Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1927005
a11s_ltc Less-M/a11-a19 1927005 9thcc:7-5A Refrigeration Temperature Controls Rev:
A11 Series
Low Temperature Cutout Control
a11b1c.tif
A11B-1
a11coil.eps
Mount Coils Horizontally ONLY
a11wire.eps
A11 Ser ies
A11 Ser ies
07/18/97
logo:
JCI/Penn
left ft:
frig
right ft:
standard
Sect# = 0
seQ# = 1
Action on Increase of Temperature
Description
The A11 Series low temperature cutout
controls incorporate a 20 foot long, vapor
charged, sensing element. The A11 reacts to
the coldest 18 inch section of the controls
sensing element. The A11 is suitable for
Accessories
• replacement cover: CVR30A-601R
Applications
• low temperature cut-out for coils and/or
pipe liquid sensing
To Order
Specify the code number from the following
selection chart.
monitoring the face temperature of hot water
coils for freeze protection.
Features
• snap-acting switch
• external temperature scale
• easy setpoint adjustment with top or bottom
access
Specifications
• ambient temperature of control:
0-140°F (-17.8 - 60°C)
• maximum element temperature:
250°F (121°C)
Electrical Ratings
Motor Ratings VAC 120 208 240
AC Full Load Amp 16.0 9.2 8.0
AC Locked Rotor Amp 96.0 55.2 48.0
Non-Inductive or
Resistance Load Amp
(Not Lamp Loads)
Pilot Duty – 125 VA, 24 to 277 VAC
16.0 9.2 8.0
Selection Chart
Code
Number
A11A-1C
A11B-1C
Switch
Action
SPST
Open Low
SPST
Open Low
Range
°F (°C)
35 to 45
(2 to 7)
35 to 45
(2 to 7)
Diff F°
(C°)
Manual
Reset
8 (4.4)
(Fixed)
Bulb and Capillary
20 ft of 1/8 in.
O.D. Tubing, 4 ft Cap.
20 ft of 1/8 in.
O.D. Tubing, 4 ft. Cap.
Range
Adjuster
Screwdriver
Slot
Screwdriver
Slot
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
1/1
© 08/02 Johnson Controls, Inc