3D CAD outline drawings available on "Control Product 3D" portal
Ordering DetailsTypeOrder CodeEAN Code
Grey-Dark Grey
Grey-Dark Grey
ZS4-SF-R21SNK 506 413 R000034725950641375018.60
ZS4-SF-R41SNK 506 416 R000034725950641685018.60
Declarations and CertificatesDocument Part Number
UE Directive1SND 225 098 C1002
Third Party Certificate1SND 161 029 A0200
RoHS1SND 230 491 F0203
Features and Benefits
- Protect your circuits with 5x20 fuse terminal blocks compliant with
IEC 60947-7-3 standard (fuse not supplied with the terminal blocks),
- Simplify the distribution thanks to the two jumper channels aligned with
ZS4 feed-through and ZS4-S-R1 disconnect terminal blocks,
- Ease the test with built-in test socket screws,
- Quickly identify the defective circuit thanks to the blown fuse indicator
(with leakage current < 0.5 mA).
Pack
(ing)
Weight g (1 pce)
4 mm²
10 AWG
General Information
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
ProtectionIP 20NEMA 1
Rail
Wire stripping length
Operating tool
Torque
Mechanical endurance
of disconnect system
DIN3-TH35
10.5 mm0.413 in
Screw clampScrew rail contact
(Maximum value)
Flat screwdriver
3.5 mm0.138 in
0.6 Nm5.31 lb.in
± 0.1 Nm± 0.885 lb.in± 0.1 Nm± 0.885 lb.in
1
Page 2
Material Specifications
2
Insulating materialPolyamide
IRC600 V
FlammabilityUL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor0.2-4 mm²24-10 AWG
1 Flexible conductor without ferrule0.22-4 mm²24-10 AWG
1 Flexible conductor with ferrule0.22-4 mm²24-12 AWG
Ferrule maximum outer diameter
5.5 mm0.216 in
Multi Connecting capacity per clamp
2 Rigid conductors0.2-1 mm²24-18 AWG
2 Flexible conductors without ferrule0.22-1 mm²24-18 AWG
2 Flexible conductors with twin ferrule0.22-1.5 mm²24-16 AWG
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Field and factory wiring Cat.2UL 1059 6.3 A
Factory wiring Cat.1UL 1059 6.3 A
CSA-C-22.2 n° 158 6.3 A
Rated short-time withstand current 1 s (Icw)480 A
Short-time withstand current0.5 sManufacturer data
5 sManufacturer data
10 sManufacturer data
30 sManufacturer data
1 mnManufacturer data
Rated short circuit withstandCSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²)Manufacturer data 6.3 A4 mm²
Maximum short circuit current (1s)Manufacturer data 480 A
Short Circuit Current Rating (SCCR) SA UL 1059 supplement
With the following congurations:
Maximum voltage
Suitable conductor wire range
Fuse rating
Fuse designation
Fuse manufacturer name
Fuse type
Short circuit current
SCCR UL 1059
Page 3
Voltage
Overload and short-circuit protection
PV separate arrangement
2.2W
3.8W
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0102030405060708090100 110 120130
Ambient air temperature T °C
Power dissipation P W
Exclusive short-circuit protection
PVK compound arrangement
4.7W
2.7W
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
(Auxiliary line Pv1)
Overload and short-circuit protection
PV compound arrangement
2.6W
1.5W
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
Exclusive short-circuit protection
PVK separate arrangement
3.6W
6.3W
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
(Auxiliary line Pv1)
3
Rated voltageIEC 60947-1 250 V
Rated voltageUL 1059 150 V
Use GroupUL 1059 D
Rated voltageCSA-C-22.2 n° 158 150 V
Rated voltage Ex eIEC/EN 60079-11
Rated impulse withstand voltage6000 V
Dielectric test voltage1890 V
Pollution degree IEC 60947-1 3
Overvoltage categoryIEC 60947-1 III
Dissipated power
Maximum dissipated power at rated current
IEC
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3
Overload and short-circuit protection
Separate arrangement
Exclusive short-circuit protection
Separate arrangement
Overload and short-circuit protection
Compound arrangement
Exclusive short-circuit protection
Compound arrangement
1 fuse and 4 feed-through blocks
5 fuse blocks
2.5 W
4 W
2.5 W
4 W
Temperature range
Ambient temperature min/maxStorage-55 +110 °C-67 +230 F
Installing-5 +40 °C-23 +104 F
ServiceIEC 60068-2-1 -55 +110 °C-67 +230 F
EN 60079-7
Current Derating curve for continuous service temperature
Page 4
Environmental Characteristics
4
Additional climatic tests
Dry heatIEC 60068-2-2 Compliant
ConditionsTemperature +100 °C
Duration of test 96 h
Cyclic damp heatIEC 60068-2-30 Compliant
ConditionsTemperature +55 °C
Number of cycles 2
ColdIEC 60068-2-1 Compliant
ConditionsTemperature -40 °C
Duration of test 96 h
Z/ABDM climatic sequenceIEC 60068-2-61 Compliant
ConditionsDry heat Duration of test / Temperature 16 h+85 °C
Cyclic damp heat Number of cycles / Temperature 1+55 °C
Cold Duration of test / Temperature 2 h-25 °C
Corrosion
Salt mistIEC 60068-2-11 Compliant
ConditionsDuration of test 96 h
Concentration 5 %
SO2ISO 6988 Compliant
ConditionsDuration of test 48 h
Concentration 0.2 dm³
Sulfur dioxideIEC 60068-2-42
ConditionsDuration of test
Hydrogen sulfurIEC 60068-2-43
ConditionsDuration of test
Flowing mixed gas corrosion testIEC 60068-2-60
ConditionsNumber of the test method
Duration of test
Vibrations
VibrationsIEC 60068-2-6 Compliant
ConditionsFrequency range 10-55 Hz
Number of cycles 10
Amplitude
Acceleration 10 m/s²
Ramdom vibrations and climatic sequenceIEC 60068-2-64
ConditionsDuration of test
Frequency range
Acceleration
Climatic cycles
Step 1 -> Temperature / Duration of test
Step 2 -> Temperature / Duration of test
Temperature variation per minute
Page 5
ZS4-SF-R Terminal Block Accessories Compatibility
5
DescriptionTypeOrder Code
1
End Stops
Jumper Bars
2
Test Adapters
3
Test Connectors
4
Spacers
5
Test Plugs
6
Tools
7
Terminal Block Markers
8
BAM31SNK 900 001 R00005013.801SNK 160 026 D0201
JB6-21SNK 906 302 R0000501.301SNK 160 029 D0201
JB6-31SNK 906 303 R0000502.101SNK 160 029 D0201
JB6-41SNK 906 304 R0000502.901SNK 160 029 D0201
JB6-51SNK 906 305 R0000503.601SNK 160 029 D0201
JB6-101SNK 906 310 R0000207.401SNK 160 029 D0201
TP21SNK 900 203 R0000201.731SNK 160 036 D0201
TP41SNK 900 205 R0000202.421SNK 160 036 D0201
TC5-R11SNK 900 201 R0000105.231SNK 160 042 D0201
ES-TC61SNK 900 105 R0000100.801SNK 160 042 D0201
FC2.MC1SNA 107 239 R0300101.001SNK 160 036 D0201
PS-31SNK 900 650 R00001380.001SNK 160 024 D0201
MC6121SNK 150 000 R0000220.061SNK 160 006 D0201
UMH1SNK 900 611 R0000100.201SNK 160 001 D0201
PROCAP61SNK 900 612 R0000200.791SNK 160 013 D0201
SAT61SNK 900 615 R000056.001SNK 160 013 D0201
(ing)
Pack
WeightTechnical Datasheet
piecesg (1 pce) PDF
Loading...