3D CAD outline drawings available on "Control Product 3D" portal
Ordering DetailsTypeOrder CodeEAN Code
Grey-Dark Grey
Grey-Dark Grey
ZS4-SF1-R21SNK 508 413 R000034725950841355013.30
ZS4-SF1-R41SNK 508 415 R000034725950841595013.30
Declarations and CertificatesDocument Part Number
UE Directive1SND 225 098 C1002
Third Party Certificate1SND 161 030 A0200
RoHS1SND 230 491 F0203
Features and Benefits
- Protect your circuit with 5x25 and 5x20 fuse terminal blocks (fuse not
supplied with the terminal blocks),
- Compliant with IEC 60947-7-3 standard,
- Ease the test with built-in test socket screws,
- Quickly identify the defective circuit thanks to the blown fuse indicator
(with leakage current < 0.5 mA).
Pack
(ing)
Weight g (1 pce)
4 mm²
10 AWG
General Information
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
ProtectionIP 20NEMA 1
Rail
Wire stripping length
Operating tool
Torque
Mechanical endurance
of disconnect system
DIN3-TH35
11 mm0.433 in
Screw clampScrew rail contact
(Maximum value)
Flat screwdriver
3.5 mm0.138 in
0.6 Nm5.31 lb.in
± 0.1 Nm± 0.885 lb.in ± 0.1 Nm± 0.885 lb.in
1
Page 2
Material Specifications
2
Insulating materialPolyamide
IRC600 V
FlammabilityUL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor0.2-4 mm²24-10 AWG
1 Flexible conductor without ferrule0.22-4 mm²24-10 AWG
1 Flexible conductor with ferrule0.22-4 mm²24-12 AWG
Ferrule maximum outer diameter
5.5 mm 0.216 in
Multi Connecting capacity per clamp
2 Rigid conductors0.2-1 mm²24-18 AWG
2 Flexible conductors without ferrule0.22-1 mm²24-18 AWG
2 Flexible conductors with twin ferrule0.22-1.5 mm²24-16 AWG
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Field and factory wiring Cat.2UL 1059 6.3 A
Factory wiring Cat.1UL 1059 6.3 A
CSA-C-22.2 n° 158 6.3 A
Rated short-time withstand current 1 s (Icw)480 A
Short-time withstand current0.5 sManufacturer data
5 sManufacturer data
10 sManufacturer data
30 sManufacturer data
1 mnManufacturer data
Rated short circuit withstandCSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²)Manufacturer data 6.3 A4 mm²
Maximum short circuit current (1s)Manufacturer data 480 A
Short Circuit Current Rating (SCCR) SA UL 1059 supplement
With the following congurations:
Maximum voltage
Suitable conductor wire range
Fuse rating
Fuse designation
Fuse manufacturer name
Fuse type
Short circuit current
SCCR UL 1059
Page 3
Voltage
Overload and short-circuit protection
PV separate arrangement
2.2W
3.8W
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0102030405060708090100 110 120130
Ambient air temperature T °C
Power dissipation P W
Exclusive short-circuit protection
PVK compound arrangement
4.7W
2.7W
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
(Auxiliary line Pv1)
Overload and short-circuit protection
PV compound arrangement
2.6W
1.5W
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
Exclusive short-circuit protection
PVK separate arrangement
3.6W
6.3W
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0102030405060708090100 110120 130
Ambient air temperature T °C
Power dissipation P W
(Auxiliary line Pv1)
3
Rated voltageIEC 60947-1 250 V
Rated voltageUL 1059 300 V
Use GroupUL 1059 D
Rated voltageCSA-C-22.2 n° 158 300 V
Rated voltage Ex eIEC/EN 60079-11
Rated impulse withstand voltage8000 V
Dielectric test voltage2200 V
Pollution degree IEC 60947-1 3
Overvoltage categoryIEC 60947-1 III
Dissipated power
Maximum dissipated power at rated current
IEC
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3
Overload and short-circuit protection
Separate arrangement
Exclusive short-circuit protection
Separate arrangement
Overload and short-circuit protection
Compound arrangement
Exclusive short-circuit protection
Compound arrangement
1 fuse and 4 feed-through blocks
5 fuse blocks
2.5 W
4 W
1.6 W
4 W
Temperature range
Ambient temperature min/maxStorage-55 +110 °C-67 +230 F
Installing-5 +40 °C-23 +104 F
ServiceIEC 60068-2-1 -55 +110 °C-67 +230 F
EN 60079-7
Current Derating curve for continuous service temperature
Page 4
Environmental Characteristics
4
Additional climatic tests
Dry heatIEC 60068-2-2 Compliant
ConditionsTemperature +100 °C
Duration of test 96 h
Cyclic damp heatIEC 60068-2-30 Compliant
ConditionsTemperature +55 °C
Number of cycles 2
ColdIEC 60068-2-1 Compliant
ConditionsTemperature -40 °C
Duration of test 96 h
Z/ABDM climatic sequenceIEC 60068-2-61 Compliant
ConditionsDry heat Duration of test / Temperature 16 h+85 °C
Cyclic damp heat Number of cycles / Temperature 1+55 °C
Cold Duration of test / Temperature 2 h-25 °C
Corrosion
Salt mistIEC 60068-2-11 Compliant
ConditionsDuration of test 96 h
Concentration 5 %
SO2ISO 6988 Compliant
ConditionsDuration of test 48 h
Concentration 0.2 dm³
Sulfur dioxideIEC 60068-2-42
ConditionsDuration of test
Hydrogen sulfurIEC 60068-2-43
ConditionsDuration of test
Flowing mixed gas corrosion testIEC 60068-2-60
ConditionsNumber of the test method
Duration of test
Vibrations
VibrationsIEC 60068-2-6 Compliant
ConditionsFrequency range 10-55 Hz
Number of cycles 10
Amplitude
Acceleration 10 m/s²
Ramdom vibrations and climatic sequenceIEC 60068-2-64
ConditionsDuration of test
Frequency range
Acceleration
Climatic cycles
Step 1 -> Temperature / Duration of test
Step 2 -> Temperature / Duration of test