3D CAD outline drawings available on "Control Product 3D" portal
Ordering DetailsTypeOrder CodeEAN Code
Grey
Blue
Orange
ZS351SNK 516 010 R000034725951601052053.40
ZS35-BL1SNK 516 020 R000034725951602042053.40
ZS35-OR1SNK 516 030 R000034725951603032053.40
Declarations and CertificatesDocument Part Number
UE Directive1SND 225 081 C1006
Third Party Certificate1SND 161 028 A0200
Features and Benefits
Closed terminal block:
- No end section needed,
- Optimized rigidity.
Pack
(ing)
Weight g (1 pce)
35 mm²
0 AWG
RoHS1SND 230 491 F0203
Atex Declaration1SND 225 085 C1003
1
General Information
2
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
ProtectionIP 20NEMA 1
Rail
Wire stripping length
Operating tool
Torque
Mechanical endurance
of disconnect system
DIN3-TH35
17 mm0.669 in
Screw clampScrew rail contact
(Maximum value)
Flat screwdriver
6.5 mm0.256 in
2.9 Nm25.7 lb.in
± 0.1 Nm± 0.885 lb.in ± 0.1 Nm± 0.885 lb.in
Material Specifications
Insulating materialPolyamide
IRC600 V
FlammabilityUL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor6-35 mm²10-0 AWG
1 Flexible conductor without ferrule6-35 mm²10-0 AWG
1 Flexible conductor with ferrule
Ferrule maximum outer diameter
14 mm0.551 in
Multi Connecting capacity per clamp
2 Rigid conductors16 mm²4 AWG
2 Flexible conductors without ferrule10 mm²6 AWG
2 Flexible conductors with twin ferrule
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Field and factory wiring Cat.2UL 1059 150 A
Factory wiring Cat.1UL 1059 150 A
CSA-C-22.2 n° 158 150 A
Rated short-time withstand current 1 s (Icw)4200 A
Short-time withstand current0.5 sManufacturer data
5 sManufacturer data
10 sManufacturer data
30 sManufacturer data
1 mnManufacturer data
Rated short circuit withstandCSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²)Manufacturer data 125 A35 mm²
Maximum short circuit current (1s)Manufacturer data 4200 A
Short Circuit Current Rating (SCCR) SA UL 1059 supplement
ZS35 Terminal block
125.0A
117.9A
110.2A
102.1A
93.2A
83.3A
72.2A
58.9A
41.7A
0.0A
0
20
40
60
80
100
120
140
5565758595105115
AMBIANT TEMPERATURE (°C)
CURRENT (A)
3
SCCR UL 1059
With the following congurations:
Maximum voltage
Suitable conductor wire range
Fuse rating
Fuse designation
Fuse manufacturer name
Fuse type
Short circuit current
Voltage
Rated voltageIEC 60947-1 1000 V
Rated voltageUL 1059 600 V
Use GroupUL 1059 C
Rated voltageCSA-C-22.2 n° 158 600 V
Rated voltage Ex eIEC/EN 60079-11 630 V
Rated impulse withstand voltage8000 V
Dielectric test voltage2200 V
Pollution degree IEC 60947-1 3
Overvoltage categoryIEC 60947-1 III
Dissipated power
Maximum dissipated power at rated current
IEC 4 W
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3
Overload and short-circuit protection
Separate arrangement
Exclusive short-circuit protection
Separate arrangement
1 fuse and 4 feed-through blocks
Overload and short-circuit protection
Compound arrangement
Exclusive short-circuit protection
Compound arrangement
5 fuse blocks
Temperature range
Ambient temperature min/maxStorage-55 +110 °C-67 +230 F
Installing-5 +40 °C-23 +104 F
ServiceIEC 60068-2-1 -55 +110 °C-67 +230 F
EN 60079-7 -55 +85 °C
Current Derating curve for continuous service temperature
Environmental Characteristics
4
Additional climatic tests
Dry heatIEC 60068-2-2 Compliant
ConditionsTemperature +100 °C
Duration of test 96 h
Cyclic damp heatIEC 60068-2-30 Compliant
ConditionsTemperature +55 °C
Number of cycles 2
ColdIEC 60068-2-1 Compliant
ConditionsTemperature -40 °C
Duration of test 96 h
Z/ABDM climatic sequenceIEC 60068-2-61 Compliant
ConditionsDry heat Duration of test / Temperature 16 h+85 °C
Cyclic damp heat Number of cycles / Temperature 1+55 °C
Cold Duration of test / Temperature 2 h-25 °C
Corrosion
Salt mistIEC 60068-2-11 Compliant
ConditionsDuration of test 96 h
Concentration 5 %
SO2ISO 6988 Compliant
ConditionsDuration of test 48 h
Concentration 0.2 dm³
Sulfur dioxideIEC 60068-2-42
ConditionsDuration of test
Hydrogen sulfurIEC 60068-2-43
ConditionsDuration of test
Flowing mixed gas corrosion testIEC 60068-2-60
ConditionsNumber of the test method
Duration of test
Vibrations
VibrationsIEC 60068-2-6 Compliant
ConditionsFrequency range 10-55 Hz
Number of cycles 10
Amplitude
Acceleration 10 m/s²
Ramdom vibrations and climatic sequenceIEC 60068-2-64
ConditionsDuration of test
Frequency range
Acceleration
Climatic cycles
Step 1 -> Temperature / Duration of test
Step 2 -> Temperature / Duration of test