metering webpage includes the data of real-time parameters for the Acuvim II se-
ries meter. This includes the Line Voltages, Phase Voltages, Current, Neutral Current, Active,
Reactive and Apparent Power, Power Factor, Frequency and Load type.
The parameters on this page are updated every 1 sec.
The values displayed in this webpage will depend on the wiring con guration mode of the
meter. For example, if the meter is con gured as '2LL' or '3LL' then the metering webpage will
not display the phase readings, only the total values will be shown.
34
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 37
Chapter 7: Web Interface Readings and Parameter Settings
7.3.2 Power & Energy
The Power & Energy webpage shows the energy data for the Acuvim II series meter such as
the Active and Reactive energy that is consumed and delivered as well as the Apparent energy per phase and total.
This webpage also shows the Demand parameters for the Active, Reactive and Apparent
Power as well as the three phase Current demands.
The parameters in this webpage are updated every 5 sec.
www.accuenergy.com
V: 1.11 Revised: May 2020
35
Page 38
AXM-WEB2 for Acuvim II Series Power Meter
From the Power & Energy page user have the option to edit and write new Energy values.
Simply click on the 'Manual Edit' button to edit the energy values.
This will be useful for users who want to start and monitor energy accumulation at a certain kilowatt hour reading. All energy parameters including individual phase, total, import,
export, and net for the real, reactive and apparent energies support this feature.
7.3.3 Min/Max
The Min/Max page shows the maximum and minimum statistics that the meter has records
since the life time of the meter or from the last reset of the min/max statistics as well as the
timestamps they were recorded at.
The parameters in this web page are updated every 10 sec.
36
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 39
7.3.4 THD
Chapter 7: Web Interface Readings and Parameter Settings
The THD web page shows the power quality data such as the THD, THFF, Crest and K Factor
for both the voltage and current.
The parameters in this web page are updated every 15 sec.
V: 1.11 Revised: May 2020
www.accuenergy.com
37
Page 40
AXM-WEB2 for Acuvim II Series Power Meter
7.3.5 Harmonics
The Harmonics web page will show the harmonics of the voltage and the current waveform
being measured. It will display the harmonics of each phase in graphical and tabular format.
Select between voltage and current to view their respective harmonics as well as between
2nd - 31st harmonics or 32nd - 63rd from the drop down list.
The parameters in this web page are updated every 15 sec.
38
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 41
Chapter 7: Web Interface Readings and Parameter Settings
7.3.6 Phase Angles
The Phase Angles web page will show the phase angles of the voltage and current waveform being measured which can be used for remote troubleshooting. This page provides
a visual diagram of the phase angles with respect to the voltage connected to the Phase A
voltage input.
The parameters in this web page are updated every 10 sec.
7.3.7 Sequence
The Sequence web page will show the positive, negative and zero components of the voltage and current waveform being measured.
The parameters in this web page are updated every 10 sec.
V: 1.11 Revised: May 2020
www.accuenergy.com
39
Page 42
AXM-WEB2 for Acuvim II Series Power Meter
7.3.8 I/O
The I/O web page displays the status of the I/O modules that are connected and their values depending on the model of the module that is connected to the meter. I.E. The AXM-
IO11 module will display the Relay Output status(on/o), DI status/counter. The I/O module
can be congured in the general settings section of the web interface which is discussed
later in the manual.
The parameters in this web page are updated every 5 sec.
40
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 43
Chapter 7: Web Interface Readings and Parameter Settings
From the IO readings page, users can perform the following functions depending on the IO
module being used:
IO ModuleFunctions
• Read Digital Input Status or Digital Input Count value
depending on the mode congured (Channels 1-6)
• Read the Relay Output Channel 1 and 2 Status ON/OFF
AXM-IO1-1/2
AXM-IO2-1/2
AXM-IO3-1/2
• Toggle Relay Output Channels 1 and 2 ON/OFF
NOTE:
Relay must be congured for Control Mode for tog-
gle function to work
• Reset DI Counter back to 0 (Counters 1-6)
• Read Digital Input Status or Digital Input Count value de-
pending on the mode congured (Channels 1-4)
• Read value of the Analog Output Channels 1 and 2, either
4-20mA, 0-20mA, 0-5V, 1-5V signals
• Reset DI Counter back to 0 (counters (1-4)
• Read Digital Input Status or Digital Input Count value de-
pending on the mode congured (Channels 1-4)
• Read the Relay Output Channel 1 and 2 Status ON/OFF
• Toggle Relay Output Channels 1 and 2 ON/OFF
NOTE
: Relay must be congured for Control Mode for toggle
function to work
• Read Analog Input Channels 1 and 2, either 4-20mA,
0-20mA, 0-5V, 1-5V signals
• Reset DI Counter back to 0 (Counters 1-4)
www.accuenergy.com
V: 1.11 Revised: May 2020
41
Page 44
AXM-WEB2 for Acuvim II Series Power Meter
7.4 Logs
Click on the 'Logs' tab to visit the metering logs web pages.
There are six kinds of logs that can be viewed, they are "Trend Log", "Trendlog Management",
"Data Log", "Alarm Log", "SOE Log" Event Log and "Waveform Log"(Only available in AcuVim
IIW model).
Each web page shows data from the Acuvim II series meter.
42
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 45
Chapter 7: Web Interface Readings and Parameter Settings
7.4.1 Trendlog
The Trend Log web page includes the real-time and energy trend diagram. The real-time trend
log diagram can be selected to show the following parameters phase voltage, line voltage,current, active power, reactive power, apparent power and power factor for each phase as well as
the totals. The energy trend log shows the imported and exported active energy, reactive energy, total energy, net energy and apparent energy.
The data of the trend log can be previewed and downloaded as a .csv le by clicking the 'Data
Review'
also be saved as an image by clicking the 'Image'
and 'Data' icons on the right top side of the diagram. The trend log diagram can
icon.
7.4.1.1 Realtime
The real time parameters can be trended at di erent time intervals depending on the Time
Frame selected. Listed below are the time intervals for each possible time frame setting:
Time FrameTime Intervals
1 second
Last 10 minutes
Last 1 Hour1 minute
15 seconds
1 minute
Today
Yesterday
15 minutes
1 hour
15 minutes
1 hour
15 minutes
Last 7 days
1 hour
1 day
Last 30 days
Last Month
1 hour
1 day
1 hour
1 day
Custom RangeDependent on range speci ed
V: 1.11 Revised: May 2020
www.accuenergy.com
43
Page 46
AXM-WEB2 for Acuvim II Series Power Meter
7.4.1.2 Energy
Similarly the energy parameters can be trended at di erent time intervals depending on the
Time Frame selected. The table below displays the time intervals:
Time FrameTime Intervals
Last 10 minutes
Last 1 Hour1 minute
Today
Yesterday
Last 7 days
Last 30 days
This Month
Last Month
Last Year
Custom RangeDependent on range speci ed
15 seconds
1 minute
15 minutes
1 hour
15 minutes
1 hour
15 minutes
1 hour
1 day
1 hour
1 day
1 hour
1 day
1 hour
1 day
1 day
1 month
44
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 47
Chapter 7: Web Interface Readings and Parameter Settings
7.4.1.3 Data Preview
The data preview allows the user to view the graphical data in tabular form.
User can also download this data into a csv le for further examination.
www.accuenergy.com
V: 1.11 Revised: May 2020
45
Page 48
AXM-WEB2 for Acuvim II Series Power Meter
7.4.2 Trendlog Management
The trendlog management page allows the user to download data from the meters data base.
The trendlog management page acts as a back up to the data logs for users.
Log Param Type: Users can select which data they want to download from the meter. In the
drop down menu there is a timestamp range to show the available data.
NOTE: Energy data will remain in meter data base for up to 3 years, whereas all other metering
data will remain in the meter data base for up to 1 month before overriding.
Log Param Type Detail: This setting allows users to modify what values they see in the data log.
Users can select the following parameter details:
• Instantaneous
• Minimum
• Maximum
• Average
Only the 'Real-time' and 'Demand' parameters support the minimum, maximum and average
parameter type details. All other parameter types such as Energy, Power Quality, and IO only
support the instantaneous values displayed in the the data log.
The log le will be downloaded as a .gz le and will need to be unzipped in order to view the csv
le.
46
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 49
Chapter 7: Web Interface Readings and Parameter Settings
7.4.2.1 Clear Logs
The clear logs function allows the user to clear and remove all metering data stored on the
module database. This will allow users to clear all readings and historical data without resetting all features and functions. Users can clear the logs by clicking on the button at the
bottom of the Trendlog page.
To clear the logs click on "Clear Logs", a warning message is displayed notifying users that
this action is irreversible once done.
NOTE: This cannot be undone, once the trend log is cleared all data in meter database is
cleared.
V: 1.11 Revised: May 2020
www.accuenergy.com
47
Page 50
AXM-WEB2 for Acuvim II Series Power Meter
7.4.3 Data Log
The data log web page includes all the data le for three di erent loggers and AcuCloud.
You can select the di erent loggers by clicking the logger tab. After the logger is selected,
the log le for this logger will show on the screen with the update time and le size. To
download the le, click on the download icon
log will be saved as a compressed csv le.
to save the le in the computer. The data
7.4.3.1 Deleting Data Logs
To delete the data logs users can check the box next to the data log le and click on the
'Delete Selected' button at the bottom of the page.
Users will be prompted by a window asking to con rm the data log delete.
NOTE: Deleting the data log is permanent, this cannot be undone once deleted.
48
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 51
Chapter 7: Web Interface Readings and Parameter Settings
7.4.4 Alarm Log
The Alarm Log web page provides the user with a summary of the alarm events that have
occurred with the meter. It will show the status of up to 16 alarm events indicating the
alarm ID, status, parameter, value that exceeded or went below the threshold and the timestamp of the alarm event.
Once all 16 alarm events are full, the newest alarm event will then wrap around to alarm 1.
The parameters in the alarm status web page are updated every 10 seconds.
V: 1.11 Revised: May 2020
www.accuenergy.com
49
Page 52
AXM-WEB2 for Acuvim II Series Power Meter
7.4.5 SOE Log
The SOE web page will display the Sequence of Event log for the enabled I/O module that
is attached to the Acuvim II series meter with timestamps and will display the DI status for
up to 20 SOE events. The SOE must be enabled from the Acuview software.
The SOE log parameters are updated every 10 sec.
50
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 53
Chapter 7: Web Interface Readings and Parameter Settings
7.4.6 Waveform Log
The waveform log is available only on Acuvim IIW models of the Acuvim II series meter.
This meter supports a waveform capture function that allows users to capture and record
10 cycles before and after the triggering point whether it be a voltage sag, swell, or over
current. The waveform log on the web interface allows users to view these waveforms
whenever a power quality event has occurred. The log displays is a table that includes the
waveform les, the time the waveform is updated at, and the size of the le. The waveform le name includes the timestamp when the event occurred as well as the parameter
name/event name that triggered the power quality event.
www.accuenergy.com
V: 1.11 Revised: May 2020
51
Page 54
AXM-WEB2 for Acuvim II Series Power Meter
button.
To view the waveform click on the icon. Users can select which voltage
or current phase they want to view on the graph during the power quality
event.
An image of the graph can be downloaded by clicking on the button.
Users can zoom into the graph for further detail by clicking on the
graph can be reset back by double clicking the
button.
. The
Users can select 'Close' to close the waveform and navigate back to the
waveform Log.
Users can perform a manual waveform capture by clicking on 'Manual
Capture'. This will manually capture voltage and current waveforms of
the system being monitored. Once the waveform is capture it will take
approximately 1-2 minutes to appear in the waveform log.
52
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 55
Chapter 7: Web Interface Readings and Parameter Settings
The le name for the manually captured waveform will include the timestamp the capture
occurred and the reason will say 'MANUAL' at the end of the le.
In the waveform log page, user also have the option to select and delete waveform les.
Simply click on the check box next to the le to select it, alternatively users can click on the
'Select All' button. Once all les are selected click on delete to remove the les from the
waveform log.
V: 1.11 Revised: May 2020
www.accuenergy.com
53
Page 56
AXM-WEB2 for Acuvim II Series Power Meter
7.4.6.1 COMTRADE
The AXM-WEB2 allows users to download the waveform data as a COMTRADE le. COMTRADE is
a le format for storing waveform data related to transient power system disturbances.
The le can be downloaded from the waveform log by clicking on the le name or by clicking
on the
button. Once downloaded the le can be read using a COMTRADE le reader where
users can further analyze the waveform data provided from the meter.
54
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 57
Chapter 7: Web Interface Readings and Parameter Settings
7.4.7 Event Log
The AXM-WEB2 provide the event log page for the user to track the activities of the module.
The user is able to specify the event level and source by choosing the level and the source type.
www.accuenergy.com
V: 1.11 Revised: May 2020
55
Page 58
AXM-WEB2 for Acuvim II Series Power Meter
The user is able to specify the event level and source by choosing the level and the source type.
7.5 About
The About tab located at the top right corner of the web interface allows users to view the Device Information page. This page provides users with information about the Acuvim II series
meter and the AXM-WEB2 module. The Device Information contains the model of the Acuvim
II meter, serial number, rmware version and the meter addresses. It also contains the serial
number, rmware version, hardware version and the MAC addresses of the AXM-WEB2 module.
The disk usage eld at the bottom of the device information page allows users to view the per-
centage of the memory that is used on the AXM-WEB2 module.
56
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 59
Chapter 7: Web Interface Readings and Parameter Settings
7.6 Settings
7.6.1 Meter
7.6.1.1 General Setting
The basic metering congurations needed to set up the meter can be applied from the web
interface by clicking on Settings and selecting the 'Meter' tab. On the metering tab users
will see the 'General' tab selected and the page presented. The general page include the
following settings:
Device Description:
play on the Dashboard page.
Voltage Wiring:
in the drop down list.
Current Wiring:
the current.
PT1:
Enter the rated input of the potential transformer that is connected to the meter. Pos-
sible range is from 50 to 1,000,000V. By default PT1 is 400.
PT2:
Enter the rated output of the potential transformer. Possible range is from 50 to 400V.
The default PT2 setting is 400.
NOTE: If the voltage input is connected directly to the meter and there are no PTs (Potential
Transformers) stepping down the voltage to the meters voltage input then the PT1 and PT2
settings can be left as the default of 400.
A description for the meter can be provided in this eld which will dis-
Select the type of wiring that the meter will be monitoring from the modes
Select the number of CT's that will be connected to the meter to measure
www.accuenergy.com
V: 1.11 Revised: May 2020
57
Page 60
AXM-WEB2 for Acuvim II Series Power Meter
CT1:
Enter the rated input of the current transformer that is used with the meter. Possi-
ble ranges for the CT1 are from 1 to 50000A.
The default settings for CT1 are dependent on the current input type of the Acuvim II
meter. The following table displays the default CT1 values for the dierent Current input options.
Acuvim II Current InputDefault CT1 Value
1A1
5A5
333mV1
RCT1000
80mA/100mA/200mA1
CT2:
Select the rated output of the current transformer from the drop down list. By de-
fault this setting is already congured.
NOTE: CT2 is congurable only for 5A and mA current inputs, 5A can be either 5A or 1A
and mA can be either 80mA, 100mA or 200mA.
58
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 61
Chapter 7: Web Interface Readings and Parameter Settings
Real time Reading:
Select the mode of the readings for the meter when it is polled through
Modbus. By default the meter is in Secondary mode which will require some parameters to
be scaled by a relationship. Conguring the meter in Primary mode does not require any
scaling.
I A Direction:
Represents the ow of direction for the Phase A current being measured, con-
gure this setting to troubleshoot issues related to incorrect polarity of readings such as real
power, Power Factor and etc.
I B Direction:
Represents the ow of direction for the Phase B current being measured, con-
gure this setting to troubleshoot issues related to incorrect polarity of readings such as real
power, Power Factor and etc.
I C Direction:
Represents the ow of direction for the Phase C current being measured, con-
gure this setting to troubleshoot issues related to incorrect polarity of readings such as real
power, Power Factor and etc.
Demand Settings
Sliding Window:
This setting refers to the demand type. There are 4 demand types that are
supported by the Acuvim II series meter, users can choose one of the following:
1. Fixed Window
- The demand is calculated based on selecting the calculation period between 1-30min. The meter will calculate and update the demand values at the end of each
calculation period.
2. Sliding Window
- The demand is calculated by selecting the calculation period between
1-30 min. The meter will average the energy accumulated within this period of time and
the demand value is updated every minute.
3. Thermal
- The demand is calculated based on thermal response, used in thermal demand
meters. This method uses a sliding window to update the demand value at the end of each
calculation period.
4. Rolling Window
- The demand is based on selecting a calculation period between 1-30min,
a subinterval(Demand Calculation Slip Time) and the demand value is updated at each
subinterval. The subinterval must be a factor of the calculation period. For example, with a
calculation period of 15min, the subinterval can be congured as 5min.
Sub Interval:
The sub interval setting is only relevant if the Rolling Window Method is selected, this method requires a sub-interval time that must be a factor of the demand calculation
period. the range for this setting is from 1-30 minutes.
V: 1.11 Revised: May 2020
www.accuenergy.com
59
Page 62
AXM-WEB2 for Acuvim II Series Power Meter
Average Interval:
The average interval window is the calculation period of the demand, and
can be set from 1-30 minutes.
On-board RS485
Protocol:
Select the protocol for the Acuvim II RS485 port, the protocol can be set to Modbus
or DNP 3.
Address:
Baud Rate:
Select the RS485 address for the meter, the range for this setting is from 1-247.
The baud rate is the communication speed of the RS485 data transfer, this rang-
es from 1200-38400.
Parity:
Select the parity bit setting for the communication.
Display
Current Password:
This password relates to the four digit password used to access the me-
ter settings from the display of the meter. By default it is 0000, the range for this setting is
0000-9999.
New Password:
Repeat Password:
60
Enter in a new four digit password.
Repeat the new password con gured in the previous setting
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 63
Chapter 7: Web Interface Readings and Parameter Settings
Backlight:
This setting refers to how long back light on the meters display is on for, the
range is from 0-120 minutes, where 0 would disable to back light from turning o .
Rated Load:
The rated load can be represented in terms of either power or current.
• If current is selected the rated current that is used would be the CT1 setting value in the
PT and CT ratio settings section of the web page. For example if CT1 is set for 1000A,
and the average current the meter is monitoring is 500A, the load percentage would be
50% (500/1000A).
• If power is selected the rated primary power would be used in the load percentage cal-
culation. The max primary power can be calculated as follows:
Max Primary Power without using PTs = 3 * (480) * (CT1)
Max Primary Power using PTs = 3 * (PT1) * (CT1)
The max primary power would be the power that is entered in this setting.
The load percentage is displayed on the front of the Acuvim II meter display. The load
percentage is calculated based on the following equation:
Load Percentage = (Active System Power / ((5A or 1A) * User Setting))) * 100% , where
the meter will have either a 5A or 1A current input. If users have Acuvim II meters with
Rogowski Coil (RCT), 333mV and mA type Current Inputs then they would use 1A in this
equation.
For example if the max primary power of your system is 576000W (or 576kW), your system is currently using 211kW and the meters current input type is 5A, then the load percentage would be calculated as follows:
The energy type can either be selected as Fundamental or Fundamental+Harmonics
Energy Reading:
This can be set to either Primary or Secondary, where Primary displays the
energy accumulation in terms of the Primary and Secondary will display the energy accumulation in terms of the secondary with resolution of up to 1Wh.
NOTE: When the energy reading mode is changed the energy will reset to 0 on the meter.
VAR/PF Convention:
The VAR/PF convention can either be set to IEEE or IEC.
IEC the power factor is dependent on the direction of the real power ow
IEEE the power factor is dependent on the nature of the load, i.e. capacitive, inductive.
62
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 65
Chapter 7: Web Interface Readings and Parameter Settings
VAR Calculation Method:
Can be selected as either True or Generalized
• True Method - Uses the Budeanu Concept to calculate the ‘True’ reactive power. This
method generally takes the harmonic components to do the calculation instead of using
the power vector triangle method. This method can be de ned by the following by the fol-
lowing expression for single phase circuit:
• Generalized Method - UsesFryze's concept to calculate the 'Generalized' reactive power.
This method separates instantaneous current into two components, active and reactive
currents.
Active current is calculated as:
and reactive current as:
V: 1.11 Revised: May 2020
www.accuenergy.com
63
Page 66
AXM-WEB2 for Acuvim II Series Power Meter
Active and reactive powers are:
where
I
and
I
represents RMS values of instantaneous active and reactive currents.
r
a
Optional Seal Con gurations:
this setting:
• Device Run Time
• DI Counters
• Communication Channel 1
• Communication Channel 2
Once all settings have been con gured users can click on save and then perform a module
reboot in order for the settings to be saved to the meter.
Users can choose to seal the following parameters from
64
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 67
Chapter 7: Web Interface Readings and Parameter Settings
7.6.1.2 IO Settings
The Acuvim II supports 3 di erent I/O expansion modules that allow users add Digital Inputs,
Digital Outputs, Relay Outputs, Analog Inputs, and Analog Outputs. There can be a max two of
the same I/O module per meter, and will represented by the I/O logic address 1 or 2. From the
AXM-WEB2 interface users can con gure the settings for these I/O modules.
AXM-IO1-1/2
The AXM-IO1 module supports 4 Digital Input channels, 2 Relay Output channels, and has a built
in 24Vdc supply.
• Digital Input - Can be con gured as either digital status or pulse counter.
• DI Pulse Constant - If the DI is con gured as pulse counter, then the DI pulse constant will
represent how many pulses equals one count, i.e pulse constant is 2 that means that every
2 pulses the inputs reads the counter is increased by 1.
• Relay Output - Can be con gured as Relay Control or Alarm Mode
• Control Mode Output Mode - Can be con gured as Latch or Momentary where users can
manually turn on/o relay
• Latch - Manually turn on/o relay
• Momentary - Manually turn on relay for a short moment of time, the RO On time range is
from 50-3000ms
• Alarm Mode - The relay can be con gured to trigger based on the alarm settings of the
meter.
V: 1.11 Revised: May 2020
www.accuenergy.com
65
Page 68
AXM-WEB2 for Acuvim II Series Power Meter
AXM-IO2-1/2
The AXM-IO2 module supports 4 Digital Input channels, 2 Digital Output channels, and 2
Analog Output channels.
• Digital Input - Can be con gured as either digital status or pulse counter.
• DI Pulse Constant - If the DI is con gured as pulse counter, then the DI pulse constant
will represent how many pulses equals one count, i.e pulse constant is 2 that means
that every 2 pulses the inputs reads the counter is increased by 1.
• Digital Output - Can be con gured for Pulse or Alarm mode.
• DO 1 Output - Users can select the type of energy pulse outputted from DO Channel 1
• DO 2 Output - Users can select the type of energy pulse outputted from DO Channel 2
• There are 4 types of energy that can be used for Energy Pulse Output:
1. System Import Active Energy
2. System Export Active Energy
3. System Import Reactive Energy
4. System Export Reactive Energy
• Pulse Width - Users can con gure the Energy pulse width, the range is from 20-1000ms
• DO Active Energy Pulse Constant - Select the Pulse Constant for Active Energy Pulse,
the range is from 1-60000
• DO Reactive Energy Pulse Constant - Select the Pulse Constant for Reactive Energy
Pulse, the range is from 1-60000
66
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 69
Chapter 7: Web Interface Readings and Parameter Settings
Pulse Constant Calculator
The pulse constant calculator allows users to determine the pulse constant value based
on the amount of energy per pulse required. Users would rst need to input the maximum
primary power which is the CT1 value multiplied by the PT1 value.
Once entered in, users can then scroll down to the 'Primary 1 Pulse =' and enter the value
that one pulse would represent, i.e. 1 pulse = 1kWh. Once this is con gured, a secondary
pulse value will be populated which is the required pulse constant value. Users can import
this value to the pulse constant setting by clicking on the 'Set as Active Energy Constant' or
'Set as Reactive Energy Constant' button.
www.accuenergy.com
V: 1.11 Revised: May 2020
67
Page 70
AXM-WEB2 for Acuvim II Series Power Meter
• Analog Output - There are two analog output channels that users can con gure.
• AO1 Slope - select the slope value, the range is from 1-3
• AO 1 Input Range 1 - Enter in the starting range for the Analog Output
• AO 1 Input Range 2/3/4 - Enter in the ending range for the Analog Output
• AO 1 Output Range 1 - Enter in the analog output signal
• AO 1 Output Range 2/3/4 - Enter in the ending analog output signal.
NOTE: The analog output range can be a 4-20mA, 0-20mA, 0-5V, 1-5V signal depending
on the model of the I/O, either voltage or current model.
The interface displays a graph for the Analog output signal according to the input range
that has been con gured.
Similar to Analog Output channel 1, the second analog output channel can also be
con gured in the same manner from the web interface.
68
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 71
Chapter 7: Web Interface Readings and Parameter Settings
AXM-IO3-1/2
The AXM-IO3 module supports 4 Digital Input channels, 2 Relay Output channels, and 2 Analog
Input channels.
• Digital Input - Can be con gured as either digital status or pulse counter.
• DI Pulse Constant - If the DI is con gured as pulse counter, then the DI pulse constant
will represent how many pulses equals one count, i.e pulse constant is 2 that means that
every 2 pulses the inputs reads the counter is increased by 1.
• Relay Output - Can be con gured as Relay Control or Alarm Mode
• Control Mode Output Mode - Can be con gured as Latch or Momentary where users can
manually turn on/o relay
• Latch - Manually turn on/o relay
• Momentary - Manually turn on relay for a short moment of time, the RO On time range
is from 50-3000ms
• Alarm Mode - The relay can be con gured to trigger based on the alarm settings of the
meter.
www.accuenergy.com
V: 1.11 Revised: May 2020
69
Page 72
AXM-WEB2 for Acuvim II Series Power Meter
• Analog Input - There are two analog input channels, users can select the type based on the
type of module they have.
• The AI types are:
1. 4-20mA
2. 0-20mA
3. 1-5V
4. 0-5V
IO Logic Address
From the WEB2 interface users have the option to change the logic addresses for the AXMIO1 and AXM-IO3 modules. This is useful when users have two modules with the same logic
address. For example if the user has two AXM-IO1-1 and attaches them both to the meter, the
meter will only recognize one of the modules. This function allows the user to change the logic
number from 1 to 2 where the user would then have one AXM-IO1-1 module and one AXM-IO1-2
module.
To change the logic address the module must be attached and installed on the back of the meter after the WEB2 communications module. Simply click on the drop down menu and select
the corresponding logic address.
NOTE: The meter be physically power cycled in order for the logic address change to take e ect.
70
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 73
Chapter 7: Web Interface Readings and Parameter Settings
7.6.1.3 Alarm Settings
The Acuvim II meters supports over/under alarms for dierent metering parameters..From the
WEB2 interface users can congure these alarms on the Alarm page. This page can be found by
clicking on 'Settings' and selecting the 'Alarm' tab.
The meter supports up to 16 Alarm channels that users can monitor when the congured parameter goes over or under the alarm threshold. If users have extended I/O modules attached
to the meter, digital outputs (DO) and relay outputs (RO) can be triggered upon alarm condition
and used to activate external devices such as a buzzer, light, etc.
Alarm Enable:
Backlight Flash Trigger:
The alarm function can be enabled or disabled
If enabled, when an alarm is triggered the backlight of the Acuvim II
meter display will ash during the alarm event.
Steps to setup alarm channels:
• To congure an alarm channel, enable the preferred alarm channel(s).
• Select the required parameter for the alarm channel under the 'Parameter' column.
• Choose the required setpoint and then select the condition for the alarm, i.e greater than (>),
less than (<), or equal to (=).
• Users have the ability to set a delay for the alarm trigger, the range is from 0-30000 ms.
• Users can use the 'AND' function to trigger an alarm event when two conditions have been
met.
www.accuenergy.com
V: 1.11 Revised: May 2020
71
Page 74
AXM-WEB2 for Acuvim II Series Power Meter
• If extended IO modules are being used, users can click on the detail tab to con gure the
digital output and relay outputs to be triggered when an alarm is triggered.
Once all alarm settings are con gured, user must click on 'Save' and then reboot the communi-
cations module in order for the settings to be saved.
7.6.1.4 Custom Read
The Acuvim II meter supports a custom read function which allows users to customize a block of
registers within the Acuvim II meter using di erent parameters (i.e. Basic metering, THD, Energy,
etc) as well as di erent data types for the parameters (i.e. Int, oat, etc). There is a total of 64
bytes that users have to create their customized register block.
NOTE: The Custom Read Function is only available in meters with rmware version 3.51 and
higher.
The window on the left under 'Not Selected' are the list of parameters available for the custom
read block. Users can choose between di erent parameters by clicking on the drop down menu
under 'Parameter Type'. The available parameter types include:
• Real-Time Metering
• Demand
• Energy
• THD
• Sequence
72
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 75
Chapter 7: Web Interface Readings and Parameter Settings
• Phase Angles
• DI Counter
• AO/AI value
Each of these parameter types are available in dierent data types, such as integer (int). oat,
and double-word. Users may select the data type for each parameter from this drop down
menu.
Users can select the parameters and click on the '>' button to add the parameters to the
'Selected' window. The parameters can be removed from the register block by clicking on the
'<' button, and can clear the entire block by selecting the 'Clear' button.
As users add and remove parameters, there is a 'Bytes Used' and 'Bytes Remaining' value that
lets users know how much space is left in the customized register block.
Once the block is congure, users can click on 'Save'.
A copy of the custom read register block can be viewed by selecting 'Custom Reading Table'.
The table can be downloaded as a csv le by clicking on 'Export Table'.
V: 1.11 Revised: May 2020
www.accuenergy.com
73
Page 76
AXM-WEB2 for Acuvim II Series Power Meter
7.6.1.5 Waveform Settings
The Acuvim IIW meters support a waveform caputure feature where users can capture waveforms based on power quality events such as voltage sags, voltage swells and over currents.
From the WEB2 interface, users can con gure these settings by clicking on the 'Settings' tab and
then selecting the 'Wavform' tab.
Rated Voltage:
The rated voltage of the system should be entered here, the range is from 50-
400V for wye systems or 50-690V for delta systems.
Voltage Swell
• Triggering Waveform Capture - Select enable to capture voltage swell events
• Threshold - Enter in the percentage of the voltage swell to be captured, the range is from
50-140%. For example if the rated voltage is 277V, and the voltage swell threshold is set for
110%. The swell event would be captured when the voltage is 110% above 277V, which is
roughly 304V.
Voltage Sag
• Triggering Waveform Capture - Select enable to capture voltage sag events
• Threshold - Enter in the percentage of the voltage sag to be captured, the range is from 20-
74
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 77
Chapter 7: Web Interface Readings and Parameter Settings
100%. For example if the rated voltage is 277V, and the voltage sag threshold is set for 50%.
The sag event would be captured when the voltage drops 50% below 277V, which is roughly
138V.
• Half-cycle Threshold - Enter in the half cycle threshold for the sag event, the range is from
4-200 half cycles.
Rated Current:
The rated current for the over current should be entered here, the range will be
dependent on the CT1 value congured on the meter. The rated current range will be from 50100% of the CT1 value. For example if CT1 is congured as 1000A, then the rated current range
for the Power Quality event is from 500A to 1000A.
Over Current
• Triggering Waveform Capture - Select enable to capture over current events
• Threshold - Enter in the percentage of the over current to be captured, the range is from
50-150%. For example if the rated current is 1000A, and the over current threshold is set
for 50%. The over current event would be captured when the current is 50% of the rated
current, which is 500A.
www.accuenergy.com
V: 1.11 Revised: May 2020
75
Page 78
AXM-WEB2 for Acuvim II Series Power Meter
If user are using external I/O modules, the waveform capture can be triggered by the Digital
Inputs Status. The DI can trigger the waveform by the following:
• From Status O to On
• From Status On to O
• Any Change
The DI triggering can be disabled is users do not require it to trigger the waveform capture.
76
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 79
Chapter 8: Communications
Chapter 8: Communications
The communication setting web page will allow the user to con gure settings related to the Ethernet
networks and the Wireless network. The functions and protocols that the AXM-WEB2 module sup-
ports can be con gured by selecting the corresponding tab such as Emails, Time/Date , Datalog, Acu-
Cloud Post for communicating with the AcuCloud software, BACnet-IP, SNMP, IEC61850, and DNP3.
8.1 Network
The rst page the user will see after selecting the Communications option under the Settings tab is the Network page. The network settings allow users to con gure all network
related settings including both Ethernet 1 and Ethernet 2 as well as WiFi.
8.1.1 RSTP Protocol
The AXM-WEB2 supports the RSTP protocol where users can daisy chain the Ethernet ports
on the AXM-WEB2 module to a network switch.
Users can con gure the meters IP manually or by setting the DHCP set as Auto.
NOTE: When the RSTP is enabled users will not be able to con gure Ethernet 1 and Ethernet
2, there is only 1 IP per meter using RSTP protocol.
Network Topology
Users can can daisy chain up to 32 devices using the RSTP protocol. This can cut down the
amount of network switches required in di erent applications and allows the use of 1 network
switch/router to be used with up to 32 devices. Each device can be accessed by con guring a
unique IP address or having the IP addresses assigned automatically by the network.
V: 1.11 Revised: May 2020
www.accuenergy.com
77
Page 80
AXM-WEB2 for Acuvim II Series Power Meter
8.1.2 VLAN
Virtual Local Area Network (VLAN) allows devices under the same physical network to be
grouped (by VLAN ID) and act as if they are in separate networks. VLANs are isolated from
one another where trac stays private in the same VLAN.
When VLAN of an interface is enabled, it allows the AXM-WEB2 module to communicate with
other devices under the same VLAN without a VLAN switch, via this interface. In other words,
the module can parse IEEE 802.1Q-tagged Ethernet VLAN frames by itself.
Users can enable VLAN from the web interface under either the Ethernet 1 or Ethernet 2 set-
tings, once enabled a VLAN ID is required.
One of the common uses is when RSTP is enabled, the module can be put between two
VLAN switches, where both ETH1 and ETH2 ports connecting to switches' trunk ports. In this
method, the module can still forward all trac between the switches; while other devices in
the same VLAN can have access to the module, and no additional switch is required.
78
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 81
Chapter 8: Communications
8.1.3 Network Settings
The settings for the Ethernet 1 and Ethernet 2 are as follows:
Ethernet 1 DHCP
If set to 'Manual', you'll also need to set the Subnet Mask and Gateway. By default the IP address for ETH1 will be 192.168.1.254
Select 'Auto' to have the meter assigned a IP address automatically. With this selection the
Subnet Mask, and Gateway will also be automatically assigned.
: Select 'Manual' to manually congure the IP address to access the meter.
Note: After changing DHCP to Auto, check the display of the meter(N02 NET Settings) to ob-
tain the new IP address that has been assigned. The new IP address will be displayed only
after a module reboot is performed and completed.
IP Address:
page. Default is 192.168.1.254
Subnet Mask:
this page. Default is 255.255.255.0
Gateway:
web page. Default is 192.168.1.1
The status of the Ethernet 1 port will display if it is connected or disconnected.
Ethernet 2 DHCP:
If congured to 'Manual' the default Manual IP address is 192.168.1.253. Users can congure the IP address to any IP once the DHCP is congured for 'Manual', users will also need to
set the Subnet Mask and Gateway if using this method.
If the DHCP is congured to Manual, the IP address can be congured from this
If the DHCP is congured to Manual, the Subnet Mask can be congured from
If the DHCP is congured to Manual, the Gateway can be congured from this
By default the Ethernet 2 port is congured to have its DHCP set to 'Auto'.
NOTE: The IP address of the Ethernet 2 can be found page N12 of the NET Settings. The
Acuvim II protocol setting must be congured to WEB2 to view this from the meters NET set-
tings.
IP Address:
the DHCP is congured to Manual, the IP address can be congured from this page.
Subnet Mask:
this page.
Gateway:
web page.
The status of the Ethernet 2 port will display if it is connected or disconnected.
www.accuenergy.com
By default the IP address is congured by DHCP, this eld will be grayed out. If
If the DHCP is congured to Manual, the Subnet Mask can be congured from
If the DHCP is congured to Manual, the Gateway can be congured from this
V: 1.11 Revised: May 2020
79
Page 82
AXM-WEB2 for Acuvim II Series Power Meter
WiFi Enabled:
WiFi Mode:
Select the Enable or Disable communication through WiFi.
The WiFi can be congured to work in two modes just like any other WIFI device. It
can be congured as either Access Point(AP) or Station mode.
Access Point:
Default conguration for AXM-WEB2. The AXM-WEB2 will act as a wireless access
point and will allow other wireless devices to connect and access the AXM-WEB2.
• In Access Point mode, users can congure the SSID, Network Key and IP of the AXM-WEB2
module as well as the DHCP DNS servers.
Station:
The AXM-WEB2 will behave like a wireless client and bridge to another wireless net-
work that is available.
• In Station mode, users can select the Wireless network to connect to under the "Connect
to SSID" setting. Click on "Select from Available Networks" and enter the Network Key for
the wireless network that the AXM-WEB2 will bridge to.
• If users are connecting to an open Wireless network that is not password protection, the
password eld can be left blank.
• The AXM-WEB2 also supports Enterprise WiFi, where users can connect using an enterprise level WiFi network which is common in many colleges/universities, hospitals, etc.
When attempting to connect to an enterprise level WiFi network the interface will show
options to connect to the network with a username and password.
80
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 83
Chapter 8: Communications
In station Mode the DHCP can congured as either manual or auto.
• If manual, users can congure the IP, Subnet Mask and Gateway and DNS Servers.
• If auto, users can check the meter's display to get the IP address and all other network
congurations assigned by the wireless network. The user can also congure the DNS
servers if the DHCP is set to Auto.
NOTE: The WiFi IP address for the AXM-WEB2 will be in parameter N11 of the NET settings.
The Acuvim II protocol setting must be congured to WEB2 to view this from the meters NET
settings.
DNS Server 1:
DNS Server 2:
HTTPS Port:
Enter the address of DNS server 1 in this eld.
Enter the address of DNS server 2 in this eld.
Enter the HTTPS port number of the meter. By default, this setting is congured
to 443. The range can be from 6000 to 9999.
Meter Channel 2 Address (Modbus TCP):
Enter the Modbus TCP address of the meter. By
default, the address is 1.
NOTE: This setting should never be congured to 80. Enable the HTTP Enable conguration to access the web interface at port 80.
HTTP Enable:
Enable HTTP so the the AXM-WEB2 cab be accessed through the HTTP protocol,
by default the HTTP port is 80 but it can be congured from 6000-9999.
Modbus TCP Port:
Enter the Modbus port number of the meter. By default, this setting is con-
gured to 502. The range can be from 2000 to 5999.
Fast Read Mode Enable:
Selecting Enable allows the user to read the real time parameters at
100ms.
• Frequency Adjustment:
Allows users to control the rate of change of frequency. The range
can be set from 1.00-5.00 Hz/s, by default this is set for 1 Hz/s.
V: 1.11 Revised: May 2020
www.accuenergy.com
81
Page 84
AXM-WEB2 for Acuvim II Series Power Meter
• The minimum range is 45Hz and the max range is 65Hz, any frequency outside of the
range will not have the frequency adjustment applied.
NOTE: Frequency Adjustment is only available when the meter is in Fast Read Mode.
NOTE: When Fast Read mode is enabled, all functions except Modbus and the Web server are disabled.
Proxy Server Enable:
Select enable to allow for forwarding of data log les to pass through
the Proxy server rst and then the data post server. IE. AcuCloud.
After making any changes on the network settings page, click 'Save'. Users will be prompted
to reboot the AXM-WEB2 immediately or later. If later is chosen the AXM-WEB2 will need to be
rebooted from the 'Management' page in order for the settings to take e ect.
82
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 85
Chapter 8: Communications
8.1.4 Default Routing Interface (Outbound Traic)
The AXM-WEB2 supports a routing default interface setting which allows users to congure
which port to use for primary routing to external networks. Since there are multiple ways the
user can connect such as Ethernet1/2, WIFI, RSTP, this setting will establish which one is used for
the main routing interface. The other interfaces can be used for local routing if being used.
Users can select the default routing interface as:
• Ethernet 1
• Ethernet 2
• WIFI - only valid if WIFI is congured for station mode
• Bridge (RSTP) - only valid if RSTP is enabled
8.2 IPv6
The AXM-WEB2 module supports IPv6 communication where users can use IPv6 to access the
web interface as well as connect via SNMP protocol. The settings for IPv6 can be accessed by
clicking on Settings and selecting the Communications tab. On the Communications page se-
lect the IPv6 tab to congure the settings.
V: 1.11 Revised: May 2020
www.accuenergy.com
83
Page 86
AXM-WEB2 for Acuvim II Series Power Meter
IPv6 Enable:
Ethernet DHCP:
Enable to access the settings for IPv6
This can be set to manual or auto.
• When set to Manual, users must congure the IPv6 address, the Subnet Prex Length, and
the Gateway.
• When set to Auto, the network will assign an IPv6 address automatically.
Ethernet Link Local Address:
Is an IPv6 address that is automatically congured on the device
with prex 'fe80' followed by the MAC address of the module.
Ethernet Status:
Displays whether there is an Ethernet cable connected or disconnected.
84
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 87
Chapter 8: Communications
8.3 Access Control
The AXM-WEB2 supports the access control function, also known as the IP whitelist.
When enabled, only the selected IP addresses can access the meter’s web interface. Users can
enter in an IPv4 or IPv6 address along with a description for the address. There is a maximum of
20 IP addresses that can be added to the IP Whitelist.
www.accuenergy.com
V: 1.11 Revised: May 2020
85
Page 88
AXM-WEB2 for Acuvim II Series Power Meter
Users can import the IP whitelist or export an existing IP whitelist.
Click “Choose File” to import an whitelist, it should be an CSV le looks like below.
To export the IP whitelist, simply add the IP addresses and click “Export”. A CSV le will be
downloaded automatically.
86
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 89
Chapter 8: Communications
8.4 Email
The AXM-WEB2 supports the SMTP protocol where users can setup the email function to enable
the meter to send emails based on a speci c time interval or whenever there is an alarm or SOE
event or a combination of both. The Email con guration page can be accessed by clicking on
the 'Email' tab on the settings page. Users must know their SMTP server provider and details
regarding their SMTP server, which can be provided by users' IT personnel.
There are three modes available for sending emails that the user can enable.
The rst mode is 'Triggered Sending' where emails are sent immediately when there is a new
alarm, SOE, or waveform event.
The second mode is 'Timed Sending' where users can receive emails at a certain period of time
based on the time interval con gured. The email will include the data that is selected to be sent.
The third mode is when both of the above are enabled.
To use this function the following settings need to be con gured:
SMTP Enabled:
Select 'Enable' to enable and to further con gure the settings related to the
SMTP function.
Start Time to Send Email:
• Click on the
• Click on the
www.accuenergy.com
icon to con gure the time and date.
icon in the bottom right to clear the time and date.
Select the date and time for when the emails should begin to send.
V: 1.11 Revised: May 2020
87
Page 90
AXM-WEB2 for Acuvim II Series Power Meter
SMTP Server:
Enter the URL of a valid SMTP server. I.E. mail.accuenergy.com or smtp.gmail.
com
SMTP Port:
SMTP From:
Enter the port number associated with the SMTP server.
Enter a name or phrase which will appear to let you know who the mail is from. I.E.
'Technical Support'
SMTP Subject:
Authentication:
Enter a subject line for the emails
Users can have email authentication on or o. If authentication is on users
will need to provide the SMTP username and password.
• SMTP Username:
• SMTP Password:
• TLS/SSL:
Users have the option to send emails using TLS/SSL protocols
Enter the SMTP user name for the SMTP server set above.
Enter the SMTP user password for the username set above.
SMTP To Address 1;2;3:
Enter up to three recipients that you wish to have the email sent to in
'SMTP To Address 1', 'SMTP To Address 2' and 'SMTP To Address 3'.
Test Address 1,2,3:
Test the if the email can be sent to 'SMTP To Address 1', 'SMTP To Address 2',
'SMTP To Address 3'.
NOTE: If the test address function fails, users can view the email post failure by clicking on the
'Details' option from the test post screen.
88
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 91
Chapter 8: Communications
After conguring the above settings, the next step is to select the content for the emails.
The content of the emails can either be time based triggered or event based triggered.
For receiving emails on a time based under Enable Periodic Email Reporting:
Enter a time between 5-1440 mins in the Set time interval
• Check o the box beside the parameters for the content the user should receive.
• Metering Data:
• Energy Data:
• Harmonics Data:
• Sequence & Phase Angles:
Report on Real-time voltage, current, power and etc.
Report on energy parameters.
Report on the voltage and current harmonics from 2nd to 63rd.
Report on the positive, negative and zero components of the
voltage and current waveform.
• Min/Max:
Report on the maximum and minimum statistics that the meter has recorded
since the lifetime of the meter or from the last reset of the min/max statistics.
• Alarm:
• SOE Record:
• Waveform:
www.accuenergy.com
Report of the alarm log.
Report of the SOE log.
Report of the waveform log.
V: 1.11 Revised: May 2020
89
Page 92
AXM-WEB2 for Acuvim II Series Power Meter
The user will receive an email with csv le attachment.
For receiving emails on a event based select either Alarm Event, SOE Record or Waveform Data
under the Enable Real-time Email Reporting.
NOTE: Waveform Data is only available for Acuvim IIW model
.
The user will receive an email with csv le attachment corresponding to the triggered event
selected.
8.5 Time/Date
The device clock of the Acuvim II series meter can be set through the web interface of the AXM-
WEB2 module. The AXM-WEB2 module also supports the NTP (Network Time Protocol) protocol
so that the module can update the meter's device clock by synchronizing with a time server.
The module can sync with up to 3 time servers. If a time server is down, the module will syn-
chronize with the second or third time server if they are con gured.
The settings for the time and date can be found by clicking on the 'Settings' and selecting the
'Communications' tab. Users can select 'Time/Date' to con gure the time settings.
The following must be con gured to set the time/date and NTP settings:
NTP Enabled:
Select enable to further con gure the settings related to the NTP (Network Time
Protocol) function
Device Clock:
• Click on the
• Click on the
90
Con gure the date and time on the meter
icon to con gure the date and time.
icon in the bottom right to clear the time and date.
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 93
Chapter 8: Communications
Sync Time:
NTP Type:
Click on Force Update to have the AXM-WEB2 sync its time with the NTP server
Select the NTP type from NTP or SNTP. SNTP should be selected when using the
IEC61850 protocol.
NTP Server 1;2;3:
Enter up to 3 NTP servers in the "NTP Server 1", "NTP Server 2" and "NTP
Server 3" elds.
Examples of North American SNTP servers are:
0.us.pool.ntp.org
1.us.pool.ntp.org
2.us.pool.ntp.org
3.us.pool.ntp.org
For more NTP servers based on region, visit the following site:
http://www.pool.ntp.org/en/
Time Zone: Select the time zone the meter is in or the time zone in which you would like the
meter's time to be synchronized to from the drop down list. Users can also select the timezone
by clicking on the region in the map.
Click 'Save' after conguring the time settings. Users will be prompted to reboot the AXM-WEB2
immediately or later. If later is chosen the AXM-WEB2 must be rebooted from the 'Management'
page in order for the settings to take eect.
www.accuenergy.com
V: 1.11 Revised: May 2020
91
Page 94
AXM-WEB2 for Acuvim II Series Power Meter
8.6 Data Log
The AXM-WEB2 supports logging data onto its on board memory.
The module supports three loggers for di erent parameters and requirements.
The data can be downloaded as a .csv le from the datalog page in the logs section or by using
a HTTP/FTP client.
Logger Enable:
To use the data log function to log the data onto the module, select 'Enable' to
view and con gure the settings that are applicable.
Post Channel:
Select the channel to push the datalog to. Only an enabled post channel can be
selected here. A post channel can be enabled in the 'Post Channel' tab on the settings page.
Log Param Type:
Users can select the type of parameters they wish to log into logger.
Users can use the '>' button to add selected parameters into the data log, and use the '<' button to remove selected parameters from the data log. Users can also use the 'All' or 'Clear'
buttons to add all or clear all parameters to and from the data log. The supported parameter
types include real-time readings, energy readings, demand readings, power quality readings
and I/O readings.
92
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 95
Chapter 8: Communications
Log Param Type Detail:
This setting allows users to modify what values they see in the data
log. Users can select the following parameter details:
• Instantaneous
• Minimum
• Maximum
• Average
Only the 'Real-time' and 'Demand' parameters support the minimum, maximum and average
parameter type details. All other parameter types such as Energy, Power Quality, and IO only
support the instantaneous values displayed in the the data log.
The image below describes how these parameter details function in the data log. The image of
the csv le below depicts a sample of a data log where the data is logged every 5 minutes. The
rst few columns are highlighted showing the Phase A Line-Neutral voltage.
• Column B highlighted in yellow shows the instantaneous value for Phase A voltage at every 5 minute interval.
• Column C highlighted in green shows the minimum value for Phase A voltage between
each 5 minute interval.
• Column D highlighted in red shows the maximum value for Phase A voltage between each
5 minute interval.
• Column E highlighted in orange shows the average value for Phase A between each
5 minute interval.
Log File Format:
Users can select the log le format at either JSON or CSV.
NOTE: JSON format is only supported via HTTP/FTP/MQTT posting and is not supported when
logging data locally to the module memory. Only CSV le format is supported for local log les.
V: 1.11 Revised: May 2020
www.accuenergy.com
93
Page 96
AXM-WEB2 for Acuvim II Series Power Meter
Timestamp Format:
Select the format of the timestamp for the data that is logged.
The format for the timestamp can be based on the Local Time (not available for
JSON format), UTC Seconds or based on ISO8601 Format.
Log File Name Format:
Select the format of the log le name for the data that is
logged. The format for the log le name can be based on the UTC timestamp or
based on Time Interval Format.
Log Interval:
Select how frequently the meter will log data to the le that will be uploaded to the server from the drop down list. The logging interval can be from 1 second
to 1 month. The minimum time interval option is according to the selected parameter.
• The Real-time & IO's min Log Interval is 1 sec
• The Energy's min Log Interval is 15 sec
• The Demand & Power Quality's min Log Interval is 1 min
NOTE: If selected parameters are Real-time and I/O, the min log interval is 1 sec.
If selected parameters are Real-time and Energy, the min log interval is 15 sec.
Post File Length:
Select how frequently the log le will be uploaded to the server
from the drop down list The log le length can be from 1 minute to 1 month.
Log File Name Prex:
Provide a name for the log le posted to post channel which will be
appended to the beginning of the log le if "Time Interval Format" is selected as the Post
File Name Format. By default "logger1" will be appended to the beginning of the log le.
Local Log File Length:
Select the length of the local log le as 1 hour, 1 day, 7 days
or 1 month of data from the drop down list. The log le will appear at the end of the
log le length interval, for example if set for 1 day users will not see the local logs
until the next day at 12AM. See the table below for more details.
Local Log File LengthDate ConguredDate log le will appear in module
1 hourNovember 11th 2020 at 1:00PMNovember 11th 2020 at 2PM
1 dayNovember 11th 2020 at 1PMNovember 12th 2020 at 12AM
7 daysNovember 11th 2020 at 1PMNovember 18th 2020 at 12AM
1 monthNovember 11th 2020 at 1PMDecember 11th 2020 at 12AM
Local Log File Name Prex:
Provide a name for the local log le which will be appended to the beginning of the log le if "Time Interval Format" is selected as the Post File
Name Format. By default "logger1" will be appended to the beginning of the log le.
94
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 97
Chapter 8: Communications
NOTE: The Post File Length and Local Log File Length must be less than or equal to the log interval selected.
www.accuenergy.com
V: 1.11 Revised: May 2020
95
Page 98
AXM-WEB2 for Acuvim II Series Power Meter
SFTP Enable:
To download the logged data from the module using a FTP client, select Enable. The
log le will then be available to be downloaded using a FTP client using the following credentials:
Host: sftp://IPaddressofthemeter
Username: sftpuser
SFTP Password: accuenergy
Port: 22
By default the password for retrieving the backup log les is accuenergy. The user can
con gure any password or can reset to the default of accuenergy by clicking on the "Reset SFTP
Password".
NOTE: A ter enabling the SFTP function the user must reboot the communication module in
order to access the data logs with the default password of 'accuenergy'.
Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB2
immediately or later. If later is chosen the AXM-WEB2 must be rebooted from the 'Management'
page in order for the changes to take e ect.
8.7 Post Channel
The AXM-WEB2 supports the HTTP and FTP Post functions to send data from the meter to a
HTTP/FTP server. The AXM-WEB2 can post.csv/.json les to three di erent HTTP or FTP servers
using HTTP Post or FTP Post.
In the case when there is no connection to the server, the AXM-WEB2 will store the posts and
send it out after the connection is restored. The module can store up to 3GB of cache post les.
The Clear Post Channel Logs button will allow users to clear the bu ered les on meter.
NOTE: If the disk usage exceeds 85% the module will begin to delete some older backup /post
cached les.
96
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Page 99
Chapter 8: Communications
The AXM-WEB2 can post data to a server at intervals of time ranging from 1 minute to 1 month.
The settings for con guring the post channels to post the data can be found by clicking on 'Settings' and then selecting 'Communications' tab. Click "Post Channels" to con gure any of the
three post channels.
Post Channel 1/2/3 Enable:
Enable the Post Channel 1 in order to con gure the settings need-
ed to post data via the HTTP(S)/FTP post functions
Post Method:
Post Name Fixed:
Select the method for posting the les, the user can choose HTTP/HTTPS or FTP
This con guration needs to be enabled in order for user to control the name
of the le that will be posted. Otherwise le name will be based on the Log File Name Format
con guration from the Data Log settings
Post File Name:
Users can enter a name for the le that will be posted as if 'Post Name Fixed' is enabled
If the HTTP/HTTPs post method is selected:
Need Authorization:
If the HTTP server requires some sort of password/authorization in order to
send les users can enter that under the token eld.
HTTP/HTTPS URL:
Enter the URL for the HTTP/HTTPS server. The URL needs to begin with the
pre x http:// or (https://)
HTTP/HTTPS Port:
HTTP/HTTPS Meter ID:
Enter the port number the server will be listening on
Enter a name or description for the meter to be identi ed on the server
If the FTP post method is selected:
FTP URL:
Enter the URL for the FTP server. The URL needs to begin with the pre x ftp://
FTP Port:
FTP Username:
FTP Password:
Enter the port number the server will be listening on
Enter the username required to log into the FTP server
Enter the password required to log into the FTP server
NOTE: The 'TEST Post Channel' button should only be utilized after clicking the 'Save' button
otherwise a fail response will be observed. If a fail response occurs after clicking 'Save' con rm
the network settings or credentials for the server.
V: 1.11 Revised: May 2020
www.accuenergy.com
97
Page 100
AXM-WEB2 for Acuvim II Series Power Meter
Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB2 immediately or later. If later is chosen the AXM-WEB2 must be rebooted from the 'Management' page
in order for the settings to take eect.
Select the Post Channel 2 tab to congure the settings for post to a second server.
Post Channel 2 Enable:
Enable the Post Channel 2 in order to congure the settings needed to
post data via the HTTP(S)/FTP post functions
Post Method:
Post Name Fixed:
Select the method for posting the les, the user can choose HTTP/HTTPS or FTP
This conguration needs to be enabled in order for user to control the name
of the le that will be posted. Otherwise le name will be based on the Log File Name Format
conguration from the Data Log settings
Post File Name:
User can enter a name for the le that will be posted as if Post Name Fixed is
enabled
If the HTTP/HTTPs post method is selected:
HTTP/HTTPS URL:
Enter the URL for the HTTP/HTTPS server. The URL needs to begin with the
prex http:// or (https://)
98
V: 1.12 Revised: Dec 2020
www.accuenergy.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.