NF(Z) contactor relays are used for switching auxiliary
and control circuits.
NF(Z) contactor relays include an electronic coil interface providing –
reduced pull-in and holding consumption, particularly for AC control
circuits
Only four coils are needed to cover control voltages between 24...500 V –
50/60 Hz or 20...500 V DC
NF(Z) offer extended operating limits and are suitable worldwide for
different control voltages. e.g.: the coil 100...250 V 50/60 Hz - DC is
suitable for Europe (230 V 50 Hz) and for North America (120 V 60 Hz
and 208 V 60 Hz).
NF(Z) contactors can manage large control voltage variations.
NFZ contactor relays equipped with a 24...60 V 50/60 Hz - 20...60 V DC –
coil allow direct control by 24 V DC 500 mA PLC-output
NFZ contactor relays withstand short voltage dips and voltage sags –
(SEMI F47-0706 compliance)
NF(Z) contactor relays have built-in surge protection and do not require –
additional surge suppressors
The contactor relays have mechanically-linked auxiliary contacts –
compliant with Annex L of IEC 60947-5-1 and include the "Mechanically
Linked" symbol on their side.
3D CAD outline drawings available on «Control Product 3D» portal
Ordering Details
Number of contactsControl voltageTypeOrder codeEANWeight
1st stackUc min. ... Uc max.
2nd stack
Pack
(ing)
1 piece
V 50/60 Hz V DC
kg
Contactor Relays
24...6020...60
48...13048...130
100...250100...250
250...500250...500
Note: NF71E-11 not suitable for a direct control by PLC-output. NF71E-11 available in some countries: please consult your ABB representative.
Note: Only NFZ contactor relays with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole
Contact Utilization Characteristics according to IEC
StandardsIEC 60947-1 / 60947-5-1 and EN 60947-1 / 60947-5-1
Rated operational voltage Ue max.690 V
Conventional free-air thermal current Ith θ ≤ 40 °C16 A
Rated frequency limits25 ... 400 Hz
Rated operational current Ie / AC-15
acc. to IEC 60947-5-1
Making capacity AC-1510 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-1510 x Ie AC-15 acc. to IEC 60947-5-1
Rated operational current Ie / DC-13
acc. to IEC 60947-5-1
Short-circuit protection gG type fuse10 A
Rated short-time withstand current I
cw
Minimum switching capacity12 V / 3 mA
with failure rate acc. to IEC 60947-5-4
Non-overlapping time between N.O. and N.C. contacts≥ 2 ms
Heat dissipation per pole at 6 A0.1 W
Max. electrical switching frequency
24-127 V 50/60 Hz
220-240 V 50/60 Hz
400-440 V 50/60 Hz
500 V 50/60 Hz
690 V 50/60 Hz
24 V DC
48 V DC
72 V DC
110 V DC
125 V DC
220 V DC
250 V DC
400 V DC
500 V DC
600 V DC
for 1.0 s
for 0.1 s
AC-15
DC-13
6 A
4 A
3 A
2 A
2 A
6 A / 144 W
2.8 A / 134 W
1 A / 72 W
0.55 A / 60 W
0.55 A / 69 W
0.27 A / 60 W
0.27 A / 68 W
0.15 A / 60 W
0.13 A / 65 W
0.1 A / 60 W
100 A
140 A
-7
10
1200 cycles/h
900 cycles/h
Main Pole - Utilization Characteristics according to UL / CSA
StandardsUL 508, CSA C22.2 N°14
Rated insulation voltage U
i
Max. rated voltage600 V AC, 600 V DC
Pilot dutyA600, Q600
AC thermal rated current10 A
AC maximum volt-ampere making7200 VA
AC maximum volt-ampere breaking720 VA
DC thermal rated current2.5 A
DC maximum volt-ampere making-breaking69 VA
600 V
ABB | Technical Datasheet 1SBC101433D0201 3
General Technical Data
B2
A
A
B1
C2
C1
Pos. 5
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Rated insulation voltage Ui
acc. to IEC 60947-5-1
acc. to UL / CSA
Rated impulse withstand voltage Uimp6 kV
Electromagnetic compatibilityDevices complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation in free air-40 ... +70 °C
Storage-60 ... +80 °C
Climatic withstandCategory B according to IEC 60947-1 Annex Q
Operating altitude≤ 3000 m
Mechanical durability
Number of operating cycles20 millions operating cycles
Max. switching frequency6000 cycles/h
Shock withstand
acc. IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Closed or open
Shock direction
position
Vibration withstand5 ... 300 Hz
acc. to IEC 60068-2-6
690 V
600 V
1/2 sinusoidal shock for 11 ms: no change in contact position
A
30 g
B1
25 g Closed position / 5 g Open position
B2
15 g
C1
25 g
C2
25 g
4 g Closed position / 2 g Open position
Magnet System Characteristics
Coil operating limits
acc. to IEC 60947-5-1
AC control voltage Rated control circuit voltage Uc24 ... 500 V AC
50/60 HzCoil consumption
Average pull-in value
Average holding value
DC control voltage Rated control circuit voltage Uc12 ... 500 V DC
Coil consumption
Average pull-in value
Average holding value
PLC-Output control(NFZ) ≥ 500 mA 24 V DC
Drop-out voltage in % of Uc min.≤ 60 % Uc min
Voltage sag immunity according to SEMI F47-0706(NFZ) conditions of use on request
Dips withstand (level 0% according to IEC 61000-4-11)(NFZ) 22 ms average for Uc = 24 ... 250 V 50/60Hz