3D CAD outline drawings available on "Control Product 3D" portal
Ordering DetailsTypeOrder CodeEAN Code
Green-Yellow
ZS10-PE1SNK 508 150 R000034725950815092022.50
Declarations and CertificatesDocument Part Number
UE Directive1SND 225 094 C1003
Third Party Certificate1SND 161 019 A0201
RoHS1SND 230 491 F0203
Features and Benefits
Improve the safety of your installation in the event of a short-circuit thanks
to our screwless rail contact:
- Rail contact non operator dependent,
- Performances above the requirements of IEC 60947-7-2 terminal block
standard,
- Secured snap on or remove from the rail,
- PE.N function available by combining ZS10-PE with ZS10-BL and 2 poles
jumper bar JB8-2.
Pack
(ing)
Weight g (1 pce)
10 mm²
6 AWG
Atex Declaration1SND 225 085 C1003
1
General Information
2
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
ProtectionIP 20NEMA 1
Rail
Wire stripping length
Operating tool
Torque
Mechanical endurance
of disconnect system
DIN3-TH35
12 mm0.472 in
Screw clampScrew rail contact
(Maximum value)
Flat screwdriver
4 mm0.157 in
1.3 Nm11.5 lb.in
± 0.3 Nm± 2.65 lb.in± 0.3 Nm± 2.65 lb.in
Material Specifications
Insulating materialPolyamide
IRC600 V
FlammabilityUL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor0.5-10 mm²20-6 AWG
1 Flexible conductor without ferrule0.5-10 mm²20-6 AWG
1 Flexible conductor with ferrule0.5-10 mm²24-8 AWG
Ferrule maximum outer diameter
7.5 mm 0.295 in
Multi Connecting capacity per clamp
2 Rigid conductors
2 Flexible conductors without ferrule
2 Flexible conductors with twin ferrule
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Field and factory wiring Cat.2UL 1059
Factory wiring Cat.1UL 1059
CSA-C-22.2 n° 158
Rated short-time withstand current 1 s (Icw)1200 A
Short-time withstand current0.5 sManufacturer data
5 sManufacturer data
10 sManufacturer data
30 sManufacturer data
1 mnManufacturer data
Rated short circuit withstandCSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²)Manufacturer data10 mm²
Maximum short circuit current (1s)Manufacturer data 1200 A
Short Circuit Current Rating (SCCR) SA UL 1059 supplement
3
With the following congurations:
Maximum voltage
Suitable conductor wire range
Fuse rating
Fuse designation
Fuse manufacturer name
Fuse type
Short circuit current
SCCR UL 1059
Voltage
Rated voltageIEC 60947-1
Rated voltageUL 1059
Use GroupUL 1059 C
Rated voltageCSA-C-22.2 n° 158
Rated voltage Ex eIEC/EN 60079-11
Rated impulse withstand voltage8000 V
Dielectric test voltage2200 V
Pollution degree IEC 60947-1 3
Overvoltage categoryIEC 60947-1 III
Dissipated power
Maximum dissipated power at rated current
IEC
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3
Overload and short-circuit protection
Separate arrangement
Exclusive short-circuit protection
Separate arrangement
Overload and short-circuit protection
Compound arrangement
Exclusive short-circuit protection
Compound arrangement
1 fuse and 4 feed-through blocks
5 fuse blocks
Temperature range
Ambient temperature min/maxStorage-55 +110 °C-67 +230 F
Installing-5 +40 °C-23 + 104 F
ServiceIEC 60068-2-1 -55 +110 °C-67 +230 F
EN 60079-7 -55 +85 °C
Current Derating curve for continuous service temperature
Environmental Characteristics
4
Additional climatic tests
Dry heatIEC 60068-2-2 Compliant
ConditionsTemperature +100 °C
Duration of test 96 h
Cyclic damp heatIEC 60068-2-30 Compliant
ConditionsTemperature +55 °C
Number of cycles 2
ColdIEC 60068-2-1 Compliant
ConditionsTemperature -40 °C
Duration of test 96 h
Z/ABDM climatic sequenceIEC 60068-2-61 Compliant
ConditionsDry heat Duration of test / Temperature 16 h+85 °C
Cyclic damp heat Number of cycles / Temperature 1+55 °C
Cold Duration of test / Temperature 2 h-25 °C
Corrosion
Salt mistIEC 60068-2-11 Compliant
ConditionsDuration of test 96 h
Concentration 5 %
SO2ISO 6988 Compliant
ConditionsDuration of test 48 h
Concentration 0.2 dm³
Sulfur dioxideIEC 60068-2-42
ConditionsDuration of test
Hydrogen sulfurIEC 60068-2-43
ConditionsDuration of test
Flowing mixed gas corrosion testIEC 60068-2-60
ConditionsNumber of the test method
Duration of test
Vibrations
VibrationsIEC 60068-2-6 Compliant
ConditionsFrequency range 10-55 Hz
Number of cycles 10
Amplitude
Acceleration 10 m/s²
Ramdom vibrations and climatic sequenceIEC 60068-2-64
ConditionsDuration of test
Frequency range
Acceleration
Climatic cycles
Step 1 -> Temperature / Duration of test
Step 2 -> Temperature / Duration of test
Temperature variation per minute
ZS10-PE Terminal Block Accessories Compatibility
5
DescriptionTypeOrder Code
1
End Stops
End Sections
2
Jumper Bars
3
Circuit Separators
4
Test Adapters
5
Test Connectors
6
Spacers
7
Protecting Covers
8
Protecting Cover Kits
9
Tools
10
Terminal Block Markers
11
BAM31SNK 900 001 R00005013.801SNK 160 026 D0201
BAZH11SNK 900 102 R00002023.901SNK 160 026 D0201
ES41SNK 505 910 R0000202.181SNK 160 022 D0201
JB8-21SNK 908 302 R0000502.701SNK 160 030 D0201
CS-R11SNK 900 103 R0000205.201SNK 160 018 D0201
TP21SNK 900 203 R0000201.731SNK 160 036 D0201
TP41SNK 900 205 R0000202.421SNK 160 036 D0201
TC51SNK 900 200 R0000105.231SNK 160 042 D0201
TC5-R11SNK 900 201 R0000105.231SNK 160 042 D0201
ES-TC81SNK 900 104 R0000101.351SNK 160 042 D0201
CO1SNK 900 604 R00001300.001SNK 160 020 D0201
KCO1SNK 900 624 R0000147,81SNK 160 028 D0201
PS-31SNK 900 650 R00001380.001SNK 160 024 D0201
MC8121SNK 160 000 R0000220.091SNK 160 009 D0201
UMH1SNK 900 611 R0000100.201SNK 160 001 D0201
PROCAP81SNK 900 613 R0000201.001SNK 160 013 D0201
SAT81SNK 900 616 R000056.001SNK 160 013 D0201
(ing)
Pack
WeightTechnical Datasheet
piecesg (1 pce) PDF
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.