This manual should be passed on to the end user.
The contents of this manual are subject to change without prior notice.
All rights reserved.
ABUS gives no warranty of any kind with regard to this manual, including, but not limited to, fitness
for a particular purpose.
If any question arises or errors are found, or if any information is missing from this manual, please
Field
Logger
inform your supplier or inform at info@abustek.com
The specifications mentioned in this manual are limited to those for the standard type under the
specified model number break-down and do not necessarily apply for customized instruments.
Please note that changes in the specifications, construction, or component parts of the instrument
may not immediately be reflected in this manual at the time of change.
If the customer or any third party is harmed by the use of this product, ABUS assumes no
responsibility for any such harm owing to any defects in the product which were not predictable, or
for any indirect damages.
Although Warning hazards are related to personal injury, and Caution hazards are associated
with equipment or property damage, it must be understood that operation of damaged equipment could,
under certain operational conditions, result in degraded process system performance leading to
personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of
our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are
not to be reproduced in full or part without prior approval of Technical Communications Department,
ABUS Technologies
.
HEALTH AND SAFETY
To ensure that our products are safe and without risk to health, the following points must be
noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained
personnel and in accordance with the information given. Any deviation from these instructions will
transfer the complete liability to the user.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when
operating in conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept
dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant
hazard data sheets (where applicable) may be obtained from the Company address on the back cover,
together with servicing and spares information.
ABUS TECHNOLOGIES INC.
2
Field
Logger
CATALOGUE
Contents Page No.
1. Introduction 4
2. Presentation
Technical Parameters
3. Dimensions 5
4. Ordering Details 5
5. Connections
Analogue Input
6. Installation
1. Input Signal
2.
7. Configuration
1. Communication Page
2. Channels Page
3. Acquisitions Page
4. Diagnosis Page
5.
8. Operation
Data Logging
9. Safety Precautions 16
Alarm
Serial Communication
4
4
6
6
7
7
7
8
8
9
10
12
13
15
15
10. Warranty 16
ABUS TECHNOLOGIES INC.
3
1. INTRODUCTION
The Field Logger is versatile data acquisition equipment for process variables,
capable of on-line or stand alone operation. When loaded with a Real Time Clock and
non-volatile memory, it can register up to 128k readings. Its universal input channels
accept a large variety of sensors and standard signals as listed in table Field Logger
Input Signals, below.
A Configuration program (Windows 95, 98 or NT) is provided for an easy
configuration of all the internal parameters.
2. PRESENTATION
Technical Parameters
Mains: 85 to 250 VAC (50/60Hz) or 100 to 250 VDC, or 24 V
(optional)
Power consumption: 2VA
All sensors factory calibrated and software linearized.
Internal cold junction compensation for thermocouples, 2 or 3 Wire Pt100.
Pt100 input: 3 wire configuration with cable length compensation.
Excitation current: 170A
Internal resolution: 20000 counts
Linearity: Better than 0.05% of FS
Accuracy
Thermocouple J, K, T, E and N: 0.2% of range ±1°C.
Thermocouple R, S and B: 0.25% of range ±3°C.
Pt100: 0.2% of range
Refer to figures Upper Side Connector and Lower Side Connector, below for connections of the
input signals, power supply and alarm outputs.
Upper Side Connector
Field
Logger
Lower Side Connector
POWER –mains input
V
– backup DC voltage (+6 to +24VDC). Allows continuous logging of data into memory when the AC
BAT
voltage is absent. When the Field Logger is working with the V
communication and alarms are inhibited.
power only, the serial
BAT
ALM1 and ALM2 – output alarm relays
DIG.IN – Digital input. A switch connected to this input acts as a “gate” for the logger (this function must
be configured). The DIG.IN input shares one terminal with the V
BAT
input.
ABUS TECHNOLOGIES INC.
6
6. INSTALLATION
6.1 Input Signal
INPUT TYPE WORKING RANGE
Field
Logger
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple E
Thermocouple N
Thermocouple R
Thermocouple S
Thermocouple B
Pt100
4-20mA type J
4-20mA type K
4-20mA type T
4-20mA type E
4-20mA type N
4-20mA type R
4-20mA type S
4-20mA type B
-50 to 760°C (-58 to 1400 °F)
-90 to 1370°C (-130 to 2498 °F)
-100 to 400°C (-148 to 752 °F)
-35 to 720°C (-31 to 1328
-90 to 1300°C (-130 to 2372 °F)
0 to 1760°C (-32 to 3200 °F)
0 to 1760°C (-32 to 3200 °F)
150 to 1820°C (302 to 3308 °F)
-200.0 to 530.0°C (-328.0 to 986.0 °F)
-50 to 760°C (-58 to 1400 °F)
-90 to 1370°C (-130 to 2498 °F)
-100 to 400°C (-148 to 752 °F)
-35 to 720°C (-31 to 1328 °F)
-90 to 1300°C (-130 to 2372 °F)
0 to 1760°C (-32 to 3200 °F)
0 to 1760°C (-32 to 3200 °F)
150 to 1820°C (302 to 3308 °F)
°F
)
4-20mA type Pt100
4-20mA
-200.0 to 530.0°C (-328.0 to 986.0 °F)
Indication range from -1999 to 9999
Field Logger Input Signals
6.2 Alarm
The Field Logger has two relays (ALM1 and ALM2) which can be used as alarm outputs. They
can also be used as digital outputs. In this case, a Modbus command controls its logical state. When it
is used as alarms these relays can be associated to any input channel in an independent way. Two
distinct alarm Set-points can be set to every input channel performing a HIGH (Maximum) or LOW
(Minimum) functions.
The HIGH alarm will signal when the input exceeds the value configured in the respective Set-
point. The alarm LOW will be ON whenever the input signal is below its respective Set-point.
The alarms can be associated to any of the relays (or both). All input channels can share the same
relay; the output which will perform an “OR” logic with all the requests. In the case where various
channels use their alarms associated to the same output, the relay will be energized when any of the
channels enters into an alarm condition, remaining so as long as at least one alarm is using it.
ABUS TECHNOLOGIES INC.
7
7. CONFIGURATION
A diskette with configuration software is included in the Field Logger package or
can be downloaded from our web site www.abustek.com . It is also included with the
FieldChart software, also available in the ABUS site.
To install the Configurator, execute the program FL_Setup.EXE distributed in
the diskette. The FieldChart software automatically installs the Configurator. The
Configurator presents 4 pages for parameter configuration: Communication
Channels, Acquisitions, and Diagnosis.
7.1 Communication Page
When running the Configurator, first select the serial port (COM1 or COM2), as referred in the
Field
Logger
Communication page (See figure communication page, below). After setting up the communication
port, the user can start the Field Logger configuration.
Communication Page
When an unknown Field Logger is to be configured (no information on baud rate or address),
the Configurator can perform an ‘Automatic Search’ on the Field Logger connected to the PC COM port.
It finds out the baud rate and address actually programmed in the Field Logger. To access this function,
go to the Communication page and then click the button “Search”, in the “Automatic Search” box. The
actual Field Logger communication parameters are shown, enabling the user to change them (for
example, when configuring a network with many Field Loggers). To change the communication
parameters, select new values for Baud Rate and Address and then hit the button “Modify”.
The configuration program requires that only one Field Logger be connected to the PC when
the “automatic search” utility is called.
ABUS TECHNOLOGIES INC.
8
The factory default for the communication parameters is:
Baud rate = 9600
Address = 1
In a network, the baud rate must be the same for all instruments, and each instrument must
have a unique address.
The Configurator can talk to any Field Logger in the network, addressing one Field Logger at a
time. After selecting a new address, and clicking in “Read Configuration”, the parameters of the selected
Field Logger are read into the Configurator.
To configure other Field Logger parameters, go to the Channels page. A screen similar to
figure Channels Page is shown below.
7.2 Channels Page
In the “Channel Selection” box, choose a channel to be configured. The parameters shown on
Field
Logger
the right side of the screen refer to the channel selected. The channels marked “Enabled” will be
monitored (on-line monitoring) or logged into memory. A 16 character field (Title) is available for
identifying the application. In addition, each channel can have a tag associated to it, up to 8 characters.
The 8 input channels are universal, and it is allowed any combination of input types, that is,
each channel can be configured independently from the others.
Channel Page
It is possible to adjust the indication range for the linear inputs (4-20mA and 0-50mV) by setting
values to the high and low limits (-1999 to 9999).
For example, when a 4-20mA input is being used and the range is set to 0-4000, the Field
Logger will convert a value equal to 2000 for an input of 12mA. In addition, one can choose the number
of decimals and associate an engineering unit to that input.
For Thermocouples and Pt100, the ranges are fixed and represent the indication span of the
sensor. The selection of the temperature unit (C or F) is available for these sensors. Each channel has
ABUS TECHNOLOGIES INC.
9
two alarms associated to it. Set-point values and alarm functions (HI or LO) are set in the Alarm 1 and
Alarm 2 boxes, as well as the selection of the output relay for each alarm. If no relay is associated to an
alarm, even so the alarm will be processed and informed to the supervisory software (refer to section –
Serial Communication).
The 2 relays may be configured as alarms, as mentioned previously, or as digital outputs,
controlled by the MODBUS Preset Single Coil command, described in section- Serial Communication.
When configured as digital output (see boxes “Relay 1 function” and “Relay 2 function”), the relay
becomes unavailable to the alarms, even if an alarm was configured to use the relay. Returning the
relay to the Alarm function, all previous alarm configurations will work again.
The odd channels (1, 3, 5, and 7) can be configured as differential, as mentioned in section-
Analogue Inputs. When a channel is configured as differential, the adjacent channel is also used;
therefore, the respective even channel (2, 4, 6 or 8) is disabled in the configuration screen.
7.3 Acquisitions Page
This page contains the parameters needed for recording data in the Field Logger internal
Field
Logger
memory. These parameters are:
- Start Logging time
- Stop Logging time.
- Base Interval Between Loggings
- Interval Multipliers for the channels (set individually for each channel).
When a new logging configuration is transmitted, the current PC time and date is updated in the
Field Logger.
Note: Make sure the date and time in the PC is correct before sending a new configuration.
The Field Logger is meant for measuring process variables, prioritizing accuracy and resolution
over speed. The update rate for the input channels depends on the number of active channels and on
the sensor type configured in each channel. It takes 50ms for an input to be converted (measured).
Other internal measurements are needed for improving accuracy (offset suppression and gain
calibration). Besides, cold junction compensation for thermocouples and cable length compensation for
Pt100 measurements are also accomplished, depending on input channel configuration. An estimate
update time for a single channel measurement is 0.2s. For 8 channels with thermocouple inputs, this
time is 0.55s, whereas 8 Pt100 channels require 0.95s for the update.
So, the time interval between loggings should not be set shorter than the total time required for
reading the inputs. This time interval is defined by the Base Interval Between Loggings and the Interval
Multipliers.
The base interval can be specified from 0.2s to many hours and is common to all channels. The
interval multiplier, however, can be configured individually for each channel, allowing distinct logging
rates among channels. For example, for a base interval of 10s, a multiplier 1 will cause a new sample to
be recorded every 10s; for a multiplier equal to 6, the channel will be recorded once every minute. Using
ABUS TECHNOLOGIES INC.
10
the multipliers, the user can manage the memory usage according to the importance of each input
variable. The start and end of loggings can be accomplished in modes shown below:
Remotely, through serial (Modbus) command: Select the option by serial command at the Start
Logging parameter, and never stop for End Logging. Apply the configuration and then click the
mouse in the button ‘Start now’. The logging will go on until the button ‘Stop now’ is hit. If the data
memory is used up, it will wrap around, overwriting old data (circular memory).
Remote start, end after a programmed number of base intervals: The logging is initiated as in
the mode above, and goes on until a defined number of base intervals is reached. The logging can
be stopped by a serial command or when the memory runs out of space.
Remote start, end at a defined date and time: The logging is initiated by a serial command,
whereas the end is programmed to occur at a programmed date and time. The data logging can be
interrupted by a serial command or when the end of memory is reached.
Start and end of loggings at programmed date and time: A start date and time as well as the
Field
Logger
end date and time have to be configured in the Field Logger. A remote serial command or a full
memory can interrupt (stop) the logging.
Start at a determined date and time, end after a specified number of base intervals: Set the
start date and time and the number of base intervals required. Again, a remote serial command or
memory full can interrupt the logging.
Start commanded by the digital input: In this mode, the logging is performed while the digital
input is active. A new segment of data is initiated every time the digital input is driven. A time stamp
is recorded into memory (8 bytes of data) preceding each segment. The data logging is interrupted
by a serial command or when the end of memory is reached.
Acquisitions Page
ABUS TECHNOLOGIES INC.
11
NOTES:
1 An optional hardware with memory and real time clock is required for the data logging. If this
hardware is not identified, the Configurator will not allow setting the acquisition parameters.
2 The Field Logger real time clock is updated with the current PC date and time every time a new
configuration is transmitted to the Field Logger.
Other information provided by the Configurator is described below:
Current time: It informs the PC current time.
Logging memory size: It shows the number of readings that can be stored in the Field Logger
data memory.
Programmed Number of Loggings: It shows the total number of readings that will be recorded
for the given configuration. This number is obtained by the sum of all readings from the active
channels. The button “
channel, for the current configuration.
Programmed Number of Base intervals: It shows the quantity of base intervals that will be
processed according to the current configuration.
Estimated Duration: Informs the needed time for the acquisition to be accomplished, according
to the current configuration.
7.4 Diagnosis Page
Here, the Configurator performs a continuous reading of all input channels, once a second, and
shows the instant readings on the screen. The disabled channels in the configuration will present the
value of 0, regardless of what is connected to their inputs. This screen is useful to check if all inputs are
properly configured and wired. The alarms status is also available in this screen.
” opens a window with details on the number of acquisitions per
Field
Logger
The Diagnosis page provides means for setting digital filters to the input channels. The values
for the filter range from 0 to 9, being 3 the factory default. For slow varying inputs, like temperature
measurements, best results are obtained with high values of filter, as opposed to fast signals (pressure
transmitters, for example), where low values of filter are recommended.
Diagnosis Page
A field called No. of Loggings informs the current number of readings recorded in the Field
Logger internal memory (for the models that have this option). Best performance of Field Logger is
obtained if the correct mains frequency is selected. Click in the corresponding box for 50 or 60Hz (the
default frequency is 60Hz). The instrument serial number, as well as the firmware version, can also be
visualized in this screen. In summary, the Diagnosis page provides useful information and it is wise to
ABUS TECHNOLOGIES INC.
12
take a look at it after applying a new configuration to the Field Logger. Click on the Apply button to send
the new configuration. The OK button will also transmit the new configuration to the Field Logger,
closing the window. The Cancel button simply closes the window, discarding any changes.
7.5 Serial Communication
The Field Logger communicates with the Configurator or the application software by its RS485
serial interface, using the Modbus protocol. The computer is the master and the Field Logger is the
slave. The communication is always started at the host (master), which transmits a command to the
destination address. The addressed slave (a Field Logger) recognizes the request and answers back to
the host. The Field Logger also responds to broadcast type commands.
OBS.: It is recommended to use a 326AWG shielded cable for serial communication.
Field
Logger
7.5.1 Characteristics
RS485 standard (2 wire, isolated)
Address capability for 247 instruments in the same network (31 instruments maximum per
The Field Logger configuration parameters are organized in a table of registers. Using the block
read capability of the protocol; many registers can be viewed in a single request command.
The user does not need to know the parameter position in the table as long as he uses the
Configurator software. A parameter is a word of 16 bits. The MODBUS command used for reading is:
03 - Read Holding Register
The following registers are equivalent to the holding registers (4X reference):
Holding
Registers
0001 Channel 1 current reading
0002 Channel 2 current reading
0003 Channel 3 current reading
0004 Channel 4 current reading
0005 Channel 5 current reading
0006 Channel 6 current reading
0007 Channel 7 current reading
0008 Channel 8 current reading
0009 Alarm status
0010 Reserved: general status
0011 Channels 1 and 2 status
0012 Channels 3 and 4 status
0013 Channels 5 and 6 status
0014 Channels 7 and 8 status
Parameter
ABUS TECHNOLOGIES INC.
13
Field
Logger
Registers 01 to 08:
It holds the most recent measurements on the channels. The channel update rate depends on
the number of active channels and on the input types configured in the channels. The Field Logger
updates the readings at the maximum possible rate (limited to the A/D conversion time).
The channels configured for Pt100 take twice the time to deliver a new conversion, since it
performs two conversions in sequence (cable length compensation).
When only one channel is active, the time needed for updating the channel is 0.2 seconds (best
case). When 8 channels are configured as Pt100, the update of the 8 channels takes 0.95s (worst
case). The returned value is in 2’s complement.
For Pt100 readings, where the resolution is 1/10
th
of a degree, the decimal point is not
transmitted, due to protocol limitations. Likewise, the decimal point is disregarded for the linear inputs
(4-20mA and 0-50mV).
Register 09:
Reports the alarm status, as drawn below:
Byte high:
Byte low:
Byte High
Byte Low
ABUS TECHNOLOGIES INC.
14
Registers 11 to 14:
Report A/D conversion errors:
Byte High odd channels:
Field
Logger
Byte High to Odd Channel
Byte Low even channels:
*Same as byte high, for the adjacent channel.
7.5.3 Digital Outputs
Field Logger relays can be configured as serial activated digital outputs. The Modbus command
for setting the digital outputs is: