Please read this manual carefully before installation, operation and maintenance of the
AcuLink810 series meter. The following symbols in this manual are used to provide warning of
danger or risk during the installation and operation of the meters.
Electric Shock Symbol: Carries information about procedures which must be
followed to reduce the risk of electric shock and danger to personal health.
Safety Alert Symbol: Carries information about circumstances which if not
considered may result in injury or death.
Prior to maintenance and repair, the equipment must be de-energized and grounded. All
maintenance work must be performed by qualied, competent accredited professionals who
have received formal training and have experience with high voltage and current devices.
Accuenergy shall not be responsible or liable for any damages or injuries caused by improper
meter installation and/or operation.
The AcuLink 810 is an intelligent data acquisition server and gateway that allows users to
collect data from all Accuenergy meters, sensors and other third party devices.
The AcuLink collects and logs time-stamped data from connected downstream devices (serial or Ethernet), and is able to store this data locally in non volatile memory. When using
Ethernet it is possible to push or pull data using HTTP or FTP protocols as well as pushing
data to dierent web-based energy management systems or any front end software platform. There is no software required for the AcuLink as all conguration is done from the
gateways web interface.
2. Functional Description
2.1 Hardware Specications
• Disk Capacity: 8 GB RAM
• Interval Recording: 1-1440 minutes, user selectable
• LAN: 2 x RJ45 10/100 Ethernet, full half duplex, auto polarity
• WIFI: 802.11 b/g/n, 2.4GHz
• USB: USB expansion port, USB 2.0 Host
2.4 Inputs
Serial Port: RS485 Modbus, supports up to 32 external devices (expandable)
Baud Rate: 9600-115200 bps
Digital Input: 8 pulse counters
Input Voltage Range: 8-28Vdc
Input Current (Max): 8mA
Start Voltage: 15V
Stop Voltage: 5V
Pulse Frequency (Max): 100Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
2.5 Environment
• North America: -25 to 70 degrees Celsius, 90% RH, non-condensing
V: 1.0 Revised: May. 2019
www.accuenergy.com
5
Chapter 3: Appearance & Dimensions
159.9mm (6.3”)
90mm (3.5”)
3. Appearance and Dimensions
10mm
6
DATA ACQUSITION SERVER
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 4: Installation
(1.27”)
10mm
32.2mm
(1.27”)
159.9mm (6.3”)
32.2mm
4. Installation
4.1 Installation Checklist
The following materials are required for the AcuLink 810 installation:
• AcuLink 810 Data Acquisition Server
• Ethernet Connection
• Ethernet Cat 5 Cable (Required for LAN or direct computer to AcuLink 810 connection)
• Power Supply (24V)
• WIFI Antenna
Optional Hardware:
• Additional Modbus RTU devices
• 2 wire Modbus/RS485 connection
35mm
6.8mm
LAN Information
• Ethernet 10/100MB connection point (router/switch)
• IP address and subnet mask (Check with system administrator)
• Gateway Address (Check with system administrator)
• DNS server address (Check with system administrator)
www.accuenergy.com
V: 1.0 Revised: May. 2019
7
Chapter 4: Installation
4.2 Hardware installation
The AcuLink 810 is DIN rail mounted, a standard 35 mm DIN rail can be used.
4.2.1 Powering the unit
• The power supply of the AcuLink 810 is rated for 24Vdc.
DATA ACQUSITION SERVER
+V -V
24Vdc
8
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 4: Installation
4.2.2 RS485 Network
The AcuLink 810 gateway supports RS485 serial communication. Users can setup an RS485
connection to the AcuLink with any Accuenergy or third party device. If connecting multiple
devices or 'daisy chaining' the devices together, ensure that a unique device address (Mod-
bus Slave ID) is congured for each RS485 device. The AcuLink 810 can support up to 32
external RS485 devices.
NOTE: A termination resistor at the end of the RS485 network is optional when daisy chaining multiple devices. If using resistor a termination value of 150 ohms can be used.
DATA ACQUSITION SERVER
AcuRev 2000 Series meter
www.accuenergy.com
Acuvim II Series meter
Third Party Modbus
Device
V: 1.0 Revised: May. 2019
9
Chapter 4: Installation
4.2.3 Digital Input Setup
The AcuLink 810 has 8 Digital Input channels. Each Digital Input can be used as an input
pulse counter.
Each channel has two terminals, a DI terminal and a DI COM terminal. In pulse output circuits a closed loop is required for the pulse to be generated. In the Image below you will see
a closed circuit on Digital Inputs 1 and 6. The positive output is connected to the DI channel
input and negative output is connected to the DI Common input.
DATA ACQUSITION SERVER
-
+
Water Meter Pulse
Output
10
V: 1.0 Revised: May. 2019
Energy Meter Pulse
+
Output
-
www.accuenergy.com
Chapter 5: Initializing the AcuLink 810
5. Initializing the AcuLink 810
The AcuLink 810 has a web interface that users can access to congure settings and view
device data. The AcuLink 810 gateway has two Ethernet ports and also supports communication via WIFI.
The default IP addresses and default modes are:
Ethernet 1:
Ethernet 2:
WIFI:
192.168.8.101
DHCP
Access Point Mode
The following will outline the methods on how to initially access the meters web interface.
5.1 Accessing the AcuLink 810 Web Interface
5.1.1 Method 1 - Direct Connection via Ethernet
For the direct connection method, there must be an Ethernet connection from the Ethernet 1 port on the AcuLink and a computer.
DATA ACQUSITION SERVER
www.accuenergy.com
V: 1.0 Revised: May. 2019
11
Chapter 5: Initializing the AcuLink 810
Next in order to access the web interface, the computers IP address must be congured within the same subnet as the AcuLink Ethernet 1 IP address. The Ethernet 1
port has a default IP address of 192.168.8.101. The following outlines how to change
the computers IP:
• Start by accessing the control panel of the computer and select 'Network and
Internet'.
• Select 'Network and Sharing Center'.
12
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 5: Initializing the AcuLink 810
• On the left panel of the screen, select 'Change adapter settings'
• Double click on 'Ethernet', or right click on 'Ethernet' and select 'Properties'.
• The following page will open, click on 'Properties'.
www.accuenergy.com
V: 1.0 Revised: May. 2019
13
Chapter 5: Initializing the AcuLink 810
• The following page will open, select 'Internet Protocol Version 4 (TCP/IPv4) and click on
'Properties'.
• Select 'Use the following IP address:' and change the IP address of the computer. The
AcuLink 810 Ethernet 1 address is 192.168.8.101, the computers IP will need to be within the
same subnet. The IP of the computer can be 192.168.8.xxx, where xxx can be any number
ranging from 1-254. For the example an IP address of 192.168.8.10 is used.
NOTE: The computers IP address and the AcuLink 810 Ethernet 1 IP address cannot be the
same.
14
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 5: Initializing the AcuLink 810
• Once all settings are complete click on 'OK' to conrm the network changes.
• Then open up a internet browser and type in the AcuLink 810 IP address of
192.168.8.101, the following login screen will be prompted.
• There are two Access Levels, 'Viewer' and 'Admin'.
• Viewer allows users to only view and read data, the password for this user level
is viewer.
• Admin allows users to read data, as well as change and modify all settings of
the AcuLink 810, the password for this user level is admin.
NOTE: The recommended internet browsers to access the 810's web interface is Google Chrome, or FireFox.
www.accuenergy.com
V: 1.0 Revised: May. 2019
15
Chapter 5: Initializing the AcuLink 810
5.1.2 Method 2 - Using WIFI to connect to the Meters Web Interface
The web interface of the AcuLink can be accessed by WIFI. Ensure that the WIFI antenna is installed on the unit.
DATA ACQUSITION SERVER
By default the AcuLink 810 has its WIFI mode set as AP (Access Point) mode, where the
AcuLink 810 acts as a wireless access point allowing other wireless devices to connect
and access the gateway.
To connect to the AcuLink via AP mode, search for the SSID in the list of wireless networks.
The SSID will be by default AcuLink810-WIFI-S8Pxxxxxxxx, where the 'S8Pxxxxxxxx' is a
unique serial number of the AcuLink gateway. The serial number of the AcuLink can be
found on the side of the unit. The password for the network is
16
V: 1.0 Revised: May. 2019
accuenergy
www.accuenergy.com
.
Chapter 5: Initializing the AcuLink 810
Once connected to the gateways wireless network, open up an internet browser and enter in
the IP address
• There are two Access Level, 'Viewer' and 'Admin'.
• Viewer allows users only to view and read data, the password for this user level is
• Admin allows users to read data, as well as change and modify the settings of the Acu-
view
.
192.168.100.1
. The following login screen will be prompted.
Link 810, the password for this user level is
admin
.
www.accuenergy.com
V: 1.0 Revised: May. 2019
17
Chapter 6: AcuLink 810 User interface
6. AcuLink 810 User Interface
When you log in the to the AcuLink 810 web interface, users are directed to the 'Dashboard'.
The dashboard provides the user with a summary of all the Oline Devices as well as the
Devices in Alarm.
The navigation panel on the left side of the interface allows users to access dierent settings
within the gateway.
The footer on the bottom of the web page includes the server time and date. The footer
also includes the time that the gateway was initially powered on.
6.1 Modbus Template
Modbus Templates are used in the AcuLink 810 to correctly read the metering data from
Accuenergy and third party Modbus devices. Before a device can be added to the gateway a
Modbus template for the device must rst be uploaded and installed onto the unit.
On the left navigation panel under the 'CONFIGURATION' menu, select 'Modbus Template'.
In the Modbus templates page users can view the templates and the version number currently installed on to the AcuLink under the 'Installed' tab.
18
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
To upload a new device template click on the 'New/Update' tab. All Accuenergy device templates can be found in the remote update section of the page. In order to use the remote
upload function, users must ensure they have sucient connection to the Internet.
NOTE: For specic or third party templates please contact Accuenergy Technical Support.
For third party device templates, users can upload and install templates manually.
NOTE: Data log and alarm monitoring congurations will be lost after updating an existing
device template.
www.accuenergy.com
V: 1.0 Revised: May. 2019
19
Chapter 6: AcuLink 810 User interface
6.2 Adding Devices to the AcuLink 810
On the left navigation panel of the AcuLink 810 web interface, there is a menu titled 'DEVICE'. In the devices menu there are two options:
1. Modbus Device
2. Digital Input
This is where users can add a Modbus device or congure the digital input on the AcuLink
810 gateway. The user can add devices to the gateway by Modbus RTU, and by Modbus TCP.
Modbus TCP
Netwiork Switch
Acuvim II Series Meter
Ethernet Cable
Ethernet Cable
DATA ACQUSITION SERVER
20
V: 1.0 Revised: May. 2019
www.accuenergy.com
Modbus RTU via RS485
Modbus RTU via USB
Chapter 6: AcuLink 810 User interface
DATA ACQUSITION SERVER
AcuRev 1310 Series Meter
Acuvim L Series Meter
www.accuenergy.com
RS485 to USB
converter cable
DATA ACQUSITION SERVER
V: 1.0 Revised: May. 2019
21
Chapter 6: AcuLink 810 User interface
To add a device to the AcuLink 810, you will need to login under Admin access level.
From the left navigation panel, select 'Modbus Device' under the 'DEVICE' menu.
The user will see all the devices that are currently communicating with the gateway on this
page.
Click on 'Add Device'.
• Provide a name for the Device under the Device Name eld
• Enter the Serial Number for the Device
• Select the Model of the Device from the Device Model drop down list
• Enter the Request Timeout from 1-60 sec.
NOTE: Users cannot add two devices with the same serial number. Each serial number must be
unique for each device.
Select the Protocol
• RTU - Serial communication via RS485, USB, or AcuMesh
• TCP - Communication using TCP over Ethernet or WiFi
22
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.2.1 Modbus-TCP/IP
With the Modbus TCP/IP protocol selected, congure the following elds:
• IP Address: Enter the IP address of the device
• Port: Enter the Modbus port of the device
• Modbus ID: Enter the Modbus address of the device
• Request Timeout: Enter the timeout setting, default for TCP is 3 seconds
Click 'Submit' once all settings are entered in correctly.
6.2.2 Modbus-RTU
With the Modbus RTU protocol selected, congure the following elds:
Address: Enter the device address (Modbus Slave ID) of the meter, range is from 1-247
V: 1.0 Revised: May. 2019
www.accuenergy.com
23
Chapter 6: AcuLink 810 User interface
Port: Users can select either RS485 or USB
Baud Rate: Select the baud rate of the device, range is from 9600-115200
Data Bit: Select the number of data bits, either 7 or 8
Parity: Select the parity of the device from the drop down list
Stop Bit: Select the number of Stop Bits
Request Timeout: Select a timeout period for the AcuLink 810 to wait for a response from
the device, range is 1-60 seconds, default for Modbus RTU is 0.5.
NOTE: Users cannot add device with the same device address (Modbus Slave ID). The device
address must be unique for each device in the RS485 network.
Click 'Submit' once all settings are entered in correctly.
24
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
After the device is added, it can be found in the 'Modbus Devices' section under the 'DEVICE'
menu
A device that is successfully connected and communicating with the gateway will have a
green 'ON' mark under the status column. Whiles a device that is oline will display a red
'OFF' warning symbol.
NOTE: After adding a new device to the gateway it may take up to 3-4 minutes for the status
to show 'ON'. If after 3-4 minutes the device is showing a 'OFF' status, double check the con-
guration settings to ensure everything is set correctly.
V: 1.0 Revised: May. 2019
www.accuenergy.com
25
Chapter 6: AcuLink 810 User interface
6.2.3 Modbus Gateway Function
The AcuLink 810 supports a Modbus Gateway Function, where users can add a Modbus
RTU device and use it as a gateway. Users must choose the device template as 'Modbus
Gateway Function Only'.
The Modbus Gateway Function allows users to forward a Modbus TCP request to the
corresponding meter.
Adding Modbus Gateway Device
To add a Modbus Gateway device, select add device. Under the 'Device Model' select
'Modbus Gateway Function Only'. Select 'RTU' as the protocol and enter in the communication settings for that RTU device (baud rate, parity, Modbus ID, etc). Click on 'Submit'
once all information is entered in correctly.
NOTE: Only Modbus RTU devices can be used as a Modbus Gateway Function on the AcuLink 810.
26
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
Once the gateway device is added there will be a gateway symbol under the 'Status' column
on the Modbus Devices page.
6.3 Viewing Data of Modbus Devices
To view the readings from your device, select 'Modbus Devices' on the left panel under the
'DEVICES' menu. On this page, all the Modbus devices added to the AcuLink 810 will appear
here. It will display the Device name, the serial number, status (oline or online) and the
number of alarms triggered for the device.
www.accuenergy.com
V: 1.0 Revised: May. 2019
27
Chapter 6: AcuLink 810 User interface
Select the device you wish to view the data for. The following Device page will open.
The Device data can be viewed on the 'Reading' tab.
In the Readings tab users can view the meters real time data. In the drop down menu there
are options to select the dierent categories of the real time data. Each drop down menu
will vary depending on the device template chosen for the device.
28
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
The readings have the parameter listed on the left and the value of the parameter listed on
the right.
6.3.1 Conguration
The conguration page can be used to edit an existing Modbus Device on the AcuLink 810.
This can be used to change the IP address or Modbus port of a Modbus TCP/IP device, users
can also change the device address, baud rate, etc on an RS485 device.
www.accuenergy.com
V: 1.0 Revised: May. 2019
29
Chapter 6: AcuLink 810 User interface
6.4 Deleting Modbus Devices from AcuLink 810
To delete a device on the AcuLink 810 navigate to the 'Modbus Devices' under the 'DEVICES'
menu on the left panel of the interface. Then click on the delete icon under the 'Action'
column.
After selecting delete device, a message will appear asking the user to conrm the delete.
Select 'Yes, Delete' to remove the device and all stored data from the AcuLink 810.
30
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
Alternatively users can also delete a device from the gateway by clicking on the device from
the 'Modbus Device' page, and then selecting the 'Conguration' tab.
6.5 Alarms
The AcuLink 810 supports alarm monitoring on the Modbus devices connected to it. The
gateway allows users to monitor selected parameters using an under/over alarm. When the
monitored parameter goes over/under the preset limit, the alarm will be triggered.
6.5.1 How to create alarm
To create an alarm, click on 'Modbus Devices' under the 'DEVICES' menu on the left panel.
Select the desired device you want to set the alarm for.
On the Device page, select the 'Alarms' tab. Click on 'Add Alarm'.
V: 1.0 Revised: May. 2019
www.accuenergy.com
31
Chapter 6: AcuLink 810 User interface
The following settings will need to congured:
• Label: Description of the alarm.
• Parameter: In the drop down menu select the parameter to be monitored.
• Min: Select the minimum value to trigger the alarm parameter.
• Max: Select the maximum value to trigger the alarm parameter.
Click on 'Save' once all settings are entered in correctly.
For example if the parameter selected was 'Frequency' with a minimum threshold of 0
and a maximum threshold of 50, the alarm will be triggered when the frequency is less
than or equal to 0 Hz and when the frequency is greater or equal to 50 Hz. Any value
outside of the range set will trigger the alarm.
6.5.2 How to view alarm
The Alarm column in the Modbus Device List will show users the number of alarms
that have been triggered.
32
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
To view the Alarm click on the Device Name, and select the 'Alarms' tab. The alarm page displays the alarm conditions (max and min) as well as the current value of the parameter, the
status of the alarm (on or o) and the action for this alarm (edit or delete). The alarms can
also be viewed from the Alarm Logs which will be discussed later in the manual.
Users can delete the alarm at any time from this page by clicking on the delete icon on the far
right column of the alarm parameter.
6.6 Digital Inputs
The AcuLink 810 supports 8 Digital Input channels that can be congured to count pulses. To
congure the Digital Input from the web interface click on 'Digital Inputs' under the 'DEVIC-
ES' menu on the left panel of the interface.
V: 1.0 Revised: May. 2019
www.accuenergy.com
33
Chapter 6: AcuLink 810 User interface
Click on Edit to congure the digital input settings.
Enter in a Description and the units the pulses will be representing. A multiplier can be applied to the count if necessary. Users can also input a starting count value to the digital input
channel.
34
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
Once the Digital Inputs are congured, users can see the count value, the reading value, units
and multiplier that is applied to the Digital Input channel.
6.7 Logs
6.7.1 Alarm Logs
Users can check the historical data of the triggered alarms by clicking on 'Alarm Log'
under 'LOG' menu.
Alarm logs can be ltered by selecting the start time, end time, serial number and
monitor ID.
Users can also clear all the alarm logs by clicking on 'Clear Logs'.
www.accuenergy.com
V: 1.0 Revised: May. 2019
35
Chapter 6: AcuLink 810 User interface
6.7.2 Event Logs
Users can check the historical data of the system event by clicking on 'Event Log' under 'LOG'
menu.
Event logs can be ltered by selecting the start time, end time and level.
Users can also clear all the event logs by clicking on 'Clear Logs'.
6.8 System Settings
The system settings page can be found on the left navigation panel under the 'CONFIGURATION' menu. The This page gives users a summary of the AcuLink 810's hardware version,
serial number ,the current rmware version and the date it was updated.
Users can restart the server, which is a soft reboot of the AcuLink 810 device.
In the System Information page there is also options to provide a Name, Description, and
location for the AcuLink 810 device. Once the user has lled in the settings correctly click on
'Save'.
In the System Status section of the page, users are provided with an overview of the CPU,
RAM, and disk usage.
36
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.9 Date & Time
Users can congure the time and date for the AcuLink 810 from the 'Date & Time' page in the
left navigation panel under the 'CONFIGURATION' menu.
• NTP Enabled: The AcuLink supports Network Time Protocol where the time can be synchronized with a time server.
• Device Clock: Users can enter in the time and date manually in the device clock setting.
Once the time and date is chosen the user must click on 'Update Time'.
• Time Sync: Users can force the time to update on the AcuLink 810 by selecting the 'Sync'
button.
• NTP Time Servers: By default the gateway uses '0.u.pool.ntp.org' time server. Users can
remove and add their own time servers as needed.
• NTP Server 1;2;3: Users can enter up to 3 NTP servers in the "NTP Server 1", "NTP Server
2" and "NTP Server 3" elds.
Examples of North American NTP servers are:
0.us.pool.ntp.org
1.us.pool.ntp.org
2.us.pool.ntp.org
3.us.pool.ntp.org
For more NTP servers based on region, visit the following site:
http://www.pool.ntp.org/en/
V: 1.0 Revised: May. 2019
www.accuenergy.com
37
Chapter 6: AcuLink 810 User interface
• Time Zone: Users can select the timezone where the gateway is installed.
6.10 Network Settings
The AcuLink 810 supports both Ethernet and WIFI communication. There are two Ethernet
ports that can be used. The network settings can be found under the 'CONFIGURATIONS'
menu on the left panel of the gateways web interface.
The DNS settings for the AcuLink are displayed. By default the DNS settings are:
• DNS 1: 8.8.8.8
• DNS 2: 8.8.4.4
6.10.1 WIFI
Users can congure the WIFI settings by selecting the 'WIFI' tab on the Network Congurations page.
Wi-Fi Enabled: Users can enable or disable the WIFI on the AcuLink 810
Wi-Fi Mode: There are two WiFi Modes:
1. Access Point Mode: Where the AcuLink 810 acts as a wireless bridge allowing other
wireless devices to connect to it.
38
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
• SSID: Users can create an SSID for the gateway, which will be used when other devices
connect.
• Network Key: Users can create a network key
• IP: Users can also enter in an IP address that will be used to access the meter while in Ac-
cess Point Mode.
NOTE: The default Network Key is accuenergy, and the default IP address is 192.168.100.1
2. Station Mode: Where the AcuLink 810 joins an existing WIFI network.
• SSID: Users can select from the list of wireless networks in range of the AcuLink 810.
• Network Key: Network key of the selected wireless network must be entered in this set-
ting.
• DHCP: Can be set to 'Manual' or 'Auto', where if 'Manual' is selected the Subnet Mask and
Gateway will also need to be provided. If 'Auto' is selected the AcuLink will have an IP address automatically assigned. With this selection the Subnet Mask, Gateway and will also
be automatically assigned.
• Interface Status: Will notify the user whether the AcuLink is connected or disconnected
to the WIFI network.
V: 1.0 Revised: May. 2019
www.accuenergy.com
39
Chapter 6: AcuLink 810 User interface
By default the WIFI mode is set for Access Point Mode, where the AcuLink 810 acts as a wireless bridge allowing other wireless devices to connect.
6.10.2 Ethernet 1
The Ethernet 1 settings can be congured by selecting the 'Ethernet 1' tab on the Network
Congurations page.
• Interface Status: Tells users whether there is an Ethernet cable connected or disconnected to the Ethernet 1 port.
• DHCP: Select 'Manual' to manually congure the IP address for Ethernet 1. If set to
'Manual', users will also need to set the Subnet Mask and Gateway. Select 'Auto' to have
the AcuLink 810 assigned an IP address automatically. With this selection the Subnet
Mask, Gateway and will also be automatically assigned.
• IP: If the DHCP is congured to Manual, the IP address can be congured.
• Subnet: If the DHCP is congured to Manual, the Subnet Mask can be congured.
• Gateway: If the DHCP is congured to Manual, the Gateway can be congured.
40
V: 1.0 Revised: May. 2019
www.accuenergy.com
By default Ethernet 1 has the following settings:
• DHCP: Manual
• IP: 192.168.8.101
• Subnet: 255.255.255.0
• Gateway: 192.168.8.1
6.10.3 Ethernet 2
Chapter 6: AcuLink 810 User interface
Ethernet 2 by default has the DHCP settings congured to 'Auto'. This means that when
connected to an internet source such as a router/switch, the network will assign an IP
address to it. Once the IP is assigned, users can discover the IP address by accessing the
Network Congurations page.
Users can also change the DHCP to 'Manual' for Ethernet 2 and connect to the network
manually.
V: 1.0 Revised: May. 2019
www.accuenergy.com
41
Chapter 6: AcuLink 810 User interface
6.11 Email (SMTP)
Users can send emails for alarm triggering. To do this on the AcuLink 810 users must con-
gure the SMTP server and credentials.
To congure the Email setting, select 'Email' under the 'Conguration' menu on the left
panel of the interface.
The user must rst congure their SMTP server settings and details in order for the gateway to send the emails.
• Email Server: Enter the SMTP Server for the email account.
• Email Port: Enter the outgoing port number the SMTP uses to send emails.
• TLS/SSL: Select Auto/On/O for the email's server. Please select Auto if the security
setting of the server is unknown.
• Sender Name: Enter a sender name for the email
• From Email Address: Enter the email address that will be in the from eld of the email
• Username: Enter the email address for where the emails will be coming from
• Password: Enter the password for the email address in Username
Click 'Save' once all the settings are entered in correctly.
42
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.12 Alarm Notication
Select 'Alarm Notication' under 'CONFIGURATION' menu to set the email recipients that will
receive the emails for alarms.
To enable the alarm notication, select 'Enabled'. With the alarm notication enabled users
will be notied via email when an alarm is over/under the alarm condition. The AcuLink 810
supports a maximum of 3 recipients, once email address for each recipient is entered and
click on 'Save'. Once an recipient has been added, users can click on 'Test Email' button to
check if a test email is received.
6.13 Post Channels
The AcuLink 810 supports 3 HTTP/FTP channels.
To congure the HTTP/FTP data forward from the web interface click on 'Post Channel' under the 'CONFIGURATION' menu on the left panel of the interface.
To congure the post channels select the corresponding post channel tab.
6.13.1 HTTP Post Method
The HTTP post method allows the user to post meter data to an HTTP/HTTPS server.
Post Channel Enable: Select Enabled to enable the post channel data forward
Post Method: Choose from either HTTP/HTTPS in the drop down menu
Post Name Fixed: Select Yes or No to enable a xed post name, if yes selected enter in
the post name.
V: 1.0 Revised: May. 2019
www.accuenergy.com
43
Chapter 6: AcuLink 810 User interface
HTTP/HTTPS URL: Select HTTP or HTTPS option from the drop down menu before entering
in the URL. Next enter in the URL of the server.
HTTP/HTTPS Port: Enter the correct port for the HTTP server.
HTTP/HTTPS Meter ID: Enter in the meter ID
Once the settings are entered in correctly click on 'Save'. After the settings are saved, users
can use the 'Test Post Channel' button to test whether the AcuLink 810 can successfully reach
the HTTP server.
NOTE: If users receive a fail message, please verify the server URL, port number and double
check the network connectivity.
6.13.2 FTP Post Method
The FTP post method allows the user to post meter data to an FTP server.
Post Channel Enable: Select Enabled to enable the post channel data forward
Post Method: Select FTP protocol
FTP URL: Enter in the FTP URL
FTP Port: Enter the FTP port number
FTP Username: Enter the username to access the FTP server
FTP Password: Enter the password to access the FTP server
44
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
Once all settings are entered in correctly, click on 'Save'. Users can use the 'Test Post
Channel' button to determine whether the 810 can reach the FTP server.
NOTE: If users receive a fail message, please verify the server URL, port number, username, password and double check the network connectivity.
6.14 Data Logging
The AcuLink 810 supports data logging to its internal memory, which has 8GB of memory.
When the memory is full the oldest data logs will be overwritten. To congure the AcuLink
810 to log the meter data click on 'Data Log' under the 'CONFIGURATION' menu on the left
navigation panel.
AcuLink 810 supports at most 3 data loggers, the data log for each logger can be pushed to
the post channel or saved in its internal memory.
• Data Log Enable: Select 'Enabled' to enable the data log
• Post Channel: Select the Post Channel from the drop down list:
• None: AcuLink 810 will log and store the data on its memory
• Post Channel 1/2/3: AcuLink 810 will log and push the data to the congured post
channel. Users will not be able to select the post channel if it is disabled.
NOTE: For more information on conguring the Upload Protocol refer to the 'Post Chan-
nels' section of the user manual.
V: 1.0 Revised: May. 2019
www.accuenergy.com
45
Chapter 6: AcuLink 810 User interface
• Timestamp Format: Select the format of the timestamp for the data that is logged. The
format for the timestamp can be based on the Local Time, UTC Seconds or based on
ISO8601 Format.
• Log File Name Format: Select the format of the log le name for the data that is
logged. The format for the log le name can be based on UTC Timestamp or Time inter-
val Format.
• Log Interval: Select how frequently the module will log data to the le from the drop
down list. The logging interval can be from 1 minute to 1 month.
• Log File length: Select the length of the log le, it can be from 1 minute to 1 month.
NOTE: The log interval must be less than or equal to the log le length.
• Log File Name Prex: Provide a name for the log le which will be appended to the be-
ginning of the log le. By default "logger1" will be appended to the beginning of the log
le.
• Select the device(s) to log the data for.
When all of the settings are entered in correctly, click on 'Save'. All the data logs can be
downloaded from 'Download' under 'DATA MANAGEMENT' menu.
NOTE: For more information on data log downloading and deleting, please refer to the 'Data
Management' section of the user manual.
46
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.15 AcuCloud
Users can upload meter data to Accuenergy's free cloud based software called
AcuCloud. AcuCloud is a cloud-based facility metering platform that provides
users access to data from Accuenergy’s power meters, and is free for all Accuenergy meters.
To congure the AcuLink 810 to post data to AcuCloud, click on 'AcuCloud'
from left navigation panel under the 'CONFIGURATION' menu.
Users will need an AcuCloud account in order to add the AcuLink 810 as a device.
To create your AcuCloud account contact Accuenergy Technical Support.
If you already have an AcuCloud account, the following steps can be used to add
the gateway to AcuCloud.
V: 1.0 Revised: May. 2019
www.accuenergy.com
47
Chapter 6: AcuLink 810 User interface
• Login to your AcuCloud account with sucient access to add new devices.
Adding a new device to the Device List can be done from the Facilities page
• Click on the Devices tab
• Click on the + NEW DEVICE button.
The following details need to be entered:
• Select the name of the Facility in which the device will belong to from the Facility drop
down list.
• Select the AcuLink 810 from the Model drop down list.
• Select "This is a gateway Device"
• Provide a name for the device under Device Name.
• The Serial Number of the AcuLink 810 in the serial number eld.
48
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
NOTE: The serial number can be found and copied on the AcuCloud conguration page of
AcuLink 810 web interface.
• Provide a description for the location of the device under Location.
• Click SUBMIT.
Once the gateway has been successfully created, a token will be returned on the ensuing
page. The user will need to copy the token that is provided as it will be used in the next step
to congure the gateway to send its data to AcuCloud.
• Go back the AcuLink 810 web interface and paste the token that was generated into the
AcuCloud Token eld.
V: 1.0 Revised: May. 2019
www.accuenergy.com
49
Chapter 6: AcuLink 810 User interface
• Select the devices that need to be connected to Acucloud.
• Click Save
• Then click on 'Test Connection' to see if the AcuLink can reach the AcuCloud server.
NOTE: If the test connection fails, please check the network settings of the AcuLink
810 and if the token is entered correctly.
The AcuLink 810 gateway is now successfully congured to report to the AcuCloud
EMS software. Check to see if AcuCloud is receiving data from the gateway by going to
the Devices page in AcuCloud and observing whether the name of the selected devices from the gateway appear in AcuCloud with a Last Received Data timestamp.
If the gateway is oline or stops posting to the cloud, it will be backed up to the last
3000 posts. Once the meter reestablishes a connection to the cloud it will post the
les to AcuCloud. Users can remove or clear the back up posts at anytime by clicking
on the 'Clear AcuCloud Post Logs' button.
50
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.16 Data Management
You can manage the data logs directly from the user interface of the AcuLink 810. This page
allows the user to download or delete data from their Modbus devices.
6.16.1 Download Data
To download the Data Logs select the 'Download' tab under 'DATA MANAGEMENT' menu.
• Select Device: Select the device you wish to read the data from.
• From/To Date: Select the date and time frame to read the data log.
NOTE: Data Logs will only be recorded for the devices that have been selected in logger 1,2,3
or AcuCloud.
Click on 'Download' once all information is entered in correctly. The data will be down-
loaded as a .csv le to your computer directly.
NOTE: Depending on the amount of data stored this may take several minutes to complete
the data download.
Delete Data
To delete the Data Logs select the 'Delete' tab under 'DATA MANAGEMENT' menu.
Select Device: Choose the device you want to delete data for.
Once all the settings are entered in correctly, click on 'Delete Data Log'. All the data related
to the selected device will be deleted.
NOTE: Once data is deleted from the AcuLink 810 it cannot be undone.
V: 1.0 Revised: May. 2019
www.accuenergy.com
51
Chapter 6: AcuLink 810 User interface
6.16.2 Users Password
When users are logged in as an Admin they can change the password for both Admin and
Viewer access levels. Once the new password is entered click on 'Save'.
6.16.3 Firmware Update
The rmware of the AcuLink 810 can be updated from the 'Firmware' page under the 'CONFIGURATIONS' menu. This page lists the current rmware of the gateway.
The rmware update can be updated manually or remotely using the server.
52
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
Manual Firmware Update
To manually update the rmware of the AcuLink 810, click browse and upload the rmware
le. The le should have a .aup le extension.
Click on 'Upload' to begin uploading the rmware.
www.accuenergy.com
V: 1.0 Revised: May. 2019
53
Chapter 6: AcuLink 810 User interface
Once the rmware is uploaded, click on 'Start' to begin the updating process.
Once the rmware update is complete, the AcuLink 810 will restart.
Remote Firmware Update
The rmware of the AcuLink 810 can be updated using the remote rmware option. This will
allow users to check for the latest rmware updates. To use the remote rmware update click
on 'Check' which will verify if there is an update available or whether the gateway already has
the latest rmware.
54
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
NOTE: When updating the AcuLink 810 rmware remotely ensure that you have sucient
connection to the internet.
Click on 'Update' to begin downloading the rmware from the remote rmware server.
www.accuenergy.com
V: 1.0 Revised: May. 2019
55
Chapter 6: AcuLink 810 User interface
Once the download is complete the rmware update will begin.
After the rmware update is complete, the AcuLink 810 will restart.
56
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
6.17 Network Diagnostics
The AcuLink 810 has a network diagnostics page which can be used to monitor the network
status of the gateway.
In the Network Status tab users can see the Ethernet Network status, the routing table, DNS,
network stat, and the WIFI status.
NOTE: In order to see the WIFI network status the AcuLink 810 must be congured for Station
Mode.
www.accuenergy.com
V: 1.0 Revised: May. 2019
57
Chapter 6: AcuLink 810 User interface
In the 'Host Look Up' tab, users can use the ping function to test whether the AcuLink can
communicate over the network it is connected to.
Under the 'Connection Test' tab user can test the local network that the AcuLink is connected to. The test result will show SUCCESS and PASS if there is no issues found, and will show
FAIL if there are network issues.
58
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 6: AcuLink 810 User interface
On the 'Debug' tab, users can turn on or turn o SSH. From the debug page users can also
download the AcuLink 810's diagnostic le.
The debug diagnostic options are recommended to be all 'OFF' as this feature is mainly
used for troubleshooting and can aect the performance of the gateway if turned on.
V: 1.0 Revised: May. 2019
www.accuenergy.com
59
Chapter 6: AcuLink 810 User interface
The AcuLink 810's diagnostic le can be downloaded by the user from the Debug
page. If users are experiencing any issues with the gateway, the diagnostic le
can be sent to Accuenergy Technical Support for further analysis.
60
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 7: LED Description
7. LED Description
There are a total of 13 LEDs on the AcuLink 810 data acquisition server and each represent
dierent functions pertaining to the unit.
DATA ACQUSITION SERVER
With the exception of the blue power LED, the remaining LEDs can be divided into three
groups:
7.1 AcuMesh LEDs
The AcuMesh has a total of six LEDs which are related to the AcuMesh status.
• RSSI - There are three RSSI LEDs which indicate the signal strength of the incoming signal.
• ASSOC - Indicates that the transceiver is powered on or it is communicating. The Red
LED is 'ON' when powered, and briey 'ON' or ashing during RF transmission.
• RX - Indicates that the transceiver is receiving data.
• TX - Indicates that the transceiver is transmitting data.
V: 1.0 Revised: May. 2019
www.accuenergy.com
61
Chapter 7: LED Description
7.2 WiFi LEDs
The WiFi has a total of 3 LEDs which are related to the WiFi status.
• AP MODE - when 'ON' Indicates that the WiFi is working in Access Point Mode
• STATION MODE - when 'ON' indicates that the WiFi is working in Station Mode
• STATUS - When 'ON' indicates that the WiFi is working and functioning properly.
7.3 RS485 LEDs
The RS485 has a total of 3 LEDs which are related to the RS485 status.
• COMM OK - When 'ON' indicates that all RS485 and USB devices in RS485 network are
online and is represented by a green LED.
• COMM ISSUE - When 'ON' indicates that some of the devices in the RS485 network are
oline and is represented by a yellow LED
• NO COMM - When 'ON' indicates that all RS485 devices in the RS485 network are of-
ine and is represented by a red LED
62
V: 1.0 Revised: May. 2019
www.accuenergy.com
Chapter 8: Reset Button
Reset Button
8. Reset Button
On the AcuLink 810 unit there is a reset button located on the back of the unit where the
Ethernet and USB ports are. The reset button resets the AcuLink 810 back to default meaning that all devices, data logs, alarm/event log, and device templates will be deleted. The
only Device Template that will remain after the reset is the Modbus Gateway Function, however all other Modbus templates will be removed.
After the reset all network communications will be restored back to default meaning the AcuLink will have the following network settings after the reset:
• WIFI Mode - Access Point (AP) mode
• Ethernet 1 - 192.168.8.101
• Ethernet 2 - DHCP enabled
To successfully perform a reset on the AcuLink 810 gateway press and hold the reset button
for 10 seconds until all LED lights on the unit are ashing. The reset will be complete when
the LED lights stop ashing.
www.accuenergy.com
DATA ACQUSITION SERVER
V: 1.0 Revised: May. 2019
63
MAKE ENERGY USAGE SMARTER