The information contained in this document is believed to be accurate at the time
of publication, however, Accuenergy assumes no responsibility for any errors which may
appear here and reserves the right to make changes without notice. Please ask the local
representative for latest product specications before ordering.
Please read this manual carefully before installation, operation and maintenance of the
AcuLink810 series meter. The following symbols in this manual are used to provide warning of
danger or risk during the installation and operation of the meters.
Electric Shock Symbol: Carries information about procedures which must be
followed to reduce the risk of electric shock and danger to personal health.
Safety Alert Symbol: Carries information about circumstances which if not
considered may result in injury or death.
Prior to maintenance and repair, the equipment must be de-energized and grounded. All
maintenance work must be performed by qualied, competent accredited professionals who
have received formal training and have experience with high voltage and current devices.
Accuenergy shall not be responsible or liable for any damages or injuries caused by improper
meter installation and/or operation.
The AcuLink 810 is an intelligent data acquisition server and gateway that allows users to
collect data from all Accuenergy meters, sensors and other third party devices.
2. Functional Description
2.1 Hardware Specications
2.2 Power
The AcuLink collects and logs time-stamped data from connected downstream devices (serial or Ethernet), and is able to store this data locally in non volatile memory. When using
Ethernet it is possible to push or pull data using HTTP or FTP protocols as well as pushing
data to dierent web-based energy management systems or any front end software platform. There is no software required for the AcuLink as all conguration is done from the
gateways web interface.
• Disk Capacity: 8 GB RAM
• Interval Recording: 1-1440 minutes, user selectable
The AcuLink 810 gateway supports RS485 serial communication. Users can setup an RS485
connection to the AcuLink with any Accuenergy or third party device. If connecting multiple
devices or 'daisy chaining' the devices together, ensure that a unique device address (Mod-
bus Slave ID) is congured for each RS485 device. The AcuLink 810 can support up to 32
external RS485 devices.
NOTE: A termination resistor at the end of the RS485 network is optional when daisy chaining multiple devices. If using resistor a termination value of 150 ohms can be used.
The AcuLink 810 has 8 Digital Input channels. Each Digital Input can be used as an input
pulse counter.
Each channel has two terminals, a DI terminal and a DI COM terminal. In pulse output circuits a closed loop is required for the pulse to be generated. In the Image below you will see
a closed circuit on Digital Inputs 1 and 6. The positive output is connected to the DI channel
input and negative output is connected to the DI Common input.
The AcuLink 810 has a web interface that users can access to congure settings and view
device data. The AcuLink 810 gateway has two Ethernet ports and also supports communication via WIFI.
The default IP addresses and default modes are:
Ethernet 1:
Ethernet 2:
WIFI:
Access Point Mode
The following will outline the methods on how to initially access the meters web interface.
192.168.8.101
DHCP
5.1 Accessing the AcuLink 810 Web Interface
5.1.1 Method 1 - Direct Connection via Ethernet
For the direct connection method, there must be an Ethernet connection from the Ethernet 1 port on the AcuLink and a computer.
Next in order to access the web interface, the computers IP address must be congured within the same subnet as the AcuLink Ethernet 1 IP address. The Ethernet 1
port has a default IP address of 192.168.8.101. The following outlines how to change
the computers IP:
• Start by accessing the control panel of the computer and select 'Network and
Internet'.
• The following page will open, select 'Internet Protocol Version 4 (TCP/IPv4) and click on
'Properties'.
• Select 'Use the following IP address:' and change the IP address of the computer. The
AcuLink 810 Ethernet 1 address is 192.168.8.101, the computers IP will need to be within the
same subnet. The IP of the computer can be 192.168.8.xxx, where xxx can be any number
ranging from 1-254. For the example an IP address of 192.168.8.10 is used.
NOTE: The computers IP address and the AcuLink 810 Ethernet 1 IP address cannot be the
5.1.2 Method 2 - Using WIFI to connect to the Meters Web Interface
The web interface of the AcuLink can be accessed by WIFI. Ensure that the WIFI antenna is installed on the unit.
DATA ACQUSITION SERVER
By default the AcuLink 810 has its WIFI mode set as AP (Access Point) mode, where the
AcuLink 810 acts as a wireless access point allowing other wireless devices to connect
and access the gateway.
To connect to the AcuLink via AP mode, search for the SSID in the list of wireless networks.
The SSID will be by default AcuLink810-WIFI-S8Pxxxxxxxx, where the 'S8Pxxxxxxxx' is a
unique serial number of the AcuLink gateway. The serial number of the AcuLink can be
found on the side of the unit. The password for the network is
When you log in the to the AcuLink 810 web interface, users are directed to the 'Dashboard'.
The dashboard provides the user with a summary of all the Oline Devices as well as the
Devices in Alarm.
The navigation panel on the left side of the interface allows users to access dierent settings
within the gateway.
The footer on the bottom of the web page includes the server time and date. The footer
also includes the time that the gateway was initially powered on.
6.1 Modbus Template
Modbus Templates are used in the AcuLink 810 to correctly read the metering data from
Accuenergy and third party Modbus devices. Before a device can be added to the gateway a
Modbus template for the device must rst be uploaded and installed onto the unit.
On the left navigation panel under the 'CONFIGURATION' menu, select 'Modbus Template'.
In the Modbus templates page users can view the templates and the version number currently installed on to the AcuLink under the 'Installed' tab.
To upload a new device template click on the 'New/Update' tab. All Accuenergy device templates can be found in the remote update section of the page. In order to use the remote
upload function, users must ensure they have sucient connection to the Internet.
NOTE: For specic or third party templates please contact Accuenergy Technical Support.
For third party device templates, users can upload and install templates manually.
NOTE: Data log and alarm monitoring congurations will be lost after updating an existing
After the device is added, it can be found in the 'Modbus Devices' section under the 'DEVICE'
menu
A device that is successfully connected and communicating with the gateway will have a
green 'ON' mark under the status column. Whiles a device that is oline will display a red
'OFF' warning symbol.
NOTE: After adding a new device to the gateway it may take up to 3-4 minutes for the status
to show 'ON'. If after 3-4 minutes the device is showing a 'OFF' status, double check the con-
guration settings to ensure everything is set correctly.
The AcuLink 810 supports a Modbus Gateway Function, where users can add a Modbus
RTU device and use it as a gateway. Users must choose the device template as 'Modbus
Gateway Function Only'.
The Modbus Gateway Function allows users to forward a Modbus TCP request to the
corresponding meter.
Adding Modbus Gateway Device
To add a Modbus Gateway device, select add device. Under the 'Device Model' select
'Modbus Gateway Function Only'. Select 'RTU' as the protocol and enter in the communication settings for that RTU device (baud rate, parity, Modbus ID, etc). Click on 'Submit'
once all information is entered in correctly.
NOTE: Only Modbus RTU devices can be used as a Modbus Gateway Function on the AcuLink 810.
Once the gateway device is added there will be a gateway symbol under the 'Status' column
on the Modbus Devices page.
6.3 Viewing Data of Modbus Devices
To view the readings from your device, select 'Modbus Devices' on the left panel under the
'DEVICES' menu. On this page, all the Modbus devices added to the AcuLink 810 will appear
here. It will display the Device name, the serial number, status (oline or online) and the
The readings have the parameter listed on the left and the value of the parameter listed on
the right.
6.3.1 Conguration
The conguration page can be used to edit an existing Modbus Device on the AcuLink 810.
This can be used to change the IP address or Modbus port of a Modbus TCP/IP device, users
can also change the device address, baud rate, etc on an RS485 device.
To delete a device on the AcuLink 810 navigate to the 'Modbus Devices' under the 'DEVICES'
menu on the left panel of the interface. Then click on the delete icon under the 'Action'
column.
After selecting delete device, a message will appear asking the user to conrm the delete.
Select 'Yes, Delete' to remove the device and all stored data from the AcuLink 810.
Alternatively users can also delete a device from the gateway by clicking on the device from
the 'Modbus Device' page, and then selecting the 'Conguration' tab.
6.5 Alarms
The AcuLink 810 supports alarm monitoring on the Modbus devices connected to it. The
gateway allows users to monitor selected parameters using an under/over alarm. When the
monitored parameter goes over/under the preset limit, the alarm will be triggered.
6.5.1 How to create alarm
To create an alarm, click on 'Modbus Devices' under the 'DEVICES' menu on the left panel.
Select the desired device you want to set the alarm for.
On the Device page, select the 'Alarms' tab. Click on 'Add Alarm'.
• Parameter: In the drop down menu select the parameter to be monitored.
• Min: Select the minimum value to trigger the alarm parameter.
• Max: Select the maximum value to trigger the alarm parameter.
Click on 'Save' once all settings are entered in correctly.
For example if the parameter selected was 'Frequency' with a minimum threshold of 0
and a maximum threshold of 50, the alarm will be triggered when the frequency is less
than or equal to 0 Hz and when the frequency is greater or equal to 50 Hz. Any value
outside of the range set will trigger the alarm.
6.5.2 How to view alarm
The Alarm column in the Modbus Device List will show users the number of alarms
that have been triggered.
To view the Alarm click on the Device Name, and select the 'Alarms' tab. The alarm page displays the alarm conditions (max and min) as well as the current value of the parameter, the
status of the alarm (on or o) and the action for this alarm (edit or delete). The alarms can
also be viewed from the Alarm Logs which will be discussed later in the manual.
Users can delete the alarm at any time from this page by clicking on the delete icon on the far
right column of the alarm parameter.
6.6 Digital Inputs
The AcuLink 810 supports 8 Digital Input channels that can be congured to count pulses. To
congure the Digital Input from the web interface click on 'Digital Inputs' under the 'DEVIC-
Click on Edit to congure the digital input settings.
Enter in a Description and the units the pulses will be representing. A multiplier can be applied to the count if necessary. Users can also input a starting count value to the digital input
channel.
Users can check the historical data of the system event by clicking on 'Event Log' under 'LOG'
menu.
Event logs can be ltered by selecting the start time, end time and level.
Users can also clear all the event logs by clicking on 'Clear Logs'.
6.8 System Settings
The system settings page can be found on the left navigation panel under the 'CONFIGURATION' menu. The This page gives users a summary of the AcuLink 810's hardware version,
serial number ,the current rmware version and the date it was updated.
Users can restart the server, which is a soft reboot of the AcuLink 810 device.
In the System Information page there is also options to provide a Name, Description, and
location for the AcuLink 810 device. Once the user has lled in the settings correctly click on
'Save'.
In the System Status section of the page, users are provided with an overview of the CPU,
RAM, and disk usage.
Users can congure the time and date for the AcuLink 810 from the 'Date & Time' page in the
left navigation panel under the 'CONFIGURATION' menu.
• NTP Enabled: The AcuLink supports Network Time Protocol where the time can be synchronized with a time server.
• Device Clock: Users can enter in the time and date manually in the device clock setting.
Once the time and date is chosen the user must click on 'Update Time'.
• Time Sync: Users can force the time to update on the AcuLink 810 by selecting the 'Sync'
button.
• NTP Time Servers: By default the gateway uses '0.u.pool.ntp.org' time server. Users can
remove and add their own time servers as needed.
• NTP Server 1;2;3: Users can enter up to 3 NTP servers in the "NTP Server 1", "NTP Server
2" and "NTP Server 3" elds.
Examples of North American NTP servers are:
0.us.pool.ntp.org
1.us.pool.ntp.org
2.us.pool.ntp.org
3.us.pool.ntp.org
For more NTP servers based on region, visit the following site:
• Time Zone: Users can select the timezone where the gateway is installed.
6.10 Network Settings
The AcuLink 810 supports both Ethernet and WIFI communication. There are two Ethernet
ports that can be used. The network settings can be found under the 'CONFIGURATIONS'
menu on the left panel of the gateways web interface.
The DNS settings for the AcuLink are displayed. By default the DNS settings are:
• DNS 1: 8.8.8.8
• DNS 2: 8.8.4.4
6.10.1 WIFI
Users can congure the WIFI settings by selecting the 'WIFI' tab on the Network Congurations page.
Wi-Fi Enabled: Users can enable or disable the WIFI on the AcuLink 810
Wi-Fi Mode: There are two WiFi Modes:
1. Access Point Mode: Where the AcuLink 810 acts as a wireless bridge allowing other
• SSID: Users can create an SSID for the gateway, which will be used when other devices
connect.
• Network Key: Users can create a network key
• IP: Users can also enter in an IP address that will be used to access the meter while in Ac-
cess Point Mode.
NOTE: The default Network Key is accuenergy, and the default IP address is 192.168.100.1
2. Station Mode: Where the AcuLink 810 joins an existing WIFI network.
• SSID: Users can select from the list of wireless networks in range of the AcuLink 810.
• Network Key: Network key of the selected wireless network must be entered in this set-
ting.
• DHCP: Can be set to 'Manual' or 'Auto', where if 'Manual' is selected the Subnet Mask and
Gateway will also need to be provided. If 'Auto' is selected the AcuLink will have an IP address automatically assigned. With this selection the Subnet Mask, Gateway and will also
be automatically assigned.
• Interface Status: Will notify the user whether the AcuLink is connected or disconnected
to the WIFI network.
By default the WIFI mode is set for Access Point Mode, where the AcuLink 810 acts as a wireless bridge allowing other wireless devices to connect.
6.10.2 Ethernet 1
The Ethernet 1 settings can be congured by selecting the 'Ethernet 1' tab on the Network
Congurations page.
• Interface Status: Tells users whether there is an Ethernet cable connected or disconnected to the Ethernet 1 port.
• DHCP: Select 'Manual' to manually congure the IP address for Ethernet 1. If set to
'Manual', users will also need to set the Subnet Mask and Gateway. Select 'Auto' to have
the AcuLink 810 assigned an IP address automatically. With this selection the Subnet
Mask, Gateway and will also be automatically assigned.
• IP: If the DHCP is congured to Manual, the IP address can be congured.
• Subnet: If the DHCP is congured to Manual, the Subnet Mask can be congured.
• Gateway: If the DHCP is congured to Manual, the Gateway can be congured.
Ethernet 2 by default has the DHCP settings congured to 'Auto'. This means that when
connected to an internet source such as a router/switch, the network will assign an IP
address to it. Once the IP is assigned, users can discover the IP address by accessing the
Network Congurations page.
Users can also change the DHCP to 'Manual' for Ethernet 2 and connect to the network
manually.
Select 'Alarm Notication' under 'CONFIGURATION' menu to set the email recipients that will
receive the emails for alarms.
To enable the alarm notication, select 'Enabled'. With the alarm notication enabled users
will be notied via email when an alarm is over/under the alarm condition. The AcuLink 810
supports a maximum of 3 recipients, once email address for each recipient is entered and
click on 'Save'. Once an recipient has been added, users can click on 'Test Email' button to
check if a test email is received.
6.13 Post Channels
The AcuLink 810 supports 3 HTTP/FTP channels.
To congure the HTTP/FTP data forward from the web interface click on 'Post Channel' under the 'CONFIGURATION' menu on the left panel of the interface.
To congure the post channels select the corresponding post channel tab.
6.13.1 HTTP Post Method
The HTTP post method allows the user to post meter data to an HTTP/HTTPS server.
Post Channel Enable: Select Enabled to enable the post channel data forward
Post Method: Choose from either HTTP/HTTPS in the drop down menu
Post Name Fixed: Select Yes or No to enable a xed post name, if yes selected enter in
HTTP/HTTPS URL: Select HTTP or HTTPS option from the drop down menu before entering
in the URL. Next enter in the URL of the server.
HTTP/HTTPS Port: Enter the correct port for the HTTP server.
HTTP/HTTPS Meter ID: Enter in the meter ID
Once the settings are entered in correctly click on 'Save'. After the settings are saved, users
can use the 'Test Post Channel' button to test whether the AcuLink 810 can successfully reach
the HTTP server.
NOTE: If users receive a fail message, please verify the server URL, port number and double
check the network connectivity.
6.13.2 FTP Post Method
The FTP post method allows the user to post meter data to an FTP server.
Post Channel Enable: Select Enabled to enable the post channel data forward
Post Method: Select FTP protocol
FTP URL: Enter in the FTP URL
FTP Port: Enter the FTP port number
FTP Username: Enter the username to access the FTP server
FTP Password: Enter the password to access the FTP server
Once all settings are entered in correctly, click on 'Save'. Users can use the 'Test Post
Channel' button to determine whether the 810 can reach the FTP server.
NOTE: If users receive a fail message, please verify the server URL, port number, username, password and double check the network connectivity.
6.14 Data Logging
The AcuLink 810 supports data logging to its internal memory, which has 8GB of memory.
When the memory is full the oldest data logs will be overwritten. To congure the AcuLink
810 to log the meter data click on 'Data Log' under the 'CONFIGURATION' menu on the left
navigation panel.
AcuLink 810 supports at most 3 data loggers, the data log for each logger can be pushed to
the post channel or saved in its internal memory.
• Data Log Enable: Select 'Enabled' to enable the data log
• Post Channel: Select the Post Channel from the drop down list:
• None: AcuLink 810 will log and store the data on its memory
• Post Channel 1/2/3: AcuLink 810 will log and push the data to the congured post
channel. Users will not be able to select the post channel if it is disabled.
NOTE: For more information on conguring the Upload Protocol refer to the 'Post Chan-
nels' section of the user manual.
• Timestamp Format: Select the format of the timestamp for the data that is logged. The
format for the timestamp can be based on the Local Time, UTC Seconds or based on
ISO8601 Format.
• Log File Name Format: Select the format of the log le name for the data that is
logged. The format for the log le name can be based on UTC Timestamp or Time inter-
val Format.
• Log Interval: Select how frequently the module will log data to the le from the drop
down list. The logging interval can be from 1 minute to 1 month.
• Log File length: Select the length of the log le, it can be from 1 minute to 1 month.
NOTE: The log interval must be less than or equal to the log le length.
• Log File Name Prex: Provide a name for the log le which will be appended to the be-
ginning of the log le. By default "logger1" will be appended to the beginning of the log
le.
• Select the device(s) to log the data for.
When all of the settings are entered in correctly, click on 'Save'. All the data logs can be
downloaded from 'Download' under 'DATA MANAGEMENT' menu.
NOTE: For more information on data log downloading and deleting, please refer to the 'Data
Management' section of the user manual.
Users can upload meter data to Accuenergy's free cloud based software called
AcuCloud. AcuCloud is a cloud-based facility metering platform that provides
users access to data from Accuenergy’s power meters, and is free for all Accuenergy meters.
To congure the AcuLink 810 to post data to AcuCloud, click on 'AcuCloud'
from left navigation panel under the 'CONFIGURATION' menu.
Users will need an AcuCloud account in order to add the AcuLink 810 as a device.
To create your AcuCloud account contact Accuenergy Technical Support.
If you already have an AcuCloud account, the following steps can be used to add
the gateway to AcuCloud.
NOTE: The serial number can be found and copied on the AcuCloud conguration page of
AcuLink 810 web interface.
• Provide a description for the location of the device under Location.
• Click SUBMIT.
Once the gateway has been successfully created, a token will be returned on the ensuing
page. The user will need to copy the token that is provided as it will be used in the next step
to congure the gateway to send its data to AcuCloud.
• Go back the AcuLink 810 web interface and paste the token that was generated into the
• Select the devices that need to be connected to Acucloud.
• Click Save
• Then click on 'Test Connection' to see if the AcuLink can reach the AcuCloud server.
NOTE: If the test connection fails, please check the network settings of the AcuLink
810 and if the token is entered correctly.
The AcuLink 810 gateway is now successfully congured to report to the AcuCloud
EMS software. Check to see if AcuCloud is receiving data from the gateway by going to
the Devices page in AcuCloud and observing whether the name of the selected devices from the gateway appear in AcuCloud with a Last Received Data timestamp.
If the gateway is oline or stops posting to the cloud, it will be backed up to the last
3000 posts. Once the meter reestablishes a connection to the cloud it will post the
les to AcuCloud. Users can remove or clear the back up posts at anytime by clicking
You can manage the data logs directly from the user interface of the AcuLink 810. This page
allows the user to download or delete data from their Modbus devices.
6.16.1 Download Data
To download the Data Logs select the 'Download' tab under 'DATA MANAGEMENT' menu.
• Select Device: Select the device you wish to read the data from.
• From/To Date: Select the date and time frame to read the data log.
NOTE: Data Logs will only be recorded for the devices that have been selected in logger 1,2,3
or AcuCloud.
Click on 'Download' once all information is entered in correctly. The data will be down-
loaded as a .csv le to your computer directly.
NOTE: Depending on the amount of data stored this may take several minutes to complete
the data download.
Delete Data
To delete the Data Logs select the 'Delete' tab under 'DATA MANAGEMENT' menu.
Select Device: Choose the device you want to delete data for.
Once all the settings are entered in correctly, click on 'Delete Data Log'. All the data related
to the selected device will be deleted.
NOTE: Once data is deleted from the AcuLink 810 it cannot be undone.
When users are logged in as an Admin they can change the password for both Admin and
Viewer access levels. Once the new password is entered click on 'Save'.
6.16.3 Firmware Update
The rmware of the AcuLink 810 can be updated from the 'Firmware' page under the 'CONFIGURATIONS' menu. This page lists the current rmware of the gateway.
The rmware update can be updated manually or remotely using the server.
Once the rmware is uploaded, click on 'Start' to begin the updating process.
Once the rmware update is complete, the AcuLink 810 will restart.
Remote Firmware Update
The rmware of the AcuLink 810 can be updated using the remote rmware option. This will
allow users to check for the latest rmware updates. To use the remote rmware update click
on 'Check' which will verify if there is an update available or whether the gateway already has
In the 'Host Look Up' tab, users can use the ping function to test whether the AcuLink can
communicate over the network it is connected to.
Under the 'Connection Test' tab user can test the local network that the AcuLink is connected to. The test result will show SUCCESS and PASS if there is no issues found, and will show
FAIL if there are network issues.
The AcuLink 810's diagnostic le can be downloaded by the user from the Debug
page. If users are experiencing any issues with the gateway, the diagnostic le
can be sent to Accuenergy Technical Support for further analysis.
On the AcuLink 810 unit there is a reset button located on the back of the unit where the
Ethernet and USB ports are. The reset button resets the AcuLink 810 back to default meaning that all devices, data logs, alarm/event log, and device templates will be deleted. The
only Device Template that will remain after the reset is the Modbus Gateway Function, however all other Modbus templates will be removed.
After the reset all network communications will be restored back to default meaning the AcuLink will have the following network settings after the reset:
• WIFI Mode - Access Point (AP) mode
• Ethernet 1 - 192.168.8.101
• Ethernet 2 - DHCP enabled
To successfully perform a reset on the AcuLink 810 gateway press and hold the reset button
for 10 seconds until all LED lights on the unit are ashing. The reset will be complete when
the LED lights stop ashing.