a19s_cbt whole
A19 Series
Action on Increase
of Temperature
Y
B
R
Refrigeration Temperature Controls Rev: 07/18/97
A19 Series
Coiled Bulb Space Thermostat
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1927050
1927050
9thcc:7-12
logo:
JCI
left ft:
refrig
right ft:
standard
Sect# = 7
seQ# = 10
a19bac1c.tif
a19.eps
A19BAC
Selection Chart
Code
Number
A19BAB-3C
◆
A19BAC-1C SPDT
A19BAF-1C SPDT
◆
A19BBC-2C
(a) Replaces White-Rodgers 201-16, -8, 2A37-1; Ranco 010-1418, -1802, 016-594, C30-C1101;
Honeywell T631A, T696A, T6054 A1005.
(a)
Switch
Action
SPST,
Open High
SPDT
Range
°F (°C)
35 to 95
(0 to 35)3(1.7) Fixed
30 to 110
(-1 to 43)
30 to 110
(-1 to 43)
-30 to 100
(-34 to 38)
Diff F°
(C°)
VENTILATING, HEATING
3 1/2
(1.9) Fixed
1 1/2
(0.9) Fixed
COOLING
3 to 12
(1.7 to 7)
Bulb and
Capillary
1 3/8 in. x 2 1/4 in.
Coiled
1 3/8 in. x 2 1/4 in.
Coiled
1 3/8 in. x 2 1/4 in.
Coiled
1 3/8 in. x 2 1/4 in.
Coiled
Range
Adjuster
Knob
Convertible
Knob
Convertible 140 (60)
Max. Bulb
Temp
°F (°C)
140 (60)
Description
Wide range temperature control with air coil
sensing element.
Features
• wide temperature range
• NEMA 1 enclosure
Applications
• return air or space temperature sensing
To Order
Specify the code number from the following
selection chart.
Replacement Parts
Code Number Description
CVR28A-617R Concealed adjustme nt
CVR28A-618R Visible scale
KNB20A-602R Knob kit
Electrical Ratings
Motor Ratings VAC 120 208 240
A19BAB, A19BAC
AC Full Load Amp 16.0 9.2 8.0
AC Locked Rotor Amp 96.0 55.2 48.0
Non-Inductive or
Resistance Load Amp
(Not Lamp Loads)
Pilot Duty – 125 VA, 24 to 600 VAC
AC Full Load Amp 6.0 3.4 3.0
AC Locked Rotor Amp 36.0 20.4 18.0
Non-Inductive or
Resistance Load Amp
(Not Lamp Loads)
Pilot Duty – 125 VA, 24 to 277 VAC
COOLING - A19BBC
AC Full Load Amp 16.0 9.2 8.0
AC Locked Rotor Amp 96.0 55.2 48.0
Non-Inductive or
Resistance Load Amp
(Not Lamp Loads)
Pilot Duty – 125 VA, 24 to 600 VAC
(a) SPST and only one side of SPDT control;
SPDT - 16 amps 120 to 277 VA C
22 amps ,120 to 277
(a)
VAC
A19BAF
10 amp, 120 to 277 VAC
22 amps, 120 to 277
(a)
VAC
▲
Universal Replacement ★ Non-Stock Item. Built to Order. (R) For Refrigerants Not Listed, Contact Application Engineering
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
1/1
© 08/02 Johnson Controls, Inc