Accoutrements LO-BOY INSTALLATION INSTRUCTIONS

MANUAL 2100-103B
INSTALLATION INSTRUCTIONS
LO-BOY
HIGH ECONOMY GAS FURNACE
APPLICATION
This is a forced air gas furnace for installation in building constructed on site. The furnace installation must conform with local building codes and ordinances or, in their absence with
the National Fuel Cas Code, ANSI Z323.1-19B0, and the National Electrical Code, ANSI/NFPA 70-1981. It is the personal responsibility and obligation of the purchaser to contract a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.
HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on зш level operation and need not be changed for operation at elevations up to 2, QOQ feet. For operation at elevations above 2,000 feet and, in the absence of specific recommendations from the local authority having jurisdiction, equipment ratings shall be
reduced at the rate of 4 percent for each 1,000 feet above sea level before selecting appropriately sized equipment. (Ref. ANSI Z223. 1-1980, Par, 8.12).
TRANSPORTATION DAMAGE All units are packed securely in shipping container. All units
should be carefully inspected upon arrival for damage. In the
event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly and request an inspection.
3. in case of concealed damage, the carrier must be notified as soon as possible within IS days after delivery.
4. Claims for any damage, apparent or concealed, should be filed with the carrier, using the following supporting documents, and within the 9-month statute of limitations.
a) Original Bill of Lading, certified copy, or indemnity
bond.
b) Original paid freight bill of indemnity in lieu thereof.
c) Original invoice or certified copy thereof showing trade
and other discounts or deductions.
d) Copy of the inspection report issued by carrier's
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim.
LOCATING THE FURNACE When selecting a location for the furnace, observe the
following points:
1. The furnace should be sat on a level floor. The IL-$eries Lo-Boy furnaces are shipped raised one inch above the floor to accommodate a damp or wet floor. If greater amounts of water are present at times, the furnace may be elevated further using a concrete base, bricks, patio blocks, etc., nuking sure adequate support is available for the furnace. Furnaces approved for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
figure 1. MINIMUM CLEARANCES (INCHES)
MINIMUM INSTALLATION CLEARANCES
Front
Model
IL8S042A IL85042C
IL11504aA IL115048C
IL14506QA IL14SD60C
* Clearance may be 1 inch when Type B-1 vent is used. + Clearance may be 0 inch when Type B-1 vent is used. C Floor may be combustible material.
Top
1
1
1 6
6 6*
6 6*
Minimum clearance at least one side for access to rear of furnace.
Vent
6*
Back
0
0 0 0
0
2. The furnace should be as centralized as practical with respect to the air distribution system.
3. Provisions must bo made for venting combustion products
outdoors through an individual venting system.
4. Provide at least the minimum clearances specified in Figure 1 for fire protection, proper operation and service access.
These clearances must be permanently maintained. The combustion and ventilating air openings in the front of the furnace must never be obstructed.
5. Minimum service clearances must take precedence over fire
protection clearances (minimum installation clearances).
6. All models are approved for a utility room or closet
installation.
7. A gas-flred furnace installed in a residential garage must
be installed so that the burners and ignition source are located not less than 18 inches above the floor, and the furnace must be located or protected to avoid physical damage by vehicles.
8. For installation in a manufactured building the furnace
should be anchored to the floor and attached to any adjacent structural members by screwing support brackets to the back or sides of the furnace with 1/2” sheet metal screws.
DUCT WORK
The air distribution systrnn should be designed and installed in conformance with Manuals 7 or 7A published by Air Conditioning Contractors of America (ACCA), as set forth in their Manual K.
CAUTION-
When i furnace Is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return atr must also be handled by a duct(s) sailed to the furnace casing and terminating outside the space containing the furnace. This is to prevent drawing possible hazardous combustion products to the circulated air.
When the furnace is used in connection with a cooling unit*, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to
prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit, unless the damper is in the full heat or cool position.
*A cooling unit is sn air conditioning coil, heat pump coil or chilled water coil.
MINIMUM SERVICE CLEARANCE
Left
Side
0 1^ C
0
Right
Side Floor
c
0 c
Front Sides
24
24
24 18 (Î)
ie®
18 Ф
Back
24
24
24
COMBUSTION AND VENTILATION AIR The furnace and furnace room must have an adequate supply
of air for safe combustion and ventilation. The provisions necessary to assure an adequate air supply will vary depending upon differences in the tightness of house construction and in the location of the furnace. Methods of providing air from some typical situations are described below. Consult local codes and ordinances for requirements applicable to your specific furnace installation conditions and comply with them. In the absence of local codes and ordinances, comply with the National Fuat Gas Code, ANSI Z223.1-19B0.
EXAMPLE I - FURNACE LOCATED IN AN UNCONFINED SPACE A. If the furnace is located in a basement or other large,
open area of a conventionally built house (loose construction), the air that leaks into the building normally
will provide an adequate air supply.
B. If the furnace is located in a tightly constructed building
(storm windows, weather stripping, cracks caulked, etc.)
an outdoor air intake must be provided. Example 2,
Section B, shows a typical method.
EXAMPLE 2 - FURNACE LOCATED IN A CONFINED SPACE
A. When the furnace is in a closet or utility room, install two
open grilles In a wall or door opening to the rest of the house. One square inch for each 1000 Btu/h of total input
rating of all gas appliances in the confined space. Refer to Figure ~T, The grilles must communicate with other open
areas having adequate air infiltration from outdoors.
If the building is tightly constructed, not enough outside
air may enter for safe combustion. Install a fresh air duct
from a point near the burners to the outside or to a ventilated attic or crawl space. Refer to Figure 3. This duct must have a free area of at least one square inch for each 4,000 Btu/h of total Input of aii gas appliances in the space. The minimum dimension of a rectangular duct must not be lass than three inches.
CAUTION: WHEN A FURNACE IS INSTALLED IN A CLOSET
FIGURE 2 — FURNACE LOCATED IN CONFINED SPACE
OR UTILITY ROOM, NEVER USE THIS ROOM AS A
RETURN AIR PLENUM.
FIGURE 3 — FRESH AIR DUCT FOR TIGHTLY SEALED
This furnace must be vented directly to the outside through a
suitable chimney. This furnace as shipped from the factory is
suitable for a ^dicated flue only. It should not be vented and
terminated horizontally through a side wall and Is not suitable
for use with plastic pip*- tffth"^'the " addition of optional
field-in stalled Common voting Kit 8620-005 or -006, it is
suitable to common vent thia furnace along with another gas
burning appliance to a single chimney for eese of installation.
Refer to section on Comann Venting beginning on page 11 of
this instruction manual for complete details. The vent must be
installed in compliance with the National Fuel Gas Coda (ANSI
Standard Z223. 1-1980, ] and these instructions.
BUILDING
GENERAL INSTRUCTIONS
1. The vent connector must be aluminum pipe and shall be the same siia as the flue outlet on the furnace. Keep the vent as short and direct as possible. Type B-1 pipe is recommended.
2. Maintain a minimum clearance of 6" (1" for B-1) to any portion of the vent connector from any adjacent combustible materials. Single wall vent connector is permitted only within the same space (room or area] at the furnace. B-1 vent is required whenever the vent is enclosed or passes through floors, walls, ceilings, roofs or furred-out spaces. Joists, studs, floors, dry wall, paneling, sheeting, rafters, roofing and other matcriais classified as combustibia must not be closer than 1“ clearance to the B-1 vent.
3. If connected into masonry chimney, the vent pipe must be inserted into, but not beyond the inside wall of the chimney.
4. The gas vent must extend at least 2 feet above the highest point where it passes through the roof of a building (3 feet for a chimnay] and at least 1 foot hlghar than any portion of a building within a horizontal distance of 10 feet. See Figure 4.
5. The vent pipe system shall be installed so as to avoid excessive turns which create unnecessary resistance to flow of vent gases.
fi.
Horizontal runs shall be as short and direct as possible. The maximum length of a single-wall vent pipe shall not exceed 75 percent of the height of the vent system. The maximum length of a Type B-1 double wall flue connection shall not exceed 100 percent of the height of the vent system.
7.
All horizontal vent pipe shall be pitched upward from the furnace at least 1/4 inch per foot.
8.
All vent systems shall be adequately supported to maintain proper clearances, to prevent physical damage, and to prevent separation to joints.
9.
Vents passing through an exterior combustible wall must use a ventilated wall thimble. See Figure 5.
10.
Vents passing through floors or ceilings must fire-stopped. See Figure 6 and Figure 7.
GAS SUPPLY AND PIPING
general recommendations
1. Be sure the gas line complies with the local codes and ordinances, or in their absence with National Fuel Gas Code, ANSI Z223.1-1980.
2. A sediment trap or drip leg must be installed in the supply line to the furnace.
3. A ground joint union shall be installed in the gas line adjacent to and upstream from the gas valve and downstream from the manual main shut off valve.
4. A 1/8” N.P.T. plugged tapping accessible for test gauge connection shall be Installed immediately upstream of the gas supply connection to the furnace for the purpose of determining the supply gas pressure.
5. A manual shut-off valve shall be installed in the supply gas line external to the furnace (see Figure 9 and 10).
6. Use steel or wrought iron pipe and fittings.
7. DO NOT thread pipe too far. Valve distortion or malfunction may result from excess pipe within the control. Use pipe joint compound resistant to the action of Liquified
Petroleum gases on male threads only. DO NOT use Teflon
tape. See illustrations below.
FIGURE 8 — GAS PIPE SIZES — NATURAL GAS
Length of Pipe, Ft.
10 132,000 20
30 40
50 60 50,000
70 80
be
too
Pipe Capacity — Btuh Per Hour
Input Pipe Size
1/2" 3/4“
92,000 73,000
63,000 56,000
46,000 96,000 43,000
38,000
278,000 520, 000 190,000 152,000
130,000 115,000 105,000
90,000 79,000
1"
350,000
285,000 245,000
215,000 195,000
180,000 170,000 150,000 305,000
1-1/4"
1,050,000
730,000 590,000
500,000
440,000
400,000 370,000
350,000
LEKGTH OF STANDARD PIPE THREADS (Indus)
PIPE SIZE
EFFECTIVE
LENGTH
OVERALL
LENGTH
OF THREAD OF THREAD
3/8
1/2
3/4
1
3/8 1/2
1/2-9/18
9/16
9/16
3/4
13/16
1
Ua£UCa!££E±SZ!£l
ThITaOS*^^ COWTgpL use moospats amount or oors
THREAD rirc aiOHT CCNGTH bXAVf I SNO THNSADS SAfIS
8. Refer to Figure 8 for Gas Pipe sizes for natural gas. If more than one appliance Is supplied from a single line size, capacity must equal or axcaed the combinad input to all appliances, and the branch lines feeding the individual appliances properly sized for eech input.
CHECKING THE GAS PIPING Before turning gas under pressure into piping, all openings
from which gas can eacape should be closed. IMMEDIATELY AFTER TURNING ON GAS, the system should be checked for leaks. This can be done by watching the 1/2 cubic foot test dial and allowing S minutes to show any movement, and by
soaping each pipe connection and watching for bubbles. If a
leek is found, make the necessary repairs immediately and
repeat the above test. The furnace must be isolated from the gas supply piping system by closing the manual shutoff valve on the combination gas control valve during pressure testing of the gas supply piping system at pressures up to 1/2 psig. The furnace must be disconnected from supply piping and
supply piping capped during sny pressure testing of supply piping system at test pressures in excess of 1/2 psig.
Defective pipes or fittings should be replaced and not
repeirad. NEVER USE A FLAME OR FIRE IN ANY FORM TO
LOCATE CAS LEAKS, USE A SOAP SOLUTION.
FIG, A — CHIMNEY OR VENT CAP INSTALLATION
2 Ft. itiintnuin if япу portion of building
Clearance may be 1 inch when Type B-I vent
A
is used.
FIG, S — VENT THBODGH FLOOR
FIG. 7 — VENT THROUGH CEILING
Loading...
+ 9 hidden pages