PRODUCT-DETAILS
S201M-B50
Miniature Circuit Breaker - S200M - 1P - B - 50
ampere
General Information
Extended Product Type
Product ID
EAN
Catalog Description
System pro M compact S200M miniature circuit breakers are current limiting. They
have two different tripping mechanisms, the delayed thermal tripping mechanism for
overload protection and the electromechanic tripping mechanism for short circuit
protection. They are available in different characteristics (B,C,D,K,Z), configurations
Long Description
(1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated
currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-
1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial
applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50%
Miniature Circuit Breaker - S200M - 1P - B - 50 ampere
S201M-B50
2CDS271001R0505
4016779543811
space.
Technical
Standards
Poles
)
n
Rated Operational
Voltage
Power Loss
at Rated Operating Conditions per Pole 3.25 W
acc. to IEC 60898-1 230 / 400 V AC
acc. to IEC 60947-2 230 V AC
IEC/EN 60898-1
IEC/EN 60947-2
1 Number of Poles
1 Number of Protected
B Tripping Characteristic
50 A Rated Current (I
3.25 W

S201M-B50
2
(Ui)
Operational Voltage
Rated Frequency (f)
Capacity (I
Rated Ultimate ShortCircuit Breaking
Capacity (I
Circuit Breaking
Capacity (I
Rated Impulse
Withstand Voltage (U
)
Indication
Electrical Endurance
Connecting Capacity
Driver
Mounting on DIN Rail
Connection
)
cn
)
cu
)
cs
imp
Failsafe Bi-directional Cylinder-lift Terminal Screw Terminal Type
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
acc. to IEC/EN 60664-1 440 V Rated Insulation Voltage
Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Maximum 253 V AC
Maximum 72 V DC
Minimum 12 V AC
Minimum 12 V DC
50 Hz
60 Hz
(230 / 400 V AC) 10 kA Rated Short-Circuit
(133 V AC) 25 kA
(230 V AC) 15 kA
(133 V AC) 18.8 kA Rated Service Short-
3 Energy Limiting Class
III Overvoltage Category
3 Pollution Degree
4 kV
(6.2 kV @ sea level)
(5.0 kV @ 2000 m)
50 / 60 Hz, 1 min: 2 kV Dielectric Test Voltage
Insulation Group II, RAL 7035 Housing Material
Insulation group II, black, sealable Actuator Type
Insulation Group II, Black, Sealable Actuator Material
I / O Actuator Marking
Red ON / Green OFF Contact Position
IP20 Degree of Protection
IP40 in enclosure with cover Remarks
20000 AC cycle
10000 AC cycle
20000 cycle
Screw Terminals Terminal Type
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
2.8 N·m Tightening Torque
Pozidriv 2 Recommended Screw
Any Mounting Position
69 mm Built-In Depth (t2)
acc. to DIN 43880 1 Installation Size
Arbitrary Power Supply
Environmental
Ambient Air
Temperature
Temperature
to IEC 60068-2-27
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In Resistance to Vibrations
Operation -25 ... +55 °C
Storage -40 ... +70 °C
30 °C Reference Ambient Air
25g / 2 shocks / 13 ms Resistance to Shock acc.