This manual should be passed on to the end user.
The contents of this manual are subject to change without prior notice.
All rights reserved.
ABUS gives no warranty of any kind with regard to this manual, including, but not limited to, fitness
for a particular purpose.
If any question arises or errors are found, or if any information is missing from this manual, please
UI
inform your supplier or inform at info@abustek.com
The specifications mentioned in this manual are limited to those for the standard type under the
specified model number break-down and do not necessarily apply for customized instruments.
Please note that changes in the specifications, construction, or component parts of the instrument
may not immediately be reflected in this manual at the time of change.
If the customer or any third party is harmed by the use of this product, ABUS assumes no
responsibility for any such harm owing to any defects in the product which were not predictable, or
for any indirect damages.
Although Warning hazards are related to personal injury, and Caution hazards are associated
with equipment or property damage, it must be understood that operation of damaged equipment could,
under certain operational conditions, result in degraded process system performance leading to
personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of
our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are
not to be reproduced in full or part without prior approval of Technical Communications Department,
ABUS Technologies
.
HEALTH AND SAFETY
To ensure that our products are safe and without risk to health, the following points must be
noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained
personnel and in accordance with the information given. Any deviation from these instructions will
transfer the complete liability to the user.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when
operating in conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept
dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data
sheets (where applicable) may be obtained from the Company address on the back cover, together with
servicing and spares information.
ABUS TECHNOLOGIES INC.
2
UI
.
CATALOGUE
Contents Page No.
1. Introduction
Applications
2. Presentation
1. Features
2.
3. Dimensions 5
4. Ordering Details 5
5. Connections 6
6. Installation
1. Input Signal
2.
7. Configuration
1. Configuration Process
2.
8. Operation
Example for Usage
9. Maintenance
Troubleshooting
10. Safety Precautions 10
Technical Parameters
Panel
Key Operation Instructions
4
4
4
4
4
6
6
6
8
8
9
9
9
9
9
11. Warranty 10
ABUS TECHNOLOGIES INC.
3
1. INTRODUCTION
UI series of universal process indicator is a high performance indicator that can
be used to monitor wide range of input signal. The various input signals could easily
be selected from the front keypad without any change in Hardware. The Standard
model comes with 2-alarms, 24V auxiliary power supply for transmitter and analogue
retransmission 4 ~ 20 mA DC output. The unit features double display for indication of
process value and programming data. The large and bright PV display, robustness of
product makes the product suitable for industrial applications. The retransmission
output could be taken to PLC, recorder and other applications, for other functions. RS485 or RS-232 communication is also optionally available.
Applications
The instrument can measure and display any range of Current, Voltage and temperature
through RTD-Pt 100 signal input. The user can select data hold or high PV hold. The instrument can be
used with 2-wire Differential Pressure Transmitter, Pressure Transmitter, Temperature Transmitter,
Temperature Sensor or any other industrial process parameters (for non-linear input). RS485
communication is also optionally available. The input, output and the power supply are isolated.
2. PRESENTATION
2.1 Features
1. Input mA, V, Pt100(T/C Optional) selected by software via Front Panel.
2. Measuring range / Zero point can be adjusted.
3. Up to 3 relay alarm available. Capacity: AC 250V/3A or 30V/3A
4. With isolated RETRANSMISSION analogue output 0-10mA, 4-20mA or 0-10V.
5. Decimal point shift is programmable.
6. Retransmission output can be scaled between USP and LSP.
7. Auxiliary Power Supply/ Transmitter Power Supply: 24V/12V, max.DC30mA.
8. With RS232 or RS485 communication, MODBUS RTU Protocol.
9. Accuracy: ±0.25% FS(Optional).
2.2 Technical Parameters
Power Supply: 90-260V AC or 18-30V AC/DC
UI
Consumption: ≤ 5VA
Accuracy: 0.25 % F.S. ± 1 Digit
Sampling Rate: ≤ 8 times/second
Retransmission Output: 4~20 mA or 0~10 V
Alarm: Up to 3 Relay alarms Capacity AC 250V/3A or DC 30 V/3A
Input: Refer to the Input Signal Table 6.1
Auxiliary Power: DC 12/24/30 mA
Communication: Rs232 or Rs485, MODBUS RTU Protocol Optional
ABUS TECHNOLOGIES INC.
4
3. DIMENSIONS
UI
4. ORDERING DETAILS
TYPE DESCRIPTION
Product
Power Supply
Analogue
AL1
AL2
Communication
Auxiliary Power
Supply
Panel Size
UI UI Series of Process Indicator
D
N
E DC 24 V
V 0~10 V
D DC 4~20 mA (Default)
R
R
N
Example: UI > D > D > R > R > N > B > 48
All Dimensions in mm
AC 90~260 V 50/60 Hz (Default)
DC 0~10 mA
Relay
S SSR / LOGIC
T SCR
N No Alarm
96 Optional 96 x 96 cutout.
Relay
S SSR / LOGIC
T SCR
N No Alarm
No Communication
2 RS-232
4 RS-485
A
B DC +24 V / 30mA
48 Standard 48 x 96 cutout.
DC +12 V / 30 mA
ABUS TECHNOLOGIES INC.
5
5. CONNECTIONS
UI
Note: For Changes refer to the label on the product
6. INSTALLATION
6.1 Input Signal
INPUT
SIGNAL
mA
V(AV/DV) 0~5V, 0~10V, 0~500V ≤ 200 K Ω DC 0~10V
Pt -200~650˚C ≤ 0.2 mA Pt100
mV 0~10 mV, ±100mV ≤ 2 M Ω 0~75mV
Rt
MEASURING
RANGE
0~1 mA 0~10 mA,
4~20mA
0~400 Ω, 0~10K
Cu50 Cu100 -50~150˚C
INPUT
IMPEDANCE
≤ 150 Ω 4~20mA
≤ 0.2 mA 0~400 Ω
DEFAULT
SETTING
STANDARD
Pr 20 Non-linear Input
1. The factory setting of the input is 4-20mA, 0-10V and Pt. In case of requirement of any
other input signal such as 0-4000hm, Pt100, please contact the manufacturer or your local
ABUS distributors.
2. High Voltage/Current input function needs special order.
3. Analogue output can also be used as Al3, but you can select only one of them, but not
both.
4. Non-Linear input needs special order.
ABUS TECHNOLOGIES INC.
6
6.2 Panel
UI
Panel Attributes
S.No. Parameters Description
1 LED Measured value (PV).
2 LED Programming Display (SV).
3 AL1
4 AL2
5 OUT Select / Confirm key / Analogue Output.
6 SET Set Key (Press SET key for 5 seconds to enter programming mode).
7 «/Rst Shift / Clear / Reset key
8
9
Indication lamps for Alarm 1- On: Output Off: No Alarm
Indication lamps for Alarm 2- On: Output Off: No Alarm
Up Key
Down Key
ABUS TECHNOLOGIES INC.
7
7. CONFIGURATION
7.1 Configuration Process
UI
ABUS TECHNOLOGIES INC.
8
7.2 Key Operation Instructions
1. Alarm setting: In the powered state press and hold SET key for more than 3 seconds, enter alarm
mode parameters setting menu. Press
2. <</RST Key, LEDflashes, press <</RST key to modify, and them press SET key to confirm. Press
SET key to read the following parameters one by one.
3. Rate setting: In powered state, press <</RST key and LED flashes, then you can modify the value
by Up and Down key. The factory setting is 1.00. Once the user want to set it to be other value.
then PV=Rate X (USP-LSP)+LSP. USP means Up limit, LSP means Down limits.
4. Zero point clear: In the displaying estate. without key operation, when the input zero point, press
and hold <</RST key for more than 2 seconds. It is for the sensor zero point clear.
5. The instrument will return to the measuring estate without any operation for 25 seconds.
8. OPERATION
Example for Usage
Used with 2 wire transmitter. The instrument can supply DC 24V auxiliary power and isolate
analogue output 4~20mA. Select input signal mA.
UI
9. MAINTENANCE
Troubleshooting
S. No. SPECIFICATIONS
1 No display
2 Wrong display
3 Wrong control
4 UUUU, LLLL
ELIMINATE
Check all the connections and wiring to ensure them
being correct. Thoroughly check connections to power
supply terminals and signal input terminals.
Check if the PVF= 0.00 Check if the input signal is
conformity with the selected symbol.
In case instrument looses the control, check for the
output diagram connection is correct or check if the
components for output part are damaged.
When the instrument displays "UUUU", it means the
input signal exceeds the measured USP range. When
the instrument displays "LLLL, it means the input signal
exceeds the measured USP range. When the instrument
displays "LLLL", it means the input signal lower
measured LSP range, or input signal terminal
connection is contrary.
ABUS TECHNOLOGIES INC.
9
10. SAFETY PRECAUTIONS
1. The unit should be powered for 15 minutes before use.
2. Use in ambient temperature of 0-60˚C.
3. Avoid vibrations, shock, excessive dust, corrosive chemical materials or gaseous
environment.
4. Input wire should not be too long. If measured signal have to be far away from the
unit, please use 2-core shielded cable.
5. Use this instrument in the scope of its specifications, otherwise fire or malfunctions
may result.
6. Contact of the instrument, with organic solvents or oils should be avoided.
UI
7. Do not turn on the power supply until all of the wiring is completed. Otherwise
electrical shock, fire or malfunction may result.
8. Do not disassemble, repair or modify the instrument.
9. All connections should be tightened properly.
10. Power supply should be constant, should not be fluctuating.
11. WARRANTY
ABUS provides the original purchaser of this instrument a one (1) year warranty
against defects in material and workmanship under the following terms:
The one year warranty begins on the day of shipment as stated on the sales bill.
During the warranty period all costs of material and labor will be free of charge
provided that the instrument does not show any evidence of misuse.
For maintenance, return the instrument with a copy of the sales bill to our factory.
All transportation and insurance costs should be covered by the owner of the
equipment.
Should any sign of electrical or mechanical shock, abuse, bad handling or misuse
be evident the warranty voids and maintenance costs will be charged.
ABUS TECHNOLOGIES INC.
www.abustek.com, E-M ail: info@abustek.com
ABUS TECHNOLOGIES INC.
10