This is a forced air gas furnace for installation in building
constructed on site. The furnace installation must conform with
local building codes and ordinances or, in their absence with
the National Fuel Cas Code, ANSI Z323.1-19B0, and the
National Electrical Code, ANSI/NFPA 70-1981. It is the
personal responsibility and obligation of the purchaser to
contract a qualified installer to assure that installation is
adequate and is in conformance with governing codes and
ordinances.
HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on зш level
operation and need not be changed for operation at elevations
up to 2, QOQ feet. For operation at elevations above 2,000 feet
and, in the absence of specific recommendations from the local
authority having jurisdiction, equipment ratings shall be
reduced at the rate of 4 percent for each 1,000 feet above sea
level before selecting appropriately sized equipment. (Ref.
ANSI Z223. 1-1980, Par, 8.12).
TRANSPORTATION DAMAGE
All units are packed securely in shipping container. All units
should be carefully inspected upon arrival for damage. In the
event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly and request an inspection.
3. in case of concealed damage, the carrier must be notified
as soon as possible within IS days after delivery.
4. Claims for any damage, apparent or concealed, should be
filed with the carrier, using the following supporting
documents, and within the 9-month statute of limitations.
a) Original Bill of Lading, certified copy, or indemnity
bond.
b) Original paid freight bill of indemnity in lieu thereof.
c) Original invoice or certified copy thereof showing trade
and other discounts or deductions.
d) Copy of the inspection report issued by carrier's
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
LOCATING THE FURNACE
When selecting a location for the furnace, observe the
following points:
1. The furnace should be sat on a level floor. The IL-$eries
Lo-Boy furnaces are shipped raised one inch above the
floor to accommodate a damp or wet floor. If greater
amounts of water are present at times, the furnace may be
elevated further using a concrete base, bricks, patio
blocks, etc., nuking sure adequate support is available for
the furnace. Furnaces approved for installation on
combustible flooring shall not be installed directly on
carpeting, tile or other combustible material other than
wood flooring.
figure 1. MINIMUM CLEARANCES (INCHES)
MINIMUM INSTALLATION CLEARANCES
Front
Model
IL8S042A
IL85042C
IL11504aA
IL115048C
IL14506QA
IL14SD60C
* Clearance may be 1 inch when Type B-1 vent is used.
+ Clearance may be 0 inch when Type B-1 vent is used.
C Floor may be combustible material.
Top
1
1
16
66*
66*
Minimum clearance at least one side for access to rear of furnace.
Vent
6*
Back
0
000
0
2. The furnace should be as centralized as practical with
respect to the air distribution system.
3. Provisions must bo made for venting combustion products
outdoors through an individual venting system.
4. Provide at least the minimum clearances specified in Figure
1 for fire protection, proper operation and service access.
These clearances must be permanently maintained. The
combustion and ventilating air openings in the front of the
furnace must never be obstructed.
5. Minimum service clearances must take precedence over fire
6. All models are approved for a utility room or closet
installation.
7. A gas-flred furnace installed in a residential garage must
be installed so that the burners and ignition source are
located not less than 18 inches above the floor, and the
furnace must be located or protected to avoid physical
damage by vehicles.
8. For installation in a manufactured building the furnace
should be anchored to the floor and attached to any
adjacent structural members by screwing support brackets
to the back or sides of the furnace with 1/2” sheet metal
screws.
DUCT WORK
The air distribution systrnn should be designed and installed in
conformance with Manuals 7 or 7A published by Air
Conditioning Contractors of America (ACCA), as set forth in
their Manual K.
CAUTION-
When i furnace Is installed so that supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return atr
must also be handled by a duct(s) sailed to the
furnace casing and terminating outside the space
containing the furnace. This is to prevent drawing
possible hazardous combustion products to the
circulated air.
When the furnace is used in connection with a cooling unit*,
the furnace shall be installed parallel with or on the upstream
side of the cooling unit to avoid condensation in the heating
element. With a parallel flow arrangement, the dampers or
other means used to control flow of air shall be adequate to
prevent chilled air from entering the furnace and, if manually
operated, must be equipped with means to prevent operation of
either unit, unless the damper is in the full heat or cool
position.
*A cooling unit is sn air conditioning coil, heat pump coil or
chilled water coil.
MINIMUM SERVICE CLEARANCE
Left
Side
01^C
0
Right
SideFloor
c
0c
FrontSides
24
24
2418 (Î)
ie®
18 Ф
Back
24
24
24
COMBUSTION AND VENTILATION AIR
The furnace and furnace room must have an adequate supply
of air for safe combustion and ventilation. The provisions
necessary to assure an adequate air supply will vary
depending upon differences in the tightness of house
construction and in the location of the furnace. Methods of
providing air from some typical situations are described below.
Consult local codes and ordinances for requirements applicable
to your specific furnace installation conditions and comply with
them. In the absence of local codes and ordinances, comply
with the National Fuat Gas Code, ANSI Z223.1-19B0.
EXAMPLE I - FURNACE LOCATED IN AN UNCONFINED SPACE
A. If the furnace is located in a basement or other large,
open area of a conventionally built house (loose
construction), the air that leaks into the building normally
will provide an adequate air supply.
B. If the furnace is located in a tightly constructed building
an outdoor air intake must be provided. Example 2,
Section B, shows a typical method.
EXAMPLE 2 - FURNACE LOCATED IN A CONFINED SPACE
A. When the furnace is in a closet or utility room, install two
open grilles In a wall or door opening to the rest of the
house. One square inch for each 1000 Btu/h of total input
rating of all gas appliances in the confined space. Refer to
Figure ~T, The grilles must communicate with other open
areas having adequate air infiltration from outdoors.
If the building is tightly constructed, not enough outside
air may enter for safe combustion. Install a fresh air duct
from a point near the burners to the outside or to a
ventilated attic or crawl space. Refer to Figure 3. This
duct must have a free area of at least one square inch for
each 4,000 Btu/h of total Input of aii gas appliances in the
space. The minimum dimension of a rectangular duct must
not be lass than three inches.
CAUTION: WHEN A FURNACE IS INSTALLED IN A CLOSET
FIGURE 2 — FURNACE LOCATED IN CONFINED SPACE
OR UTILITY ROOM, NEVER USE THIS ROOM AS A
RETURN AIR PLENUM.
FIGURE 3 — FRESH AIR DUCT FOR TIGHTLY SEALED
This furnace must be vented directly to the outside through a
suitable chimney. This furnace as shipped from the factory is
suitable for a ^dicated flue only. It should not be vented and
terminated horizontally through a side wall and Is not suitable
for use with plastic pip*- tffth"^'the " addition of optional
field-in stalled Common voting Kit 8620-005 or -006, it is
suitable to common vent thia furnace along with another gas
burning appliance to a single chimney for eese of installation.
Refer to section on Comann Venting beginning on page 11 of
this instruction manual for complete details. The vent must be
installed in compliance with the National Fuel Gas Coda (ANSI
Standard Z223. 1-1980, ] and these instructions.
BUILDING
GENERAL INSTRUCTIONS
1. The vent connector must be aluminum pipe and shall be
the same siia as the flue outlet on the furnace. Keep the
vent as short and direct as possible. Type B-1 pipe is
recommended.
2. Maintain a minimum clearance of 6" (1" for B-1) to any
portion of the vent connector from any adjacent
combustible materials. Single wall vent connector is
permitted only within the same space (room or area] at the
furnace. B-1 vent is required whenever the vent is
enclosed or passes through floors, walls, ceilings, roofs or
furred-out spaces. Joists, studs, floors, dry wall,
paneling, sheeting, rafters, roofing and other matcriais
classified as combustibia must not be closer than 1“
clearance to the B-1 vent.
3. If connected into masonry chimney, the vent pipe must be
inserted into, but not beyond the inside wall of the
chimney.
4. The gas vent must extend at least 2 feet above the highest
point where it passes through the roof of a building (3
feet for a chimnay] and at least 1 foot hlghar than any
portion of a building within a horizontal distance of 10
feet. See Figure 4.
5. The vent pipe system shall be installed so as to avoid
excessive turns which create unnecessary resistance to
flow of vent gases.
fi.
Horizontal runs shall be as short and direct as possible.
The maximum length of a single-wall vent pipe shall not
exceed 75 percent of the height of the vent system. The
maximum length of a Type B-1 double wall flue connection
shall not exceed 100 percent of the height of the vent
system.
7.
All horizontal vent pipe shall be pitched upward from the
furnace at least 1/4 inch per foot.
8.
All vent systems shall be adequately supported to maintain
proper clearances, to prevent physical damage, and to
prevent separation to joints.
9.
Vents passing through an exterior combustible wall must
use a ventilated wall thimble. See Figure 5.
10.
Vents passing through floors or ceilings must
fire-stopped. See Figure 6 and Figure 7.
GAS SUPPLY AND PIPING
generalrecommendations
1. Be sure the gas line complies with the local codes and
ordinances, or in their absence with National Fuel Gas
Code, ANSI Z223.1-1980.
2. A sediment trap or drip leg must be installed in the
supply line to the furnace.
3. A ground joint union shall be installed in the gas line
adjacent to and upstream from the gas valve and
downstream from the manual main shut off valve.
4. A 1/8” N.P.T. plugged tapping accessible for test gauge
connection shall be Installed immediately upstream of the
gas supply connection to the furnace for the purpose of
determining the supply gas pressure.
5. A manual shut-off valve shall be installed in the supply
gas line external to the furnace (see Figure 9 and 10).
6. Use steel or wrought iron pipe and fittings.
7. DO NOT thread pipe too far. Valve distortion or
malfunction may result from excess pipe within the control.
Use pipe joint compound resistant to the action of Liquified
Petroleum gases on male threads only. DO NOT use Teflon
tape. See illustrations below.
FIGURE 8 — GAS PIPE SIZES — NATURAL GAS
Length of
Pipe, Ft.
10132,000
20
30
40
50
6050,000
70
80
be
too
Pipe Capacity — Btuh Per Hour
Input Pipe Size
1/2"3/4“
92,000
73,000
63,000
56,000
46,00096,000
43,000
38,000
278,000520, 000
190,000
152,000
130,000
115,000
105,000
90,000
79,000
1"
350,000
285,000
245,000
215,000
195,000
180,000
170,000
150,000305,000
1-1/4"
1,050,000
730,000
590,000
500,000
440,000
400,000
370,000
350,000
LEKGTH OF STANDARD PIPE THREADS (Indus)
PIPE SIZE
EFFECTIVE
LENGTH
OVERALL
LENGTH
OF THREADOF THREAD
3/8
1/2
3/4
1
3/8
1/2
1/2-9/18
9/16
9/16
3/4
13/16
1
Ua£UCa!££E±SZ!£l
ThITaOS*^^ COWTgpL use moospatsamount or oors
THREAD rirc aiOHT CCNGTH bXAVf I SNO THNSADS SAfIS
8. Refer to Figure 8 for Gas Pipe sizes for natural gas. If
more than one appliance Is supplied from a single line size,
capacity must equal or axcaed the combinad input to all
appliances, and the branch lines feeding the individual
appliances properly sized for eech input.
CHECKING THE GAS PIPING
Before turning gas under pressure into piping, all openings
from which gas can eacape should be closed. IMMEDIATELY
AFTER TURNING ON GAS, the system should be checked for
leaks. This can be done by watching the 1/2 cubic foot test
dial and allowing S minutes to show any movement, and by
soaping each pipe connection and watching for bubbles. If a
leek is found, make the necessary repairs immediately and
repeat the above test. The furnace must be isolated from the
gas supply piping system by closing the manual shutoff valve
on the combination gas control valve during pressure testing
of the gas supply piping system at pressures up to 1/2 psig.
The furnace must be disconnected from supply piping and
supply piping capped during sny pressure testing of supply
piping system at test pressures in excess of 1/2 psig.
Defective pipes or fittings should be replaced and not
repeirad. NEVER USE A FLAME OR FIRE IN ANY FORM TO
LOCATE CAS LEAKS, USE A SOAP SOLUTION.
FIG, A — CHIMNEY OR VENT CAP INSTALLATION
2 Ft. itiintnuin if япу
portion of building
Clearance may be 1 inch when Type B-I vent
A
is used.
FIG, S — VENT THBODGH FLOOR
FIG. 7 — VENT THROUGH CEILING
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.