AbsolutAire AMC 1022 User Manual

AMC 1022 (standard)
GAS MONITOR
Enclosure: ASA 61 gray enameled 14 gauge steel Supply voltage: 120 VAC, 60 Hz Relay contacts: For low and high alarms, DPDT 10A Calibration: Factory calibrated in L.E.L,
PPM or % by volume
Dimensions and weights: 20.5cm H x 15.5cm W x 9cm D
(8” x 6” x 3.5”) 8 lb
Operating temperature: 0°C to 40°C (32°F to 104°F) Storage temperature: -40°C to 65°C (-40°F to 149°F) Monitor warranty: Two years Indicators per channel: Power on - green LED
Fail indicator - amber LED Low alarm - yellow LED, five
minute time delay High alarm - red LED, ten minute time delay
Features: Alarms disabled during warm-up, test switch
Disable switches for audio alarm and time delays
Approvals: CSA and UL
Sensor element warranty:
Response time:
Sensor type:
Range:
Repeatability:
Accuracy:
Operating temperature:
Operating humidity:
Life expectancy:
Storage:
The Armstrong Monitoring Corporation 215 Colonnade Road South Ottawa, Ontario K2E 7K3
Tel: 613.225.9531 Fax: 613.225.6965 North America: 800.465.5777 www.armstrongmonitoring.com
Combustible gas Carbon monoxide Refrigerant gas Ammonia
0 - 50% L.E.L 0 - 100 PPM 0 - 1000 PPM 0 - 500 PPM
The AMC 1022 monitor is an economical all-in-one gas detection system engineered to continuously monitor a variety of toxic or combustible gases. Featuring LEDs for power, fail, high and low alarm indication. The AMC 1022 is a complete system including built-in sensor, two 10 amp relays (DPDT), user selectable time delays, and audible alarm.
The method of operation of each detection point is such that when the level of gas surpasses the preset gas concentration settings, the circuitry will activate a remote alarm and/or an exhaust system utilizing the 10 amp heavy duty relays. Sensor reaction is instantaneous; however, alarms can be delayed dependent upon user preference.
Note: For multi sensor applications refer to AMC 1022M, AMC 1030
and AMC 1022D technical data sheets
Metal oxide semiconductor
Two years
Less than ten seconds 80% in 30 seconds
10% of full scale
8% of full scale
-30°C to 50°C 0°C to 40°C 0 - 99% RH, non-condensing
Greater than five years
Unlimited
AMC 1022 WIRING DIAGRAM
For more information: Authorized Distributor
Warranty: All Armstrong equipment is warranted against defects in materials and workmanship for two years from date of delivery, except sensors. Please contact factory for sensor warranty. During the warranty period, we will repair or replace components that prove, in our opinion, to be defective. We are not liable for auxiliary interfaced equipment, nor consequential damage. All warranty items must be returned by prepaid freight.
Note: Due to ongoing product development, the manufacturer reserves the right to change specifications without prior notice. The information contained herein is based on data considered accurate. However, no warranty is expressed or implied regarding the accuracy of this data.
The Armstrong Monitoring Corporation 215 Colonnade Road South Ottawa, Ontario K2E 7K3
Tel: 613.225.9531 Fax: 613.225.6965 North America: 800.465.5777 www.armstrongmonitoring.com
Rev. 010804
Loading...