ABB KLF Instruction Leaflet

ABB Power T&D Company Inc.
Power Automation and Protection Division Coral Springs, FL 33065
Type KLF
Instruction Leaflet
41-748.21C
Effective: January 1997 Supersedes I.L. 41-748.21B, Dated December 1993
( | ) Denotes Changed Since Previous Issue
CAUTION
!
Before putting protective relays into ser­vice, make sure that all moving parts oper­ate freely, inspect the contacts to see that they are clean and close properly, and oper­ate the relay to check the settings and elec­trical connections.
1. APPLICATION
These relays have been specially designed and tested to establish their suitability for Class 1E applications in accordance with the ABB Power T&D Company program for Class 1E Qulification Testing ad detailed in bulletin STR-1. Materials have been selected and tested to insure that the relays will perform their intended functions for their design life when operated in a normal environment as defined by ANSI standards when exposed to
radiation levels up to 104 rads, and when subjected to seismic events producing a Shock Response Spectrum within the limits of the relay rating.
“Class 1E” is the safety classification of the elec­tronic equipment and systems in nuclear power generating stations that are essential to emergency shutdown of the reactor, containment isolation, cooling the reactor, and heat removal from the con­tainment and reactor, or otherwise are essential in preventing significant release of radioactive mate­rial to the environment.
The KLF relay is a single-phase relay connected to the ac side of a synchronous machine and contains three units connected so that the operation of two units sounds an alarm warning the operator of a low excitation condition, and the additional opera-
Loss-of-Field Relay
(For Class 1E Application)
tion of the third unit sets up the trip circuit. The relay can be applied without modification to all types of synchronous machines, such as turbo gen­erators, water wheel generators or motors.
The KLF relay is designed for use with 3-phase 3­wire voltage supply and may use wye or delta-con­nected voltage transformers. The type KLF-1 relay may be used to increase security during inadvert­ent loss-of-potential (such as due to a blown poten­tial fuse).
2. CONSTRUCTION
The relay consists of two (2) air-gap transformers (compensators), two tapped auto-transformers, one reactor, one cylinder-type distance IT, direc­tional unit with adjustable reactor, an under-voltage unit with adjustable resistor, telephone relay with solid state time delay circuit, and an ICS indicating contactor switch.
2.1 Compensator
The compensators, which are designated TA and TC, are two (2) winding air-gap transformers (Fig-
ure 2). The primary or current winding of the
long-reach compensator TA has seven taps which terminate at the tap block. They are marked 2.4,
3.16, 4.35, 5.93, 8.3, 11.5, 15.8. The primary wind­ing of the short-reach compensator TC also has
seven taps which terminate at this tap block. They are marked 0.0, 0.91, 1.27, 1.82, 2.55, 3.64, 5.1. Voltage is induced in the secondary which is pro­portional to the primary tap and current magnitude. This proportionality is established by the cross sec­tional area of the laminated steel core, the length of an air gap which is located in the center of the coil, and the tightness of the laminations. All of these factors which influence the secondary voltage pro­portionality have been precisely set at the factory.
All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
41-748.21C
Front View Rear View
Figure 1. Type KLF Relay
The clamps which hold the laminations should not be disturbed by either tightening or loosening the clamp screws.
The secondary winding is connected in series with the relay terminal voltage. Thus voltage, which is proportional to the line current, is added vectorially to the relay terminal voltage.
2.2Auto-Transformer
The auto-transformer has three taps on its main winding, S, which are numbered 1, 2, and 3 on the tap block. A tertiary winding M has four taps which may be connected additively or subtractively to inversely modify the setting by any value from -15 to +15 percent in steps of 3 percent.
2
The sign of M is negative when the R lead is above the L lead. M is positive when L is in a tap location which is above the tap location of the R lead. The M setting is determined by the sum of per unit val­ues between the R and L lead. The actual per unit values which appear on the tap plate between taps are 0,.03,.06, and.06.
The auto-transformer makes it possible to expand the basic ranges of the long and the short reach
compensators by a multiplier of . Any relay
S
-------------­1 M±
ohm setting can be made within±1.5 percent from
2.08 ohms to 56 ohms for the long-reach and from.79 ohms to 18 ohms for the short-reach.
Sub 1 185A181
Figure 2. Compensator Construction
2.3 Impedance Tripping Unit
The distance unit is a four pole induction cylinder type unit. The operating torque of the unit is pro­portional to the product of the voltage quantities applied to the unit and the sine of the phase angle between the applied voltages. The direction of the torque depends on the impedance phasor seen by the relay with respect to its characteristic circle.
Mechanically, the cylinder unit is composed of four basic components: A die-cast aluminum frame, and electromagnet, a moving element assembly, and a molded bridge. The frame serves as a mounting structure for the magnetic core. The magnetic core which houses the lower pin bearing is secured by the frame by a locking nut. The bear­ing can be replaced, if necessary, without having to remove the magnetic core from the frame.
The electromagnet has two sets of two series con­nected coils mounted diametrically opposite one another to excite each set of poles. Locating pins on the electromagnet are used to accurately posi­tion the lower pin bearing, which is mounted on the frame, with respect to the upper pin bearing, which is threaded into the bridge. The electromagnet is secured to the frame by four mounting screws.
The moving element assembly consists of a spiral spring, contact carrying number, and an aluminum cylinder assembled to a molded hub which holds the shaft. The hub to which the moving-contact
41-748.21C
arm is clamped has a wedge and cam construc­tion, to provide low-bounce contact action. A casual inspection of the assembly might lead one to think that the contact arm bracket does not clamp on the hub as tightly as it should. However, this adjustment is accurately made at the factory and is locked in place with a lock nut and should not be changed. Optimum contact action is obtained when a force of 4 to 10 grams pressure applied to the face of the moving contact will make the arm slip from the condition of reset to the point where the clamp projection begins to ride up on the wedge. The free travel can vary between 15° to
20°. The shaft has removable top and bottom jewel
bearings. The shaft rides between the bottom pin bearing and the upper pin bearing with the cylinder rotating in an air-gap formed by the electromagnet and the magnetic core. The stops are an integral part of the bridge.
The bridge is secured to the electromagnet and frame by two mounting screws. In addition to hold­ing the upper pin bearing, the bridge is used for mounting the adjustable stationary contact hous­ing. This stationary contact has .002 to .006 inch follow which is set at the factory by means of the adjusting screw. After the adjustment is made the screw is sealed in position with a material which flows around the threads and then solidifies. The stationary contact housing is held in position by a spring type clamp The spring adjuster is located on the underside of the bridge and is attached to the moving contact arm by a spiral spring. The spring adjuster is also held in place by a spring type clamp.
When contacts close, the electrical connection is made through the stationary contact housing clamp, to the moving contact, through the spiral spring and out to the spring adjuster clamp.
2.4 Directional Unit
The directional unit is an induction cylinder unit operating on the interaction between the polarizing circuit flux and the operating circuit flux.
Mechanically, the directional unit is composed of the same basic components as the distance unit: a die-cast aluminum frame, an electromagnet, a moving element assembly, and a molded bridge.
The electromagnet has two series-connected polarizing coils mounted diametrically opposite one another; two series-connected operating coils
3
41-748.21C
* Sub 4 3531A58
Figure 3. Internal Schematic of Type KLF Relay in FT-41 Case
*Denotes Change
mounted diametrically opposite one another; two magnetic adjusting plugs; upper and lower adjusting plug clips, and two locating pins. The locating pins are used to accurately position the lower pin bearing, which is threaded into the bridge. The electromagnet is secured to the frame by four mounting screws.
The moving element assembly consists of a spiral spring, contact carrying mem­ber, and an aluminum cylinder assem­bled to a molded hub which holds the shaft. The shaft has removable top and bottom jewel bearings. The shaft rides between the bottom pin bearing and the upper pin bearing with the cylinder rotat­ing in an air gap formed by the electro­magnet and the magnetic core.
The bridge is secured to the electromag­net and frame by two mounting screws. In addition to holding the upper pin bear­ing, the bridge is used for mounting the adjustable stationary contact housing. The stationary contact housing is held in position by a spring-type clamp. The spring adjuster is located on the under­side of the bridge and is attached to the moving contact arm by a spiral spring. The spring adjuster is also held in place by a spring type clamp.
2.5 Undervoltage Unit
The voltage unit is an induction-cylinder unit.
Mechanically, the voltage unit is com­posed, like the directional unit, of four components: A die-cast aluminum frame, and electromagnet, a moving element assembly, and a molded bridge.
The electromagnet has two pairs of volt­age coils. Each pair of diametrically opposed coils is connected in series. In addition one pair is in series with an adjustable resistor. These sets are in
Sub 4 3533A29
parallel as shown in Figure 3. The adjustable resistor serves not only to shift the phase angle of the one flux with
Figure 4. KLF Time Delay Schematic
respect to the other to produce torque, but it also provides a pickup adjustment.
4
41-748.21C
Sub 3 1487B21
Figure 5. External Schematic of Type KLF Relay
Otherwise the undervoltage unit is similar in its construction to the directional unit.
2.6 Solid State Time Delay Circuit
The telephone relay (x) is energized through a solid state time delay circuit (TD) as shown in Fig-
ure 3. The solid state time delay circuit shown in Figure 4 consists basically of an adjustable inte-
grating RC circuit with quick reset. The RC circuit is adjusted to provide the voltage level to trigger the SCR through a multi-layer silicon switch. The SCR in turn energizes the relay.
2.7 Indicating Contactor Switch Unit (ICS)
The dc indicating contactor switch is a small clap­per-type device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts, complet­ing the trip circuit. Also during this operation two fingers on the armature deflect a spring located on the front of the switch, which allows the operation indicator target to drop. The target is reset from the outside of the case by a push rod located at the bottom of the cover. The front spring, in addition to holding the target, provides restraint for the arma­ture and thus controls the pickup of the switch.
3. OPERATION
The relay is connected and applied to the system as shown if Figure 5. The directional unit closes its contacts for lagging VAR flow into the machine. Its zero torque line has been set at -13° from the
R-axis. Its primary function is to prevent operation of the relay during external faults. The impedance unit closes its contacts when, as a result of reduc­tion in excitation, the impedance of the machine as viewed from its terminals is less than a predeter­mined value. The operation of both impedance and directional units energize the time delay circuit which operates the X unit after .4 ±.05 seconds.
The operation of impedance, directional and X unit sounds an alarm, and the additional operation of the under voltage unit trips the machine. This time delay is to insure positive contact coordination under all possible operating conditions. During a seismic event which exposes the relay to a ZPA level of 5.7g, the operate time of the X unit may vary from .25 second to 1.25 seconds due to bounce induced in the Z and the D contacts. Dur­ing normal conditions, all contacts are open.
3.1 Principle of Distance Unit Operation
The distance unit is an induction cylinder unit hav­ing directional characteristics. Operation depends on the phase relationship between magnetic fluxes in the poles of the electromagnet.
5
41-748.21C
Sub 2 185A331
Figure 7. Effect of Compensator Voltages
(ZC is positive)
One set of opposite poles, designated as the oper­ating poles are energized by voltage V1Tmodified
by a voltage derived from the long reach compen­sator TA. The other set of poles (polarizing) are
energized by the same voltage V1T except modi­fied by a voltage derived from the short reach com-
pensator TC. The flux in the polarizing pole is so adjusted that the unit closes its contacts whenever
flux in the operating set of poles leads the flux in the polarizing set.
The voltage V1T is equal to:
V120.5 V
+ 1.5 V
==
1T
23
1N
(1)V
As shown in Figure 5, one-half of V23, voltage is physically derived in the relay at midtap of a reac-
tor connected across voltage V23. Reach of the distance unit is determined by com-
pensators TA and TC as modified by auto-trans­former settings. Compensators TA and TC are designed so the their mutual impedances ZA and ZC have known and adjustable values as described below under “CHARACTERISTICS” and
SETTING CALCULATIONS”. The mutual imped- ance of a compensator is defined here as the ratio of secondary induced voltage to primary current and is equal to T. Each secondary compensator voltage is in series with the voltage V1T. Compen-
sator voltages are equal to 1.5 I1 ZAfor long reach compensator and 1.5 I1 ZC for short reach com­pensator, where I, is the relay current.
Figure 6 shows how the compensation voltages
1.5 I1 ZA and 1.5 I1 ZC influence the R-X circle. Notice that ZA independently determines the “long reach”, while ZC independently determines the “short reach”. With the reversing links in the nor-
mal position (+ZC) the circle includes the origin; with the opposite link position (-ZC) the circle misses the origin. The following paragraphs
explain this compensator action. Referring to Figure 5 notice that resistor RB and
capacitor CB cause the polarizing voltage to be shifted 90° in the leading direction. Thus, when the current is zero, polarizing voltage V
leads the
POL
operating voltage VOP by 90° and of sufficient magnitude to operate the relay. This means the
apparent impedance is along the X axis. Notice in Figure 7(b) that the ZA compensation reverses the
operating voltage phase position. The relay bal­ances when this voltage is zero. Note also this bal­ance is unaffected by the ZC compensation, since
this compensation merely increases the size of V
.
POL
Sub 2
185A182
Figure 6. R-X Diagram Characteristics with various
ZC - Compensator Settings.
6
For lagging current conditions notice Figure 7(c) illustrates how V
is reversed by the ZC com-
POL
pensation. In this case the ZA compensation has no effect of the balance point. This explains why
the reach point is fixed independently by ZC. Figure 7 assumes that ZC is positive (circle
includes origin). If the current coil link is reversed,
41-748.21C
the compensation becomes +1.5 IZC. In Figure 7(b) this change would result in V
POL
being
reduced rather than increased by the compensa­tion. As the current increases V
will finally be
POL
reversed establishing restraining torque. Thus, the current need not reverse in order to obtain a “short reach” balance point. Instead the apparent imped­ance need only move towards the origin in the - X circle region to find the balance point. Therefore the circle does not include the origin with a reversed link position.
4. CHARACTERISTICS
The type KLF relay is available in one range.
4.1 Distance Unit
The distance unit can be set to have characteristic circles that pass through origin, include it, or exclude it, as shown in Figure 6.
The ZAand ZC values are determined by compen­sator settings and modified by auto-transformer
settings, S, L, and R. The impedance settings in ohms reach can be made for any value from 2.08 to 56 ohms for ZA, and from 0.79 ohm to 18 ohms
for ZC in steps of 3 percent. The taps are marked as follows:
T
-------------------------------------------------------------------------------------
2.4 3.16 4.35 5.93 8.3 11.5 15.8,,,,,,
-------------------------------------------------------------------------------------
0.0 0.91 1.27 1.82 2.55 3.64 5.1,,,,,, ,()
S
ASC
----------------------
123,,
---------------------------------------------------------------------------------
values between taps .03, .06, .06±
A
T
C
MAMC,()
age. This voltage is equal to 1.5 V1N voltage. The contacts can be adjusted to close over the range of
65 to 85 percent of normal system voltage. The dropout ratio of the unit is 98 percent or higher.
4.4 Trip Circuit
The main contacts will safely close 30 amperes at 250 volts dc and the seal-in contacts of the indicat­ing contactor switch will safely carry this current long enough to trip a circuit breaker.
4.5 Trip Circuit Constant
Indicating Contactor Switch (ICS)
0.2 ampere rating
1.0 ampere rating
2.0 ampere rating
8.5 ohm dc resistance .37 ohms dc resistance .1 ohm dc resistance
4.6 Burden
Current
5 amps, 60 Hz
T
& T
A
C
Settings VA
MAX.
MIN.
Phase AB
S
= SC VA
A
1 2 3
18.0
14.4
13.9
Rating Watts + Rated
125 250
18.6
3.8
POTENTIAL
120 VOLTS, 60 Hz
Angle
of LAG
°
2
31° 39°
dc Circuit
Angle
of LAG
°
77 51°
Phase BC
Angle VA of LAG
2.6
5.9
6.6
12° 38° 42°
3.9
7.8
4.2 Directional Unit
The KLF relay is designed for potential polarization with an internal phase shifter, so that maximum torque occurs when the operating current leads the polarizing voltage by approximately 13 degrees. The minimum pickup has been set by the spring tension to be approximately 1 volt and 5 amperes at maximum torque angle.
4.3 Undervoltage Unit
The undervoltage unit is designed to close its con­tacts when the voltage is lower than the set value. The undervoltage unit is energized with V1T-volt-
4.7 Thermal Ratings
Potential: 132 volts (L-L) continuous Current: 8 amperes continuous
200 amperes for 1 second
5. SETTING CALCULATIONS
5.1 General Setting Recommendations
The KLF relay may be applied as a single-zone device, or two relays may be used to provide two-zone protection. The single-zone setting may be fully offset (Zone 1) or may include the origin (Zone 2). The two-zone application would require a
7
Loading...
+ 16 hidden pages