NF71E-.. / NFZ71E-.. Contactor Relays
AC / DC Operated - with Screw Terminals
NF(Z) contactor relays are used for switching auxiliary and control circuits.
NF(Z) contactor relays include an electronic coil interface providing – reduced pull-in and holding consumption, particularly for AC control circuits Only four coils are needed to cover control voltages between 24...500 V – 50/60 Hz or 20...500 V DC NF(Z) offer extended operating limits and are suitable worldwide for different control voltages. e.g.: the coil 100...250 V 50/60 Hz - DC is suitable for Europe (230 V 50 Hz) and for North America (120 V 60 Hz and 208 V 60 Hz). NF(Z) contactors can manage large control voltage variations. NFZ contactor relays equipped with a 24...60 V 50/60 Hz - 20...60 V DC – coil allow direct control by 24 V DC 500 mA PLC-output NFZ contactor relays withstand short voltage dips and voltage sags – (SEMI F47-0706 compliance) NF(Z) contactor relays have built-in surge protection and do not require – additional surge suppressors The contactor relays have mechanically-linked auxiliary contacts – compliant with Annex L of IEC 60947-5-1 and include the "Mechanically Linked" symbol on their side.
3D CAD outline drawings available on «Control Product 3D» portal
Ordering Details
Number of contacts Control voltage Type Order code EAN Weight
1st stack Uc min. ... Uc max.
2nd stack
Pack
(ing)
1 piece
V 50/60 Hz V DC
kg
Contactor Relays
24...60 20...60
48...130 48...130
100...250 100...250
250...500 250...500
Note: NF71E-11 not suitable for a direct control by PLC-output. NF71E-11 available in some countries: please consult your ABB representative.
NF71E-11 1SBH 137 001 R1171 NF71E-12 1SBH 137 001 R1271 NF71E-13 1SBH 137 001 R1371 NF71E-14 1SBH 137 001 R1471
3471523100411 0.320 3471523100428 0.320 3471523100435 0.320 3471523100442 0.360
Contactor Relays - Low Consumption
- 12...20
24...60 20...60
48...130 48...130
100...250 100...250
Note: Only NFZ contactor relays with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole
NFZ71E-20 1SBH 136 001 R2071 NFZ71E-21 1SBH 136 001 R2171 NFZ71E-22 1SBH 136 001 R2271 NFZ71E-23 1SBH 136 001 R2371
3471523102002 0.360 3471523102019 0.360 3471523102026 0.360 3471523102033 0.360
Certifications and Approvals
ABB | Technical Datasheet 1SBC101433D0201 1
2 Technical Datasheet 1SBC101433D0201 | ABB
Contact Utilization Characteristics according to IEC
Standards IEC 60947-1 / 60947-5-1 and EN 60947-1 / 60947-5-1 Rated operational voltage Ue max. 690 V Conventional free-air thermal current Ith θ ≤ 40 °C 16 A Rated frequency limits 25 ... 400 Hz Rated operational current Ie / AC-15
acc. to IEC 60947-5-1
Making capacity AC-15 10 x Ie AC-15 acc. to IEC 60947-5-1 Breaking capacity AC-15 10 x Ie AC-15 acc. to IEC 60947-5-1 Rated operational current Ie / DC-13
acc. to IEC 60947-5-1
Short-circuit protection gG type fuse 10 A Rated short-time withstand current I
cw
Minimum switching capacity 12 V / 3 mA
with failure rate acc. to IEC 60947-5-4
Non-overlapping time between N.O. and N.C. contacts ≥ 2 ms Heat dissipation per pole at 6 A 0.1 W Max. electrical switching frequency
24-127 V 50/60 Hz 220-240 V 50/60 Hz 400-440 V 50/60 Hz
500 V 50/60 Hz 690 V 50/60 Hz
24 V DC 48 V DC
72 V DC 110 V DC 125 V DC 220 V DC 250 V DC 400 V DC 500 V DC 600 V DC
for 1.0 s
for 0.1 s
AC-15 DC-13
6 A 4 A 3 A 2 A 2 A
6 A / 144 W
2.8 A / 134 W 1 A / 72 W
0.55 A / 60 W
0.55 A / 69 W
0.27 A / 60 W
0.27 A / 68 W
0.15 A / 60 W
0.13 A / 65 W
0.1 A / 60 W
100 A 140 A
-7
10
1200 cycles/h 900 cycles/h
Main Pole - Utilization Characteristics according to UL / CSA
Standards UL 508, CSA C22.2 N°14 Rated insulation voltage U
i
Max. rated voltage 600 V AC, 600 V DC Pilot duty A600, Q600
AC thermal rated current 10 A AC maximum volt-ampere making 7200 VA AC maximum volt-ampere breaking 720 VA DC thermal rated current 2.5 A DC maximum volt-ampere making-breaking 69 VA
600 V
ABB | Technical Datasheet 1SBC101433D0201 3
General Technical Data
B2
A
A
B1
C2
C1
Pos. 5
Pos. 3
Pos
. 2
Pos. 1 Pos. 1 ± 30°
+30° -30°
Pos. 4
Rated insulation voltage Ui
acc. to IEC 60947-5-1
acc. to UL / CSA
Rated impulse withstand voltage Uimp 6 kV Electromagnetic compatibility Devices complying with IEC 60947-1 / EN 60947-1 - Environment A Ambient air temperature close to contactor
Operation in free air -40 ... +70 °C Storage -60 ... +80 °C
Climatic withstand Category B according to IEC 60947-1 Annex Q Operating altitude ≤ 3000 m Mechanical durability
Number of operating cycles 20 millions operating cycles Max. switching frequency 6000 cycles/h
Shock withstand
acc. IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Closed or open
Shock direction
position
Vibration withstand 5 ... 300 Hz
acc. to IEC 60068-2-6
690 V 600 V
1/2 sinusoidal shock for 11 ms: no change in contact position
A
30 g
B1
25 g Closed position / 5 g Open position
B2
15 g
C1
25 g
C2
25 g
4 g Closed position / 2 g Open position
Magnet System Characteristics
Coil operating limits
acc. to IEC 60947-5-1
AC control voltage Rated control circuit voltage Uc 24 ... 500 V AC 50/60 Hz Coil consumption
Average pull-in value
Average holding value
DC control voltage Rated control circuit voltage Uc 12 ... 500 V DC
Coil consumption
Average pull-in value
Average holding value
PLC-Output control (NFZ) ≥ 500 mA 24 V DC Drop-out voltage in % of Uc min. ≤ 60 % Uc min Voltage sag immunity according to SEMI F47-0706 (NFZ) conditions of use on request Dips withstand (level 0% according to IEC 61000-4-11) (NFZ) 22 ms average for Uc = 24 ... 250 V 50/60Hz
-20 °C ≤ θ ≤ +60 °C
Operating time
between coil energization and:
between coil de-energization and:
N.O. contact closing N.C. contact opening N.O. contact opening
N.C. contact closing
AC supply
DC supply
at θ ≤ 60°C 0.85 x Uc min ... 1.1 x Uc max at θ ≤ 70°C 0.85 x Uc min ... Uc max
at θ ≤ 60°C 0.85 x Uc min ... 1.1 x Uc max at θ ≤ 70°C (NF) 0.85 x Uc min ... Uc max - (NFZ) 0.85 x Uc min ... 1.1 x Uc max
(NF) 50 VA - (NFZ) 16 VA (NF) 2.2 VA / 2 W - (NFZ) 1.7 VA / 1.5 W
(NF) 50 W - (NFZ) 12 ... 16 W (NF) 2 W - (NFZ) 1.7 W
40 ... 95 ms 38 ... 90 ms 11 ... 95 ms 13 ... 98 ms
Mounting Characteristics
Mounting positions
Max. add-on N.C. auxiliary contacts: see accessory fitting details for a NF contactor relay
Mounting distances The contactor relays can be assembled side by side. Fixing
on rail according to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm by screws (not supplied) 2 x M4 screws placed diagonally