AcuRev 2100
Smart Metering System
Page 2

Copyright © 2021 V1.00
This manual may not be altered or reproduced in whole or in part by any means
without the expressed written consent of Accuenergy.
II
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 3

The information contained in this document is believed to be accurate at the time
of publication, however, Accuenergy assumes no responsibility for any errors which may
appear here and reserves the right to make changes without notice. Please ask the local
representative for latest product specications before ordering.
Please read this manual carefully before installation, operation and maintenance of the
AcuRev 2100 Series Power Meter. The following symbols in this manual are used to provide
warning of danger or risk during the installation and operation of the meters.
Electric Shock Symbol: Carries information about procedures which must be
followed to reduce the risk of electric shock and danger to personal health.
Safety Alert Symbol: Carries information about circumstances which if not
considered may result in injury or death.
Prior to maintenance and repair, the equipment must be de-energized and grounded. All
maintenance work must be performed by qualied, competent accredited professionals who
have received formal training and have experience with high voltage and current devices.
Accuenergy shall not be responsible or liable for any damages or injuries caused by improper
meter installation and/or operation.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
1
Page 4

Table of Contents
Chapter 1 - Introduction .......................................................................................5
1.1 Introduction to Ethernet .............................................................................................. 6
Chapter 2 - Functional Description of the Ethernet module ............................7
Chapter 3 - Installation Method ...........................................................................9
3.1 Denition of RJ45 ....................................................................................................... 10
Chapter 4 - Initializing the Ethernet Module ....................................................11
4.1 Cable ............................................................................................................................12
Chapter 5 - Connection Method .........................................................................13
5.1 Direct Connect to a Computer .................................................................................. 14
5.2 Direct Connect to a Router/Switch ........................................................................... 17
5.3 Connect through WiFi ................................................................................................18
5.4 Description of Modbus-TCP Protocol ....................................................................... 18
5.4.1 Protocol ............................................................................................................18
a. Data Frame Format ........................................................................................ 18
b. Modbus Application Header (MBA Header) Field ......................................19
c. Function Field .................................................................................................. 19
d. Data Field ........................................................................................................20
5.4.2 Format of communication .............................................................................. 20
Explanation of frame .........................................................................................20
Chapter 6 - Web Interface Readings and Parameter Settings ........................22
6.1 User Access Login ....................................................................................................... 23
6.2 Dashboard ................................................................................................................... 24
6.3 Metering web page ..................................................................................................... 25
6.3.1 Basic Metering .................................................................................................26
6.3.2 Demand ............................................................................................................ 27
6.3.3 Energy ............................................................................................................... 28
6.3.4 Harmonics ........................................................................................................ 29
6.3.5 I/O ...................................................................................................................... 30
6.4 Logs ..............................................................................................................................31
2
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 5

6.4.1 Trend Log ..........................................................................................................32
6.4.1.1 Real-Time Parameters ........................................................................... 33
6.4.1.2 Energy .....................................................................................................34
6.4.2 Data log ............................................................................................................. 35
6.4.3 Alarm Log .........................................................................................................36
6.4.4 Event Log .......................................................................................................... 37
6.5 About ........................................................................................................................... 37
6.6 Settings ........................................................................................................................38
6.6.1 Meter ................................................................................................................. 38
Chapter 7 - Communications ..............................................................................39
7.1 Network .......................................................................................................................40
7.1.1 Network Settings .............................................................................................40
7.2 Email ............................................................................................................................. 44
7.3 Time/Date .................................................................................................................... 48
7.4 Data Log ....................................................................................................................... 49
7.5 Post Channel ...............................................................................................................52
7.6 AcuCloud ...................................................................................................................... 54
7.7 BACnet/IP ..................................................................................................................... 56
7.8 SNMP ............................................................................................................................ 57
7.9 MQTT ............................................................................................................................ 58
7.9.1 MQTT General Settings ................................................................................... 58
7.9.2 MQTT Authentication ...................................................................................... 59
7.9.3 MQTT Encryption ............................................................................................. 60
7.9.4 Last Will & Testament .....................................................................................60
7.9.5 Topic and Parameter Selection ...................................................................... 61
7.10 Remote Access .......................................................................................................... 62
Chapter 8 - Management ....................................................................................64
8.1 Parameter Reset ......................................................................................................... 65
8.2 Reboot Meter & Communications Module .............................................................65
8.3 Change Password ...................................................................................................... 66
8.4 SSH ...............................................................................................................................66
V: 1.00 Revised: Jan 2021
www.accuenergy.com
3
Page 6

8.5 Debug Diagnostic .......................................................................................................66
8.6 Diagnostic File ............................................................................................................. 67
Chapter 9 - Network Diagnostic .........................................................................68
9.1 Network Status ...........................................................................................................69
9.2 Host Lookup ................................................................................................................ 70
9.3 Connection Test .......................................................................................................... 70
Chapter - 10 Firmware .........................................................................................71
10.1 Module Firmware Update .......................................................................................72
10.1.1 Manual Update .............................................................................................. 73
10.1.2 Remote Update..............................................................................................74
Chapter 11 - Config Management ......................................................................77
11.1 Backup Conguration ..............................................................................................79
11.2 Export/Apply Conguration ....................................................................................80
11.3 Import Conguration ............................................................................................... 81
4
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 7

Series Power Meter: Web Manual
Chapter 1: Introduction
1.1 Introduction to Ethernet
Page 8

AcuRev 2100 Series Power Meter: Web Manual
Chapter 1: Introduction
The AcuRev 2100 meter provides a dual Ethernet and WiFi communication channel. Users will
be able to use both Ethernet ports and WiFi simultaneously with dierent networks and data
acquisition systems.
1.1 Introduction to Ethernet
Ethernet was originally developed by Xerox and then further developed by DEC and Intel. This
networking technology uses Carrier Sense Multiple Access with Collision Detection (CDSM/CD)
protocol and provides transmission speeds up to 100Mbps.
Ethernet is not a network but more of a standard. It is the most current communication
standard Local Area Network (LAN). This standard denes the type of cable that is used and
the method of Signal Processing. The AcuRev 2100 meter supports two Ethernet channels.
6
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 9

Series Power Meter: Web Manual
Chapter 2: Functional Description
Chapter 2: Functional Description
of the Ethernet Module
Page 10

AcuRev 2100 Series Power Meter: Web Manual
Chapter 2:
Functional Description of the Ethernet module
The AcuRev 2100 meter supports a wide range of communication protocols. Some of the
more commonly used protocols are briey explained below.
This module supports the Modbus-TCP protocol. When connected to the AcuRev 2100 series
meter, it is a slave device that can only respond to queries. The default value for the Modbus
Port is 502. The user-dened range is 2000~5999.
The AcuRev 2100 grants users the ability to send emails based on a time interval or when
there is a triggered event using the SMTP protocol. It can send mail from encrypted servers
and servers that use dierent SMTP ports.
The AcuRev 2100 supports HTTPS protocol. It is used as an HTTPS server and where the
default value of the protocol port is 443. Using the HTTPS protocol, the AcuRev 2100 can send
post requests to both HTTP and HTTPS servers.
The following are all the protocols supported by the AcuRev 2100:
• Modbus TCP
• BACnet-IP
• SNMP V2
• HTTP/HTTPs
• FTP
• sFTP
• Wi-Fi WPA, WPA Enterprise
• NTP
• SMTP
• MQTT
8
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 11

Series Power Meter: Web Manual
Chapter 3: Appearance and Dimensions
Chapter 3: Installation Method
3.1 Denition of RJ45
Page 12

AcuRev 2100 Series Power Meter: Web Manual
Chapter 3: Appearance and Dimensions
3.1 Denition of RJ45
The AcuRev 2100 uses two standard RJ45 connectors to access the Ethernet network. The
mechanical and electrical characteristics of the connector are consistent with the requirements
of IEC 603-7.
LED_L (Yellow): Displays the speed status. When the LED is on it indicates 100Mpbs, whiles an
o LED represents a speed of 10Mbps.
LED_R (Green): Displays the link and activity status. When the LED is on it indicates the link
status. When the LED is ashing it indicates that there is activity.
10
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 13

Series Power Meter: Web Manual
Chapter 4: Installation
Chapter 4: Initializing the Ethernet Module
4.1 Cable
Page 14

AcuRev 2100 Series Power Meter: Web Manual
Chapter 4: Initializing the Ethernet module
The default settings in the AcuRev 2100 meter series meter are as follows:
Ethernet 1 (Static IP address)
• IP Address (192.168.1.254)
• Subnet Mask (255.255.255.0)
• Gateway (192.168.1.1)
• DNS Server 1 (8.8.8.8)
• DNS Server 2 (8.8.4.4)
• Modbus Port 502
4.1 Cable
An RJ45 cable is needed to connect the meter to the network.
A shielded twisted pair cable (standard 568A or standard 568B) is recommended as a
reference to the EIA/TIA standard.
12
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 15

Series Power Meter: Web Manual
Chapter 5: LED Description
Chapter 5: Connection Method
5.1 Direct Connect to a Computer
5.2 Direct Connect to a Router/Switch
5.3 Connect through WiFi
5.4 Description of Modbus-TCP Protocol
Page 16

AcuRev 2100 Series Power Meter: Web Manual
Chapter 5: Connection Method
5.1 Direct Connect to a Computer
The AcuRev 2100 can be connected to a computer using a crossover cable (standard 568A).
The AcuRev 2100 module supports Modbus-TCP and HTTPS Functions for this method of
connection.
To connect the meter directly to the computer, the computer's IP must be within the same
subnet as the meter's IP address. The following steps outline how to change the computers IP
using a computer running the Windows OS:
• Manually connect the meter via Ethernet cable to the computer
• Right-click on the connection icon
• Select "Open Network Sharing Center"
• Click on Change adapter options
14
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 17

Chapter 5: Connection Method
• Once there, right-click on the local area connection icon and select properties.
• Select the icon that says Internet Protocol Version 4 TCP/IP
www.accuenergy.com
V: 1.00 Revised: Jan 2021
15
Page 18

AcuRev 2100 Series Power Meter: Web Manual
• The Internet Protocol Version 4 (TCP/IP) Properties box will pop up
• Click on ''Use the following IP address'' and enter an IP number so that the meter and
computer are in the same local network range. For example, if the meter has an IP
address of 192.168.1.254, then the computer must be assigned with an IP 192.168.1.xxx,
where xxx can be any number but cannot be the same as the value the meter has.
16
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 19

Chapter 5: Connection Method
• Once you have entered in the IP address, press the Tab key on your keyboard until you
hit the bottom and click OK
• Before selecting the OK button make note of the IP address you have assigned to the
meter and then press OK.
NOTE: The meter and computer cannot have the same IP address, they must be dierent.
5.2 Direct Connect to a Router/Switch
The AcuRev 2100 can be connected to a router or switch using a patch cable. The DHCP can be
congured to Auto to have the router assign the meter with an IP address or the DHCP can be
congured to Manual to set an IP address and network settings manually.
AcuRev 2100 has two Ethernet ports, Ethernet 1 is set to have the static DHCP, and Ethernet 2
is set to have the dynamic DHCP. Both of the Ethernet ports have the same functionalities, you
can use either of them according to the requirement.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
17
Page 20

AcuRev 2100 Series Power Meter: Web Manual
5.3 Connect through WiFi
The AcuRev 2100 can be connected through a WiFi network.
By default, the AcuRev 2100 will be in Access Point mode with the default IP address of
192.168.100.1. Ensure the device connecting to the AcuRev 2100 has DHCP enabled or it
should be in the same subnet as the AcuRev 2100. The module will appear in the WiFi network
as AcuRev 2100-WIFI-(serial number of the module) as the SSID or name of the wireless
network. By default, the network key or password will be ''accuenergy''.
• Once connected to the network, open an internet browser and type in the IP address of
the WIFI module: 192.168.100.1
• Log in at Admin access level, using the default password of 'admin'.
5.4 Description of Modbus-TCP Protocol
The Modbus-TCP protocol is used as one of the communication protocols in the AcuRev 2100.
The protocol establishes a master and slave connection in Ethernet. The master device (client)
rst sets up a TCP-IP link with the slave device(server). The master device then sends a request
to the slave device and the slave device in return sends a response to the master device. The
gure below shows how the Modbus-TCP protocol works.
5.4.1 Protocol
a. Data Frame Format
MBAP Header Function Data
7x8 bits 8-bits Nx8 bits
18
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 21

Chapter 5: Connection Method
b. Modbus Application Header (MBA Header) Field
The Modbus application header eld is the start of the data frame and consists of seven bytes.
Field Length Description
Transaction Identier 2 Bytes
Identication of a Modbus Request/Response
transaction
Protocol Identier 2 Bytes Modbus Protocol = 0
Length 2 Bytes Number of following bytes
Unit Identier 1 Bytes Slave address, in the range of 0-247 decimal
c. Function Field
The function code eld of a message frame contains eight bits. Valid codes are in the range of
1-255. When a message is sent from a client to a server device, the function code eld tells the
server what kinds of action to perform.
Code Meaning Action
05 Control Single Relay Output Force Relay to a state of ON or OFF
01 Read Relay Output Status Obtain current status of Relay Output
02 Read Digital Input (DI) Status Obtain current status of Digital Input
03 Read Data Obtain current binary value in one or more registers
16 Write Multiple Registers
www.accuenergy.com
Place specic value into a series of consecutive
multiple registers
V: 1.00 Revised: Jan 2021
19
Page 22

AcuRev 2100 Series Power Meter: Web Manual
d. Data Field
The data eld is constructed using sets of two hexadecimal digits, in the range of 00 to FF. The
data eld of messages sent from a master to a slave contains additional information that the
slave must use to take the action dened by the function code. This can include information
such as the register addresses, the number of registers to query and the count of the actual
number of data bytes. For example, if the master requests a slave to read a group of holding
registers (function code 03), the data field specifies the starting register and how many
registers are to be read.
If the master needs to write data (function code 10 hexadecimal) to a group of registers in the
slave, the data eld species the starting register, how many registers to write, the count of
data bytes to follow in the data eld and the data to be written into the registers.
5.4.2 Format of Communication
Explanation of frame
Transaction
identier hi
Transaction
identier lo
Protocol
identier hi
Protocol
identier lo
Length hi Length lo
Unit
identier
00H 00H 00H 00H 00H 06H 01H
Function Code Data start register hi Data start register lo Data # of registers hi Data # of registers lo
03H 40H 00H 00H 48H
The meaning of each abbreviated eld above is:
Transaction identier hi: High byte of the transaction identier
Transaction identier lo: Low byte of the transaction identier
Protocol identier hi: High byte of the protocol identier
Protocol identier low: Low byte of the protocol identier
Length hi: High byte of length
Length lo: Low byte of length
Unit identier: Slave address
20
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 23

Chapter 5: Connection Method
Fun: Function code
Data start register hi: High byte of starting register address
Data start register lo: Low byte of starting register address
Data # of registers hi: High byte of number of registers
Data # of registers lo: Low byte of number of registers
www.accuenergy.com
V: 1.00 Revised: Jan 2021
21
Page 24

Series Power Meter: Web Manual
Chapter 6: Web Interface Readings
and Parameter Settings
6.1 User Access Login
6.2 Dashboard
6.3 Metering Web Page
6.4 Logs
6.5 About
6.6 Settings
Page 25

Chapter 6: Web Interface Readings and Parameter Settings
Chapter 6:
Web Interface Readings and Parameter Settings
The AcuRev 2100 supports the HTTPS protocol to allow for the use of a web interface. The user
will need to access the AcuRev 2100 interface to congure the module and use its functions.
The web interface allows for remote initial setup of the AcuRev 2100 meter.
The AcuRev 2100 interface allows for dierent user access levels.
To access the web interface the IP address for the AcuRev 2100 either Ethernet 1, Ethernet 2
or a WiFi IP address must be known.
6.1 User Access Login
Enter the correct IP address of the module in the search bar of the internet browser to access
the web interface of the AcuRev 2100.
The user will be redirected to a web page prompting to select the Access Level and enter the
appropriate password for that level.
The User level is ideal for users who need only to take readings and view status from the meter.
The default password for the User level is view.
It is recommended that no more than 5 users are logged in at the same time for this level to
ensure the optimal performance of the web interface.
The Admin level is ideal for users who need access to congurations on the meter or the web
interface and to view readings.
The default password for the Admin level is admin.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
23
Page 26

AcuRev 2100 Series Power Meter: Web Manual
The two dierent access levels are summarized below:
Access Level Default Password Read Parameter/Status Congure Settings
User view Yes No
Admin admin Yes Yes
6.2 Dashboard
In the dashboard, the user will nd the tabs to access dierent pages in the web interface such
as Metering, Logs, and Settings. The dashboard is the rst page the user will see once they
have entered the correct password for the appropriate access level and is the same for both
access levels.
The dashboard displays the basic metering page which allows users to view the real time
readings such as voltage, current, power and power factor. This table is a summary of all user
channels (circuits) connected to the AcuRev 2100 meter.
24
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 27

Chapter 6: Web Interface Readings and Parameter Settings
By clicking on "Select Channel" under the chart, the user will be able to see each input
channel’s reading or three-phase User reading below.
The parameters on this page are updated every 5 sec.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
25
Page 28

AcuRev 2100 Series Power Meter: Web Manual
6.3 Metering Web Page
Click on the Metering menu option to visit the metering data web pages. There are 5 kinds of
metering parameter web pages. They are "Basic Metering", "Demand", "Energy", 'Harmonics'
and ''I/O''. Each web page shows data from the AcuRev 2100 meter.
6.3.1 Basic Metering
The Basic Metering webpage includes the data of real-time parameters for the AcuRev 2100
meter. This includes the Line Voltages, Phase Voltages, Current, Active, Reactive and Apparent
Power, Power Factor, Frequency and Load type.
The parameters on this page are updated every 5 sec.
Users can use the select a channel drop down menu to select a desired channel or circuit.
26
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 29

Chapter 6: Web Interface Readings and Parameter Settings
6.3.2 Demand
The demand page shows the Current Demand, Active Power Demand, Reactive Power
Demand and Apparent Power Demand for each phase.
The demand table also includes the peak demand, the peak demand timestamp, and the
demand prediction. This table provides the overall demand for all circuits connected to the
AcuRev 2100 meter.
User can select and view the demand for specic circuits by using the drop down menu option
on the demand page. The demand table for the specic circuit will be displayed below the
meter demand readings.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
27
Page 30

AcuRev 2100 Series Power Meter: Web Manual
6.3.3 Energy
The Power & Energy webpage shows the energy data for the AcuRev 2100 meter such as the
Active, Reactive and Apparent energy that is consumed. The energy data is displayed as the
total as well as per phase. If users have congured TOU (Time of Use) on the meter, the TOU
energy can be viewed from the energy page as well.
The AcuRev 2100 does not support bi-directional energy and is only able to view the consumed energy.
The parameters on this webpage are updated every 5 sec.
28
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 31

Chapter 6: Web Interface Readings and Parameter Settings
Users can select and view the energy for each circuit by using the drop-down menu below the
main energy table. The individual circuit energy table is presented below the main table.
6.3.4 Harmonics
The Harmonics web page will show the harmonics of the voltage and the current waveform
being measured. It will display the harmonics of each phase in graphical and tabular format.
Select between voltage and current to view their respective harmonics.
In the harmonic page users can view the THD, Voltage/Current unbalance factor, Even/Odd
THD, Crest Factor and THFF readings.
The parameters on this web page are updated every 15 sec.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
29
Page 32

AcuRev 2100 Series Power Meter: Web Manual
6.3.5 I/O
There are 18 digital inputs for AcuRev 2100 series meter. Each digital input channel can be
programmed as either a status indicator or a DI pulse input counter. Users can view the pulse
count or digital status as well as reset the DI count from this page.
30
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 33

Chapter 6: Web Interface Readings and Parameter Settings
There are also two Relay Outputs that can be toggled On/O or congured as an alarm output.
NOTE: The DI and RO settings must be congured on the Acuview software.
6.4 Logs
Click on the 'Logs' tab to visit the metering logs web pages.
There are four kinds of logs that can be viewed, they are "Trend Log", "Data Log, "Alarm Log",
and "Event Log".
Each web page shows data from the AcuRev 2100 meter series meter.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
31
Page 34

AcuRev 2100 Series Power Meter: Web Manual
6.4.1 Trend Log
The Trend Log web page includes the real-time and energy trend diagram. The real-time trend
log diagram can be selected to show the following parameters phase voltage, line voltage,
current, active power, reactive power, apparent power and power factor for each phase as well
as the totals. The energy trend log shows the imported and exported active energy, reactive
energy, total energy, net energy and apparent energy.
The data of the trend log can be previewed and downloaded as a .csv le by clicking the 'Data
Review' and 'Data' icons on the right top side of the diagram. The trend log diagram can also
be saved as an image by clicking the 'Image' icon. See the icons outlined (red box) in the
image below.
32
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 35

Chapter 6: Web Interface Readings and Parameter Settings
6.4.1.1 Real-Time Parameters
The real-time parameters can be trended at dierent time intervals depending on the Time
Frame selected. Listed below are the time intervals for each possible time frame setting:
Time Frame Time Intervals
Last 1 Hour 1 minute
Last 30 days
Last Month
Last 10 minutes
Today
Yesterday
1 hour
1 day
1 hour
1 day
15 seconds
1 minute
15 seconds
1 hour
15 seconds
1 hour
15 minutes
Last 7 days
1 hour
1 day
Custom Range Dependent on range specied
www.accuenergy.com
V: 1.00 Revised: Jan 2021
33
Page 36

AcuRev 2100 Series Power Meter: Web Manual
6.4.1.2 Energy
Similarly, the energy parameters can be trended at dierent time intervals depending on the
Time Frame selected. The table below displays the time intervals:
Time Frame Time Intervals
Last 10 minutes
Last 1 Hour 1 minute
15 seconds
1 minute
Today
Yesterday
15 seconds
1 hour
15 seconds
1 hour
15 minutes
Last 7 days
1 hour
1 day
Last 30 days
This Month
Last Month
Last Year
1 hour
1 day
1 hour
1 day
1 hour
1 day
1 day
1 month
Custom Range Dependent on range specied
34
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 37

6.4.2 Data Log
Chapter 6: Web Interface Readings and Parameter Settings
The data log web page includes all the data les for three dierent loggers and AcuCloud.
Users can select the dierent loggers by clicking the logger tab. After the logger is selected, the
log le for this logger will show on the screen with the update time and le size. To download
the le, click on the download icon to save the le on the computer. The data log will be saved
as a compressed CSV le.
To delete the data logs users can check the box next to the data log file and click on the
'Delete Selected' button at the bottom of the page.
Users will be prompted by a window asking to conrm the data log delete.
NOTE: Deleting the data log is permanent, this cannot be undone once deleted.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
35
Page 38

AcuRev 2100 Series Power Meter: Web Manual
6.4.3 Alarm Log
The Alarm Log web page provides the user with a summary of the alarm events that have
occurred with the meter. It will show the status of up to 16 alarm events indicating the alarm
ID, status, parameter, value that exceeded or went below the threshold and the timestamp of
the alarm event.
Once all 16 alarm events are full, the newest alarm event will then wrap around to alarm 1.
The parameters in the alarm status web page are updated every 10 seconds.
36
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 39

Chapter 6: Web Interface Readings and Parameter Settings
6.4.4 Event Log
The event log web page will display the event log that involved in the parameter and setting
changes.
The event log parameters are updated every 10 sec.
6.5 About
The About tab located at the top right corner of the web interface allows users to view the
Device Information page. This page provides users with information about the AcuRev 2100
series meter. The Device Information contains the model of the AcuRev 2100 meter, serial
number, firmware version and the meter addresses. It also contains the serial number,
rmware version, hardware version and the MAC addresses of the AcuRev 2100 web module.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
37
Page 40

AcuRev 2100 Series Power Meter: Web Manual
6.6 Settings
6.6.1 Meter
The basic metering configurations needed to set up the meter can be applied from the
web interface by clicking on the Settings and selecting the Meter. The meter settings page
includes the following settings:
• Device Description: A description for the meter can be provided in this eld which will
display on the Dashboard page.
• Device Transformer: Users can select the secondary output of the CTs being used on the
meter. Users can select RCT or 333mV for the mV model and 80mA/100mA/200mA for
the mA model.
NOTE: Users cannot mix and match CTs, for example if users have the mV current input model they
cannot mix and match RCT and 333mV CTs.
• Wiring of Three Phase User: Select the type of wiring that the meter will be monitoring
from the modes available. Users can select 1LN, 2LN, 3LN.
• CT Ratio: Set the rating of the CT that is connected to the meter to measure the current
for each channel. For example if a 200A:333mV CT is being used, “200” must be entered
in the CT ratio setting.
38
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 41

Series Power Meter: Web Manual
Chapter 8: System Settings
Chapter 7: Communications
7.1 Network
7.2 Email
7.3 Time/Date
7.4 Data Log
7.5 Post Channel
7.6 AcuCloud
7.7 BACnet/IP
7.8 SNMP
7.9 MQTT
7.10 Remote Access
Page 42

AcuRev 2100 Series Power Meter: Web Manual
Chapter 7: Communications
The communication setting web page will allow the user to configure settings related to the
Ethernet networks and the Wireless network. The functions and protocols that the AcuRev
2100 supports can be congured by selecting the corresponding tab such as Emails, Time/Date,
Datalog, AcuCloud Post for communicating with the AcuCloud software, BACnet-IP, SNMP.
7.1 Network
The rst page the user will see after selecting the Communications option under the Settings
tab is the Network page. The network settings allow users to congure all network-related
settings including both Ethernet 1 and Ethernet 2 as well as WiFi.
7.1.1 Network Settings
The settings for the Ethernet 1 and Ethernet 2 are as follows:
• Ethernet 1 DHCP: Select 'Manual' to manually configure the IP address to access the
meter. If set to 'Manual', you'll also need to set the Subnet Mask and Gateway. By default,
the IP address for ETH1 will be 192.168.1.254. By default Ethernet port 1 is set to Manual.
Select “Auto” to have the meter assigned an IP address automatically. With this selection,
the Subnet Mask, and Gateway will also be automatically assigned.
NOTE: After changing DHCP to Auto, check the display of the meter (N02 NET Settings) to obtain the
new IP address that has been assigned. The new IP address will be displayed only after a module
reboot is performed and completed.
40
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 43

Chapter 7: Communications
• IP Address: If the DHCP is congured to “Manual”, the IP address can be congured from
this page. Default is 192.168.1.254
• Subnet Mask: If the DHCP is congured to “Manual”, the Subnet Mask can be congured
from this page. Default is 255.255.255.0
• Gateway: If the DHCP is congured to Manual, the Gateway can be congured from this
web page. Default is 192.168.1.1
The status of the Ethernet 1 port will display if it is connected or disconnected.
• Ethernet 2 DHCP: By default, the Ethernet 2 port is congured to have its DHCP set to
“Auto”. If congured to “Manual” the default Manual IP address is 192.168.1.253. Users
can congure the IP address to any IP once the DHCP is congured for “Manual”, users
will also need to set the Subnet Mask and Gateway if using this method.
NOTE: The IP address of the Ethernet 2 can be found on page N12 of the NET Settings. The AcuRev 2100
meter protocol setting must be congured to AcuRev 2100 to view this from the meters NET settings.
• IP Address: By default, the IP address is congured by DHCP, this eld will be grayed out.
If the DHCP is congured to Manual, the IP address can be congured from this page.
• Subnet Mask: If the DHCP is congured to Manual, the Subnet Mask can be congured
from this page.
• Gateway: If the DHCP is congured to Manual, the Gateway can be congured from this
web page.
The status of the Ethernet 2 port will display if it is connected or disconnected.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
41
Page 44

AcuRev 2100 Series Power Meter: Web Manual
The AcuRev 2100 also supports WIFI communication where the WIFI setttings can also be
congured on the Network settings page. The following WIFI settings are congurable from
the interface:
• WiFi Enabled: Select the Enable or Disable communication through WiFi.
• WiFi Mode: The WiFi can be configured to work in two modes just like any other WIFI
device. It can be congured as either Access Point (AP) or Station mode.
• Access Point: Default conguration for AcuRev 2100. The AcuRev 2100 will act as a wireless
access point and will allow other wireless devices to connect and access the AcuRev 2100.
In Access Point mode, users can congure the SSID, Network Key and IP of the AcuRev
2100 as well as the DHCP DNS servers.
• Station: The AcuRev 2100 will behave like a wireless client and bridge to another
wireless network that is available.
In Station mode, users can select the Wireless network to connect to under the
"Connect to SSID" setting. Click on "Select from Available Networks" and enter the
Network Key for the wireless network that the AcuRev 2100 will bridge to.
If users are connecting to an open Wireless network that is not password protected, the
password eld can be left blank.
AcuRev 2100 also supports Enterprise WiFi, where users can connect using an enterprise-level
WiFi network which is common in many colleges/universities, hospitals, etc. When attempting
to connect to an enterprise-level WiFi network the interface will show options to connect to
the network with a username and password.
42
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 45

Chapter 7: Communications
In station mode the DHCP can be congured as either manual or auto.
• If manual, users can congure the IP, Subnet Mask and Gateway and DNS Servers.
• If auto, users can check the meter's display to get the IP address and all other network
configurations assigned by the wireless network. The user can also configure the DNS
servers if the DHCP is set to Auto.
NOTE: The WiFi IP address for the AcuRev 2100 will be in parameter N11 of the NET settings.
• DNS Server 1: Enter the address of DNS server 1 in this eld. Default DNS1 is 8.8.8.8
• DNS Server 2: Enter the address of DNS server 2 in this eld. Default DNS2 is 8.8.4.4
• HTTPS Port: Enter the HTTPS port number of the meter. By default, this setting is
congured to 443. The range can be from 6000 to 9999.
• HTTP Enable: Enable HTTP so the AcuRev 2100 can be accessed through the HTTP
protocol, by default the HTTP port is 80 but it can be congured from 6000-9999.
• Modbus TCP Port: Enter the Modbus port number of the meter. By default, this setting is
congured to 502. The range can be from 2000 to 5999.
• Proxy Server Enable: Select enable to allow for forwarding of data log files to pass
through the Proxy server rst and then the data post server. IE. AcuCloud.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
43
Page 46

AcuRev 2100 Series Power Meter: Web Manual
After making any changes on the network settings page, click 'Save'. Users will be prompted
to reboot the AcuRev 2100 immediately or later. If later is chosen the AcuRev 2100 will need to
be rebooted from the 'Management' page in order for the settings to take eect.
7.2 Email
The AcuRev 2100 supports the SMTP protocol where users can congure the meter to send
emails based on a specific time interval or whenever there is an alarm, System Event or a
combination of both. The Email conguration page can be accessed by clicking on the Email
tab under Communications.
There are three modes available for sending emails that the user can enable.
The rst mode is Real Time Email Reporting where emails are sent immediately when there
is a new alarm, or System event.
44
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 47

Chapter 7: Communications
The second mode is Periodic Email Reporting where users can receive emails at a certain
period of time based on the time interval congured. The email will include the data that is
selected to be sent.
The third mode is when both of the above are enabled.
Users must know their SMTP server provider and details regarding their SMTP server, which
can be provided by users' IT personnel.
The following settings must be congured for email reporting:
• SMTP Enabled: Select 'Enable' to enable and to further congure the settings related to
the SMTP function.
• Start Time to Send Email: Select the date and time for when the emails should begin to send.
• Click on the icon to congure the time and date.
• Click on the icon in the bottom right to clear the time and date.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
45
Page 48

AcuRev 2100 Series Power Meter: Web Manual
• SMTP Server: Enter the URL of a valid SMTP server. I.E. mail.accuenergy.com or smtp.
gmail.com
• SMTP Port: Enter the port number associated with the SMTP server.
• SMTP From: Enter a name or phrase which will appear to let you know who the mail is
from. I.E. 'Technical Support'
• SMTP Subject: Enter a subject line for the emails
• Authentication: Users can have email authentication on or o. If authentication is on
users will need to provide the SMTP username and password.
• SMTP Username: Enter the SMTP user name for the SMTP server set above.
• SMTP Password: Enter the SMTP user password for the username set above.
• TLS/SSL: Users have the option to send emails using TLS/SSL protocols
• SMTP To Address 1/2/3: Enter up to three recipients that you wish to have the email sent
to in “SMTP To Address 1/2/3”.
• Test Address 1/2/3: Test the if the email can be sent to “SMTP To Address 1/2/3”.
NOTE: If the test address function fails, users can view the email post-failure by clicking on the
'Details' option from the test post screen.
46
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 49

Chapter 7: Communications
After conguring the above settings, the next step is to select the content for the emails.
The content of the emails can either be time-based triggered or event-based triggered.
For receiving emails on a time based under Enable Periodic Email Reporting:
Enter a time between 5-1440 mins in the Set time interval
• Check o the box beside the parameters for the content the user should receive.
• Real Time: Report on Real-time voltage, current, power and etc.
• Energy Data: Report on energy parameters.
• Alarm: Report of the alarm log.
• Demand: Report demand data.
• System Event: Report of the SOE log.
• DI: Report DI status/counters.
The user will receive an email report in a CSV file attachment. The report will include the
readings and/or the real time triggered event.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
47
Page 50

AcuRev 2100 Series Power Meter: Web Manual
7.3 Time/Date
The device clock of the AcuRev 2100 meter series meter can be set through the web interface
of the AcuRev 2100. The AcuRev 2100 supports NTP (Network Time Protocol) so that the
module can update the meter's device clock by synchronizing with a time server.
The module can sync with up to three time servers. If a time server is down, the module will
synchronize with the second or the third time server if they are congured.
The settings for the time and date can be found by clicking on Settings and selecting the
Communications tab. Users can select Date & Time to congure the time settings.
The following must be congured to set the time/date and NTP settings:
• NTP Enabled: Select enable to further congure the settings related to the NTP (Network
Time Protocol) function
• Device Clock: Congure the date and time on the meter
• Click on the icon to congure the date and time.
• Click on the icon in the bottom right to clear the time and date.
• Sync Time: Click on Force Update to have the AcuRev 2100 sync its time with the NTP
server
• NTP Server 1/2/3: Enter up to 3 NTP servers in the "NTP Server 1", "NTP Server 2" and
"NTP Server 3"
0.us.pool.ntp.org
1.us.pool.ntp.org
2.us.pool.ntp.org
3.us.pool.ntp.org
48
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 51

Chapter 7: Communications
For more NTP servers based on region, visit the following site: http://www.pool.ntp.org/en/
• Time Zone: Select the time zone the meter is in or the time zone in which you would like
the meter's time to be synchronized to from the drop-down list. Users can also select the
time zone by clicking on the region on the map.
Click “Save” after conguring the time settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen the AcuRev 2100 must be rebooted from the
“Management” page in order for the settings to take eect.
7.4 Data Log
The AcuRev 2100 supports logging data onto its onboard memory, where the module has 8GB
of memory.
The module supports three loggers for dierent parameters and requirements.
The data can be downloaded as a .csv le from the “data log” page in the logs section or by
using an HTTP/FTP client.
• Logger Enable: To use the data log function to log the data onto the module, select
'Enable' to view and congure the settings that are applicable.
• Post Channel: Select the channel to push the data log to an external HTTP/FTP server.
Only an enabled post channel can be selected here. A post channel can be enabled in the
'Post Channel' tab on the settings page.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
49
Page 52

AcuRev 2100 Series Power Meter: Web Manual
• Log Param Type: Users can select the type of parameters they wish to log into logger.
Use the '>' button to add selected parameters into the data log and use the '<' button to remove
selected parameters from the data log. Users can also use the 'All' or 'Clear' buttons to add all
or clear all parameters to and from the data log. The supported parameter types include real-
time readings, energy readings, demand readings, power quality readings and I/O readings.
• Timestamp Format: Select the format of the timestamp for the data that is logged. The
format for the timestamp can be based on the Local Time, UTC Seconds or based on
ISO8601 Format.
• Log File Name Format: Select the format of the log le name for the data that is logged.
The format for the log le name can be based on the UTC timestamp or based on Time
Interval Format.
• Log Interval: Select how frequently the meter will log data to the file that will be
uploaded to the server from the drop-down list. The logging interval can be from 1 second
to 1 month. The minimum time interval option is according to the selected parameter.
• The Real-time & IO's min Log Interval is 15 seconds
• The Energy's min Log Interval is 1 minute
• The Demand & Power Quality's min Log Interval is 1 min
50
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 53

Chapter 7: Communications
NOTE: If the selected parameters are Real-time and I/O, the min log interval is 15 seconds. If the
selected parameters are Real-time and Energy, the min log interval is 1 minute.
• Post File Length: Select how frequently the log le will be uploaded to the server from
the drop-down list The log le length can be from 1 minute to 1 month.
• Log File Name Prex: Provide a name for the log le posted to the post channel which
will be appended to the beginning of the log le. By default "logger1" will be appended to
the beginning of the log le.
• Local Log File Length: Select the length of the local log le as 1 hour, 1 day, 7 days or 1
month of data from the drop-down list.
• Local Log File Name Prex: Provide a name for the local log le which will be appended
to the beginning of the log le. By default "logger1" will be appended to the beginning of
the log le.
NOTE: The Post File Length and Local Log File Length must be less than or equal to the log interval selected.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
51
Page 54

AcuRev 2100 Series Power Meter: Web Manual
• SFTP Enable: To download the logged data from the module using an FTP client, select
Enable. The log le will then be available to be downloaded using an FTP client using the
following credentials:
Host: sftp://IPaddressofthemeter
Username: sftpuser
SFTP Password: accuenergy
Port: 22
By default the password for retrieving the backup log files is accuenergy. The user can
congure any password or can reset to the default of accuenergy by clicking on the "Reset
SFTP Password".
NOTE: After enabling the SFTP function the user must reboot the communication module in order
to access the data logs with the default password of 'accuenergy'.
Click 'Save' after changing any settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen, the AcuRev 2100 must be rebooted from the
'Management' page in order for the changes to take eect.
7.5 Post Channel
The AcuRev 2100 supports the HTTP and FTP Post functions to send data from the meter to
an HTTP/FTP server. The AcuRev 2100 can post .csv les to three dierent HTTP or FTP servers
using HTTP Post or FTP Post.
In the case when there is no connection to the server, the AcuRev 2100 will store the posts and
send it out after the connection is restored. A maximum of 3000 les will be buered on the
module. The Clear Post Channel Logs button will allow users to clear the buered les on the
meter.
The AcuRev 2100 can post data to a server at intervals of time ranging from 1 minute to 1 month.
The settings for conguring the post channels to post the data can be found by clicking on
Settings and then selecting the Communications tab. Click Post Channels to congure any
of the three post channels.
52
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 55

Chapter 7: Communications
• Post Channel 1/2/3 Enable: Enable the Post Channel 1 in order to congure the settings
needed to post data via the HTTP(S)/FTP post functions
• Post Method: Select the method for posting the les, the user can choose HTTP/HTTPS
or FTP
• Post Name Fixed: This conguration needs to be enabled in order for the user to control
the name of the le that will be posted. Otherwise, the le name will be based on the Log
File Name Format conguration from the Data Log settings
• Post File Name: Users can enter a name for the le that will be posted as if 'Post Name
Fixed' is enabled
If the HTTP/HTTPs post method is selected:
• HTTP/HTTPS URL: Enter the URL for the HTTP/HTTPS server. The URL needs to begin with
the prex http:// or https://
• HTTP/HTTPS Port: Enter the port number the server will be listening on
• HTTP/HTTPS Meter ID: Enter a name or description for the meter to be identied on
the server
If the FTP post method is selected:
• FTP URL: Enter the URL for the FTP server. The URL needs to begin with the prex ftp://
• FTP Port: Enter the port number the server will be listening on
• FTP Username: Enter the username required to log into the FTP server
• FTP Password: Enter the password required to log into the FTP server
NOTE: The 'TEST Post Channel' button should only be utilized after clicking the 'Save' button
otherwise a fail response will be observed. If a fail response occurs after clicking 'Save' conrm the
network settings or credentials for the server.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
53
Page 56

AcuRev 2100 Series Power Meter: Web Manual
Click 'Save' after changing any settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen the AcuRev 2100 must be rebooted from the
'Management' page in order for the settings to take eect.
7.6 AcuCloud
The AcuRev 2100 can directly interface with the Accuenergy Cloud software AcuCloud, where
the meter can post data to the cloud every ve minutes.
AcuCloud will require the serial number of the AcuRev 2100 which will then provide a token
that will be used to congure the AcuRev 2100 so it can send its data to AcuCloud.
The settings for the AcuCloud post function can be found by clicking on the Settings tab and
selecting Communications. Select AcuCloud to access the settings to congure the AcuRev
2100 to send data to the cloud.
• AcuCloud Enable: Select 'Enable' to enable the function and to further configure the
settings related to AcuCloud.
• AcuCloud Token: Copy and paste the token provided by the AcuCloud software into this eld.
NOTE: The "TEST AcuCloud" button should only be utilized after clicking the 'Save' button otherwise
a fail response will be observed. If a fail response occurs after clicking 'Save', please double-check
the serial number entered in AcuCloud, the token pasted in the web page as well viewing the test
post details by clicking on the 'Details' option.
54
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 57

Chapter 7: Communications
Users can use the 'Link to AcuCloud' to access the cloud software and congure the required
settings on that platform. Users must have sucient access to add devices on their account
in order to correctly congure the meter on the software.
NOTE: For inquiries on creating your AcuCloud account please contact Accuenergy Technical
Support.
Click 'Save' after changing any settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen the AcuRev 2100 must be rebooted from the
'Management' page for the settings to take eect.
The AcuRev 2100 will post the data continuously every 5 minutes after the reboot.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
55
Page 58

AcuRev 2100 Series Power Meter: Web Manual
7.7 BACnet/IP
The AcuRev 2100 supports the BACnet/IP protocol. The settings for the BACnet/IP protocol
can be found on the web by clicking on the Settings tab and selecting Communications. Once
on the communications page select BACnet/IP to access the settings to congure the AcuRev
2100 to communicate with a BACnet client.
• BacNet Enabled: Select Enable to enable the BACnet protocol.
• BACnet Port: Enter the BACnet or UDP port number. The default port is 47808.
• Device Instance: Enter the instance number for the device in the BACnet system. It must
be unique within the system.
• Device Name: Enter a name for the device to distinguish it from other devices within the
network.
Under the "Enable Foreign Device Function", select 'Enable' to communicate with a BACnet
device from another subnet.
• Enter the IP of the BACnet Broadcast Management Device (BBMD) under the 'BBMD IP'
eld for the device which will receive broadcast messages on one subnet and forward
them to another subnet.
• Enter BACnet Port of the BBMD in "BBMD Port"
• Enter a value between 5-1440 min in the "Time To Live" for how often the foreign device
will register in the BBMD's foreign device table.
56
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 59

Chapter 7: Communications
Click 'Save' after changing any settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen the AcuRev 2100 must be rebooted from the
'Management' page in order for the settings to take eect.
7.8 SNMP
The AcuRev 2100 supports the Simple Network Management Protocol (SNMP) for reporting
the metering data to the management station. The AcuRev 2100 uses a public community
string for read-only access. By default, the module will communicate using SNMP port 161.
The settings for the SNMP protocol can be found by clicking on the Settings tab and selecting
Communications. From the communications page, select the SNMP tab to access the settings
to congure the AcuRev 2100 for communication with an SNMP management station.
• SNMP Enable: Select 'Enable' to enable the function and to further congure the settings
related to the SNMP protocol.
• SNMP Port: By default, the SNMP Port is congured to 161. The SNMP Port can be any
value from ranging from 16100 to 16199.
• Read Only Community: By default the community string is Public, this conguration is
similar to a password that allows only authorized users to access the meters data.
Click 'Save' after changing any settings. Users will be prompted to reboot the AcuRev
2100 immediately or later. If later is chosen the AcuRev 2100 must be rebooted from the
'Management' page in order for the settings to take eect.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
57
Page 60

AcuRev 2100 Series Power Meter: Web Manual
7.9 MQTT
AcuRev 2100 supports the MQTT protocol where the gateway can publish device data to a
subscriber using an MQTT broker. The MQTT broker is a central server where all MQTT clients
would connect to. The broker/server manages all message topics and updates new messages
to all clients that are subscribed to a particular topic. All related MQTT settings can be
congured in the MQTT page under the Communication tab.
7.9.1 MQTT General Settings
Under the General tab in the MQTT page, users can enable the MQTT protocol and congure
the broker settings.
• Enable MQTT: Select Enable to enable MQTT protocol
• Broker Address: Enter the broker address of the MQTT server
• Broker Port: Enter the port number for the MQTT Broker
• Client ID: Enter the Client ID for the AcuRev 2100; must be a unique ID number
• Keep Alive: The client communicates a time interval in seconds to the broker, “Keep-
Alive” is the maximum length of time in seconds that the broker and the client cannot
communicate with each other.
• Facility ID: Users can specify the facility ID
Once all settings are configured click Save. The connection to the broker can be tested by
using the Test MQTT button.
58
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 61

Chapter 7: Communications
7.9.2 MQTT Authentication
The User Credential tab allows users to configure a “User Name” and “Password”
authentication if the broker is able to support it.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
59
Page 62

AcuRev 2100 Series Power Meter: Web Manual
7.9.3 MQTT Encryption
The SSL/TLS tab allows users to use the MQTT protocol with encryption.
On this page, users will be able to upload the required certicate and key les.
7.9.4 Last Will & Testament
The AcuRev 2100 supports Last Will and Testament messages via the MQTT protocol. These
settings can be congured under the Last Will & Testament tab.
The last will and testament message are used to notify other clients regarding other
disconnected clients. The message is an MQTT message that contains a topic, a QoS level and
a payload.
• Topic: Refers to the path used to access the MQTT message.
• QoS: Stands for Quality of Service and refers to the reliability of the message delivery
between the publisher and subscriber. There are three types of quality of service:
• QoS 0 - is the lowest level, and is dened as “at most once” delivery. This level has the
fastest message delivery but the success rate of delivery is not reliable.
• QoS 1 - is dened as “at least once” delivery. These types of messages are reliable and
are guaranteed, however, the messaged may be sent as duplicates several times.
• QoS 2 - Is the highest level, and is dened as “exactly once” delivery. These messages
are more reliable and are guaranteed to be sent once without any duplicates. This
type of messaging sends the most reliable message however it has a slower message
60
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 63

Chapter 7: Communications
delivery. Each client can optionally specify its own LWT message when it connects to a
broker. The broker stores this message so that if the client disconnects ungracefully,
the broker will send the disconnected client’s LWT message to all the other clients that
are subscribed to that last will message topic.
7.9.5 Topic and Parameter Selection
Under the Topic and Parameter Selection tab users can congure the sending interval and
devices data they want to publish to the broker.
• Topic: Users can enter the Topic, which is usually a base topic followed by the serial
number of the device.
• QoS: Users can congure the quality of service level, where Qos 0 is the lowest level and
Qos 2 is the highest level.
• Retained: Users have the option to retain messages or not. If a client retains messages
that were published to the topic, a second client that is subscribed to the same topic will
be able to see the retained message.
Users will need to specify the data they want to publish under the parameter selection box.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
61
Page 64

AcuRev 2100 Series Power Meter: Web Manual
7.10 Remote Access
The AcuRev 2100 supports a remote access function that allows users to access the meters
web interface remotely from anywhere using a special url. Users will have full functionality
and access to all meter readings and settings with this function.
• Remote Access Enable: Select 'Enable' to enable the function and allow for Remote
Access.
• Current Status: Will provide the user with a status of the Remote Access on whether it is
“Registered” or “Unregistered”.
62
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 65

Chapter 7: Communications
Users can click on the 'Manual Register' button to register the remote access. The following
page will be displayed.
NOTE: The module must be rebooted in order for the remote access connection to work properly.
• Registration Status: Displays the status as 'Registered' or 'Unregistered'
• Remote Access Information: Lets users know if the remote access status is online or
oine.
• Remote Access URL: The URL used to access the meters web server remotely. This URL
can be copied and shared with all users that require remote access.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
63
Page 66

Series Power Meter: Web Manual
Chapter 8: Management
8.1 Parameter Reset
8.2 Reboot Meter & Communications Module
8.3 Change Password
8.4 SSH
8.5 Debug Diagnostic
8.6 Diagnostic File
Page 67

Chapter 8: Management
Chapter 8: Management
8.1 Parameter Reset
The Management web page allows the user to clear and reset certain parameters in the meter.
The following parameters can be reset from the Management page:
• Demand
• Energy
• Alarm Record
• Device Run Time
• API Token
8.2 Reboot Meter & Communications Module
Users can also reboot the web module and meter which is required after any communication
or meter setting is changed if a module reboot is not performed the settings will not be saved
to the meter and will go back to its default settings. This not only resets the communication
module, it also performs a soft reboot on the AcuRev 2100 meter.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
65
Page 68

AcuRev 2100 Series Power Meter: Web Manual
8.3 Change Password
The access level passwords can be changed from the Management page as well, all new
passwords must be 6 characters or more.
8.4 SSH
The AcuRev 2100 supports the SSH which can be enabled to allow users to remotely log into
the meter using the SSH protocol. When enabled the status will show 'On', when disabled the
status will show 'O'.
8.5 Debug Diagnostic
The debug diagnostic allows the user to enable or disable the debug logs. The current status
will say 'All o' if disabled, 'All On' if enabled.
66
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 69

Chapter 8: Management
Users can click on the advanced link, to turn on or o specic debug logs. If certain debug logs
are enabled the current status will show 'Partial On'.
NOTE: The system performance may be aected by enabling the debug logs.
8.6 Diagnostic File
The is a diagnostic file on the AcuRev 2100 that users can download which can be used to
analyze the modules diagnostics.
NOTE: Please send the diagnostic le to Accuenergy Technical Support (support@accuenergy.com)
for analysis.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
67
Page 70

Series Power Meter: Web Manual
Chapter 9: Network Diagnostic
9.1 Network Status
9.2 Host Lookup
9.3 Connection Test
Page 71

Chapter 9: Network Diagnostic
Chapter 9: Network Diagnostic
9.1 Network Status
The Network Diagnostic page can be used to monitor the network status of the module.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
69
Page 72

AcuRev 2100 Series Power Meter: Web Manual
9.2 Host Lookup
In the Host Lookup tab, users can utilize the 'ping' function to test the reach-ability to other
networks. Users can also use the ping6 function to ping an IPv6 address.
9.3 Connection Test
Users can also use the Connection Test function to test the local network that the module
connected to. The test result will show SUCCESS and PASS if there are no issues found.
70
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 73

Series Power Meter: Web Manual
Chapter 9: Protocols
Chapter 10: Firmware
10.1 Module Firmware Update
Page 74

AcuRev 2100 Series Power Meter: Web Manual
Chapter 10: Firmware
10.1 Module Firmware Update
The Module Firmware web page is used for updating the firmware version on the AcuRev
2100. The user can check if the module they are using is up to date and update the module
if needed using the remoter rmware update. Users can also manually update the rmware
by uploading the rmware le. The current version of the rmware will be displayed on the
Module rmware update page and can also be viewed on the 'Device Information' page of the
web interface.
There is an Auto Firmware Update feature available also, this allows users to update the
module automatically without manually going into the webserver and performing the update.
NOTE: Users can also contact Accuenergy Technical Support for the latest rmware.
72
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 75

Chapter 10: Firmware
10.1.1 Manual Update
Select and upload the AcuRev 2100 rmware le, it is a .a2up le extension.
Once the upload was successfully uploaded you will see the following page conrming that the
le was uploaded.
Click 'Process' to begin the update.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
73
Page 76

AcuRev 2100 Series Power Meter: Web Manual
The meter will reboot itself after the update.
Login to the web interface of AcuRev 2100 after the reboot is complete, and go to the 'About'
page to check if the module rmware version is updated.
10.1.2 Remote Update
Users can also use the remote firmware server to update the module firmware. Click on
'Check' to verify if there is a rmware update available.
74
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 77

Chapter 10: Firmware
If there is an update available users can proceed to download the rmware.
Once the download is complete the updating process will begin.
www.accuenergy.com
V: 1.00 Revised: Jan 2021
75
Page 78

AcuRev 2100 Series Power Meter: Web Manual
When the rmware update is complete, the module will reboot. The rebooting process will
take 1-2 minutes to complete.
After the module reboots, users will be able to log back into the web interface. When logged
in click on the 'About' tab located on the top right corner of the web page to view the 'Device
Information' page. From the Device Information page, users can ensure that the meter was
updated correctly to the right rmware version.
76
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 79

Series Power Meter: Web Manual
Chapter 9: Protocols
Chapter 11: Cong Management
11.1 Backup Conguration
11.2 Export/Apply Conguration
11.3 Import Conguration
Page 80

AcuRev 2100 Series Power Meter: Web Manual
Chapter 11: Cong Management
The AcuRev 2100 has a configuration management page that allows users to save all web
settings with the exception of certain settings into a conguration le. This is useful if users
have more than one meter that needs to be programmed with the same settings, and
eliminates any error when trying to congure another AcuRev 2100.
The following settings are saved in the conguration le:
• All Meter settings (Wiring, CT ratio)
• Network settings (Only DNS1, DNS2, Modbus TCP Port, HTTP Proxy)
• All Email settings
• All Time/Date settings
• All Data Log settings
• All Post Channel settings
• All BACnet settings
• All SNMP settings
• Management settings (the View and Admin Access Level passwords, SSH, and Debug
Conguration)
• MQTT settings (General, User Credentials, Last Will & Testament, Topic & Parameter Selection)
The settings that are not included or aected by the Cong Management le is:
• Most Network settings (DHCP, IP, Submask, Gateway, HTTP Port for both Ethernet 1 and 2.
All WiFi settings, HTTP enable, and HTTPS port is not changed)
• AcuCloud
• Remote Access
• MQTT client ID and SSL certicates
78
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 81

Chapter 11: Config Management
The Cong Management page can be accessed by clicking on the Settings tab and selecting
Cong Management.
11.1 Backup Conguration
Users can create a backup of the current congurations on the AcuRev 2100 interface.
• Backup Current Configuration Description: Enter in a description for the backup
conguration le.
Once the description is entered in click on the Backup button.
The backup is displayed in the List of Local Configurations. The file has a file format that
includes the module serial number, module rmware version, and time stamp that the le was
created.
NOTE: Users cannot have more than 10 congurations in the List of Local Congurations.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
79
Page 82

AcuRev 2100 Series Power Meter: Web Manual
Users can click on Detail to view the description of the conguration le. The details include
the Model name, serial number, time created. rmware version and the description entered
when the backup was created. Users can remove any of the conguration les from the list at
any time by selecting Delete.
11.2 Export/Apply Conguration
Users can export the configuration file and use it on other AcuRev 2100 units. The file is
downloaded as a .ehm le.
80
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 83

Chapter 11: Config Management
To implement the conguration le click on the green check button to Apply. A prompt warning
the user that the existing .conf.ehm le will be overwritten is shown. Click Yes to continue.
A module reboot is required for the conguration to take eect. if users decided to reboot
later the reboot must be performed from the Management page in order for the settings to
take eect on the device.
11.3 Import Conguration
Import Configuration: Users can import a configuration file (.conf.ehm file format) to the
AcuRev 2100.
V: 1.00 Revised: Jan 2021
www.accuenergy.com
81
Page 84

AcuRev 2100 Series Power Meter: Web Manual
Click on Import to upload the conguration le to the AcuRev 2100.
The newly imported le will now appear in the List of Local Congurations
NOTE: Users cannot import a file that already exists on the local configurations, when the list
already contains 10 cong les, and cannot import a cong le that has been exported from an
AcuRev 2100 with a higher rmware version.
82
V: 1.00 Revised: Jan 2021
www.accuenergy.com
Page 85

MAKE ENERGY USAGE SMARTER
ACCUENERGY (CANADA) INC.
2 Lansing Square, Suite 700
Toronto, ON M2J 4P8, Canada
ACCUENERGY SOUTH AFRICA (PTY) LTD
Castle Walk Corporate Park,
Block B, Cnr. Nossob & Swakop Street
Erasmuskloof, Pretoria, 0181
South Africa
TF: 1-877-721-8908
INT: +1-416-497-4100
FAX: +1-416-497-4130
E: marketing@accuenergy.com
TF: +27 (0) 87 802 6136
Revision Date: Jan 2021