ABB S201-K0.5 Technical data

currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1,
PRODUCT-DETAILS
S201-K0,5
Miniature Circuit Breaker - S200 - 1P - K - 0.5 ampere
General Information
Extended Product Type
Product ID
EAN
Catalog Description
System pro M compact S200 miniature circuit breakers are current limiting. They have
two different tripping mechanisms, the delayed thermal tripping mechanism for
overload protection and the electromechanic tripping mechanism for short circuit
protection. They are available in different characteristics (B,C,D,K,Z), configurations
Long Description
(1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated
IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial
applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50%
Miniature Circuit Breaker - S200 - 1P - K - 0.5 ampere
S201-K0,5
2CDS251001R0157
space.
Technical
Standards
Poles
)
n
Rated Operational Voltage
Power Loss
at Rated Operating Conditions per Pole 1.1 W
acc. to IEC 60898-1 230 / 400 V AC
acc. to IEC 60947-2 230 V AC
IEC/EN 60947-2
UL 1077
1 Number of Poles
1 Number of Protected
K Tripping Characteristic
0.5 A Rated Current (I
1.1 W
S201-K0,5
2
(Ui)
Operational Voltage
Rated Frequency (f)
Rated Ultimate Short­Circuit Breaking Capacity (I
Circuit Breaking Capacity (I
Rated Impulse Withstand Voltage (U )
Indication
Connecting Capacity
Driver
Mounting on DIN Rail
Connection
)
cu
)
cs
imp
Failsafe Bi-directional Cylinder-lift Terminal Screw Terminal Type
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
acc. to IEC/EN 60664-1 440 V Rated Insulation Voltage
Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Minimum 12 V AC / 12 V DC
50 Hz 60 Hz
(133 V AC) 20 kA (230 V AC) 10 kA
(133 V AC) 15 kA Rated Service Short-
3 Energy Limiting Class
III Overvoltage Category
3 Pollution Degree
4 kV
(6.2 kV @ sea level) kV
(5.0 kV @ 2000 m) kV
50 / 60 Hz, 1 min: 2 kV Dielectric Test Voltage
Insulation Group II, RAL 7035 Housing Material
Insulation group II, black, sealable Actuator Type
Insulation Group II, Black, Sealable Actuator Material
I / O Actuator Marking
Red ON / Green OFF Contact Position
IP20 Degree of Protection
IP40 in enclosure with cover Remarks
20000 AC cycle Electrical Endurance
20000 cycle
Screw Terminals Terminal Type
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
2.8 N·m Tightening Torque
Pozidriv 2 Recommended Screw
Any Mounting Position
69 mm Built-In Depth (t2)
acc. to DIN 43880 1 Installation Size
Arbitrary Power Supply
Environmental
Ambient Air Temperature
to IEC 60068-2-27
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In Resistance to Vibrations
acc. to IEC 60068-2-6
Environmental Conditions
Following EU Directive 2002/95/EC August 18, 2005 and amendment RoHS Status
Operation -25 ... +55 °C
Storage -40 ... +70 °C
25g / 2 shocks / 13 ms Resistance to Shock acc.
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %