ABB S201P-K4 Technical data

System pro M compact S200P miniature circuit breakers are current limiting. They have
PRODUCT-DETAILS
S201P-K4
Miniature Circuit Breaker - S200P - 1P - K - 4 ampere
General Information
Extended Product Type
Product ID
EAN
Catalog Description
two different tripping mechanisms, the delayed thermal tripping mechanism for
overload protection and the electromechanic tripping mechanism for short circuit
protection. They are available in different characteristics (B,C,D,K,Z), configurations
Long Description
(1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 25 kA at 230/400 V AC) and rated
currents (up to 63A). All MCBs of the product range S200P comply with IEC/EN 60898-
1, IEC/EN 609 47-2, UL1077 and CSA 22.2 No. 235, allowing the use for residential,
commercial and industrial applications. Bottom-fitting auxiliary contact can be
Miniature Circuit Breaker - S200P - 1P - K - 4 ampere
mounted on S200P to save 50% space.
S201P-K4
2CDS281001R0337
Technical
Standards
Poles
)
n
Rated Operational Voltage
acc. to IEC 60898-1 230 V AC acc. to IEC 60947-2 230 V AC
CSA 22.2 No. 235
IEC/EN 60947-2
UL 1077
1 Number of Poles
1 Number of Protected
K Tripping Characteristic
4 A Rated Current (I
2.6 W Power Loss
S201P-K4
at Rated Operating Conditions per Pole 2.6 W
(Ui)
Operational Voltage
Rated Frequency (f)
Capacity (I
Circuit Breaking Capacity (I
Circuit Breaking Capacity (I
Rated Impulse Withstand Voltage (U )
Indication
Connecting Capacity
Driver
Mounting on DIN Rail
Connection
)
cn
)
cu
)
cs
imp
Maximum (Incl. Tolerance) 253 V AC / 242 V DC
Failsafe Bi-directional Cylinder-lift Terminal Screw Terminal Type
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
acc. to IEC/EN 60664-1 440 V Rated Insulation Voltage
Maximum (Incl. Tolerance) 72 V DC
50 Hz 60 Hz
25 kA Rated Short-Circuit
(230 V AC) 25 kA Rated Ultimate Short-
(230 V AC) 12.5 kA Rated Service Short-
3 Energy Limiting Class
III Overvoltage Category
3 Pollution Degree
4 kV
(6.2 kV @ sea level) kV
(5.0 kV @ 2000 m) kV
50 / 60 Hz, 1 min: 2 kV Dielectric Test Voltage
Insulation Group II, RAL 7035 Housing Material
Insulation group II, black, sealable Actuator Type
Insulation Group II, Black, Sealable Actuator Material
I / O Actuator Marking
Red ON / Green OFF Contact Position
IP20 Degree of Protection
IP40 in enclosure with cover Remarks
20000 AC cycle Electrical Endurance
20000 cycle
Screw Terminals Terminal Type
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 16 mm²
Flexible 0.75 ... 16 mm²
Rigid 0.75 ... 25 mm²
Stranded 0.75 ... 25 mm²
2.8 N·m Tightening Torque
Pozidriv 2 Recommended Screw
Any Mounting Position
69 mm Built-In Depth (t2)
acc. to DIN 43880 1 Installation Size
Arbitrary Power Supply
2
Environmental
Ambient Air Temperature
to IEC 60068-2-27
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In Resistance to Vibrations
acc. to IEC 60068-2-6
Environmental Conditions
Following EU Directive 2011/65/EU RoHS Status
Operation -25 ... +55 °C
Storage -40 ... +70 °C
25g / 2 shocks / 13 ms Resistance to Shock acc.
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %