ABB KA-4 Instruction Leaflet

41-923.4M
Figure 1. Type KA-4 Relay without case. (Front View)
2
41-923.4M
Sub 3 629A389
Figure 2.Internal Schematic of the Type KA-4 Relay for KR
Carrier Set.
Sub 9 629A476
Figure 3. Inter nal Schema tic of the Type KA-4 Re lay for TC
Carrier Set.
Sub 1 3491A17
Modified Carrier Stop to Terminal 11 for TC Carrier Set.
Sub 1 349A16
Figure 5.Internal Schematic of the Type KA-4 Relay for the
TA-3 tones.
3
41-923.4M
shaft. The shaft has remo va ble top and botto m jewel bearings. The shaft rides between the bottom pin bearing and the upper pin bearing with the cylinder rotating in an air gap formed by the electromagnet and the magnetic core.
The bridge is secured to the electromagnet and frame by two mounti ng sc rews . In a ddi tio n t o h old in g the upper pin bear ing, the bridge is used for mount­ing the adjustable stationary contact housing. The stationary contact housing is held in position by a spring type clamp. The spring adjuste r is located on the underside of the bridge and is attached to the moving contact arm by a spiral spring. The spring adjuster is also held in place by a spring type clamp.
With the contacts closed, the el ectrical connec tion is made through the stationary contact housing clamp, to the moving contact, through the spiral spring out to the spring adjuster clamp.
When the current in the overcurrent uni t exceeds the pick-up value the contacts open, allowing positive potential to be applied to the carrier transmitter.
A transformer and cu rrent limiting reactor is used i n conjunction with the cylinder unit. The transformer supplies one set of coils on the cylinder unit with volt­age shifted by approximately 90° from the residual current supplied directly to another set of coils. The transformer and reactor are of the saturating type which limits energy to the cylinder unit and reduces the burden on the transmission line CT.
2.2. AUXILIARY UNITS
These are two solenoid- type cont actor switches des­ignated as CSP and CSG. The plunger of the contac­tor switch has a circular conduc ting disc mou nted on its lower end and as the pl unger travels upwar d, the disc bridges three silver stationary contacts. The CSP switch is ener gized by the operati on of t he sec ­ond zone or KD-10 distance relay, and the CSG switch, by the operation of the directi onal and over­current units of the KRD-4 ground relay. The contacts of the two switches are connected in parallel as shown in the internal schematic. The operation of either of these switches conn ects the carrier control circuit to negative to stop carrier, and energizes the RRT operating coil of the receiver relay unit.
Figure 6.Typical Time Characteristics of c arrier start over-
current unit of the type KA-4 Relay.
2.3. RECEIVER UNIT
The receiver unit consists of an armature and con­tacts mounted on a leaf spring supporte d symmetri­cally within a magnet frame. The armature rides in the front air-gap of the fr ame with the contacts pro­jecting outside. The poles of a permanent magnet clamp directly to each side of the frame. Two adjust­able shunts are located across the rear air-gaps. These change the reluctance of the magnetic path as shown in Figure 7 so as to force some of the flux thru the moving armature which is fastened to the fram e midway between the two rear air gaps. Flux in the armature polarizes it and creates a magnetic bias, causing it to move towards either the left or right, depending upon the adjustment.
Tw o st ati ona ry c onta ct sc re ws ar e m ount ed t o t he l eft (front view) of the moving contact assembly and adjusted for normally open contac ts. These co ntacts are designated, RRP and RRG, and are connected in the phase and ground trip circuit respecti vely. These contacts are operate d by two concentric coils, RRT and RRH, which are placed around the armature and within the magnetic fra me. RRT is the operating coil and receives its en ergy from the local battery when either CSP or CSG is clo se d. R R H is th e h o ld ing c oil and receives its en ergy from the carrier transmitted either from the local tra nsmi tter or th e o ne a t th e en d of the line section. These two coils are connect ed in oppose each other with the operating coil, RRT oper-
4
Shunt
41-923.4M
N
S
N
BALANCED AIR GAPS UNBALANCED AIR GAPS
S
Moving Contact
Figure 7. Permanent Magnet Flux Paths of Receiver and Alarm Units
Permanent Magnet
Armature
ating to close the RRP and RRG contacts and trip; and the holding co il, R RH to h old t he RRP and RRG contacts open and block tripping. The restraining torque of the RRH coil is sufficient to overcome th e operating torque of the RRT coil. Consequently, RRP and RRG contacts cannot c lose as long as RRH is energized.
2.4. ALARM UNIT
The alarm unit is similar in construction to the receiver unit except that it is energized by a single coil and opera tes a singl e set of c ontac ts. T he c oil is energized by the received carrier to close its contacts and give an alarm. This unit has a higher pick-up than that of the receiver unit in order to obtain a direct check on the sensi tivity of the car rier transmit­ter-receiver. The failure of the alarm unit to pick-up when carrier is started indicates insufficient output from the transmitter receivers.
2.5. SQUELCH UNIT
The function of the squelch unit is to hold of the car­rier for a period o f 15 0 m il lise co nds af ter th e B r eaker “a” contact opens. This is to insure that all other ter ­minals of the line are tripp ed before allowing carrier to be transmitted for any functions.
The squelch unit is a telephone type unit of slow release type.
N
S
N
S
N
Additional Flux Path
183A062
In these relays, an electromagnet attracts a right angle iron bracket which in turn operates one nor­mally open contact. The sl ow release is obtained by a copper slug locat ed at the end opposite from the armature. When the coil beco mes deenergized, the change in flux through the slug results in an e lectro­motive force and associated current in it. This current produces a flux whic h aids the main flux and d elays the release of the arm ature. When the coil is ener­gized, the operation of the relay is not appreciably delayed because the armature is operated by flux not linking the slug.
2.6. OPERATION INDICATOR
The operation indicator gives a visual indication of a carrier tripping op eration for phase faul ts by the dis­tance relay through the RRP contac ts. For a groun d fault carrier relaying ope ration, the indi cating conta c­tor switch (ICS) located in the ground relay will drop a target.

3.0 CHARACTERISTICS

The characteristics of the various elements of the relays are as follows:
The pick-up and o perating values of thes e units are given under “Adjustments and Maintenance”.
The time characteristic of the overcurrent unit is
5
41-923.4M
For Use With KR-Set
CSP or CSG Coil CSP & CSG Tapped Resistor Carrier Resistor RRT Operating Coil RRT Coil Resistor RRH Holding Coil AL-Alarm Coil Operation Indicator (1 amp.) Squelch Unit Coil Squelch Unit Adj. Resistor
For Use With TC-Set
CSP or CSG Coil CSP & CSG Tapped Resistor Carrier Resistor RRT Operating Coil RRT Coil Resistor RRH Holding Coil AL-Alarm Coil Operation Indicator (1 amp.) Squelch Unit Coil Squelch Unit Adj. Resistor
For Use With TA-3 Tones
CSP or CSG Coil CSP & CSG Tapped Resistor Carrier Resistor RRT Operating Coil RRT Coil Resistor RRH Holding Coil AL-Alarm Coil Operation Indicator (1 amp.) Squelch Unit Coil Squelch Unit Adj. Resistor
48V
Avg.
Ohms
27
200 2000 1100 1320 1700
500
0.1
3300
27
200 1000 1100 1320
20
0.1
3300
27 200 200
1100 1320 1700
500
0.1
3300
125
Avg.
Ohms
600 3750 1100 5000 1700
500
3300
-
8500
27
0.1
250
Avg.
Ohms
435
6000
19000
1100
11200
1700
500
0.1 3300 1500
the rear mounting stud or studs for projec tion mount­ing. Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal studs furnished with the rela y for thick panel mounting. The terminal studs may be easily removed or inserted by lock ing two nuts on the st ud and then turning the proper nut with a wrench.
The carrier relaying schematic (supplied with the car­rier order) should be consulted for details of the external connections of these relays.
27
600 3750 1100 5000
4
20
4
0.1
3300
-
8500
45
6000
1100
11200
20
0.1
3300
15000

6.0 ADJUSTMENTS & MAINTENANCE

-
The proper adjustments to insure correct operation of this relay have been made at the factory. Upon
4
receipt of the relay, no customer adjustments, other than those covered under “SETTINGS”, should be required.
6.1. ACCEPTANCE CHECK
27
600 4000 1100 5000 1700
500
0.1
3300
-
8500
435
6000
10600
1100
11200
1700
500
0.1
3300
15000
The following check is recommended to insure that the relay is in proper working order.
6.1.1. Overcurrent Unit
Pass 0.5 amperes of altered current through relay terminals 16 and 17, the contact should pickup within .475 and .525 amp.
shown in figure 6.
The pick-up value of the overcurrent unit can be changed from the factory adjusted value of 0.5 amperes to any value up to 1 amp. by increasing spring restraint.

4.0 SETTINGS

There are not settings to be made

5.0 INSTALLATION

The relays should be mounted on switchbo ard pan­els or their equivalent in a location free from dirt, moisture, excessive vibration, and heat. Mount the relay vertically by means of the four mounting holes on the flange for semi-flus h mou nting or by mea ns of
6
6.1.2. Auxiliary Units (CSP and CGS)
Each contactor switch has a section of a tapped resistor in series with it, and will pick up positively when rated control voltage is applied across the coil and its section of the resistor.
These units should o per at e a t 24 v olts f or the 48 -vol t relay, 60 volts for the 125-volt relay, and 120 volts for 250-volt relay. These units have an interm ittent rat­ing, and should not be energized for more than a few seconds.
6.1.3. Operation Indicator (OI)
With the polar unit contacts closed, apply direct cur ­rent to the operation indicator relay terminals. The operation indicator should pick-up a nd drop the indi­cator target between 1 ampere and 1.2 amperes dc.
41-923.4M
6.1.4. Squelch Unit (SQ)
Apply rated dc voltage to relay terminals that will energize the squelch unit and note contact operation.
6.1.5. Blocking Zener Diode
Apply rated dc voltage in series with 10,000 ohm resistors across te rminal s 8 a nd 9 wi th pos itiv e on 9 , the current leakage fl ow should not exceed .25 mA. Reserve polarity of the applied voltage; the current flow should be equ al to the applied voltage divide d by the series resistance.
6.2. FOR RELAYS TO BE USED WITH TC-TYPE CARRIER
6.2.1. Receiver Unit
Connect a jumper between the middle and left-hand contact connection of the CS G or CSP switch. The CSG switch is locate d on the left-hand pe destal and CSP is located on the right-hand pedestal on the relay (front view). Apply rated voltage across the RRT coil and the RRT coil resistor, observing polarity as shown in the internal schematic. The armature should move to the left.
To the holding coil (RRH) relay terminals, apply direct current observing pol arity. Increase the current until the armature moves to the right.
The armature should move to the right at approxi­mately 60 mA. Now reduce the current and the arma­ture should move to the left at approximately 40 mA.
6.2.2. Alarm Unit (AL)
Connect direct curren t to the alarm unit relay termi­nals. Increase the cu rrent until the contacts p ick-up. The contacts should pick up at approximately 80 mA. Now reduce the current and the contacts should open at 40 to 60 mA.
6.3. FOR RELAYS TO BE USED WITH TYPE KR CARRIER OR TA-3 TONES
6.3.1. Receiver Unit
Connect a jumper between the middle and left-hand contact connection of the CSG or CSP switch.
CSG switch is locate d on the left-hand pe destal and CSP is located on the right-hand pedestal on the
relay (front view). Apply rated voltage across the RRT coil and the RRT coil resistor, observing polarity as shown in the internal schematic. The armature should move to the left.
To the holding coil (RRH) relay terminals, apply direct current observing correct polarity. Increase the cur­rent until the armature mov es to the right. The arma­ture should move t o the r ight at a pprox imately 6 mA . Now reduce the current and the armature should move to the left at approximately 4 mA.
6.3.2. Alarm Unit (AL)
Connect direct curren t to the alarm unit relay termi­nals. Increase the curren t until the contacts pickup. The contacts should pick up at approximately 8 mA. Now reduce the current and the contacts should open at 4 to 6 mA.

7.0 ROUTINE MAINTENANCE

All relays should be inspected periodically and the operation should be checked at least once every year or at such other tim e intervals as may be dic­tated by experience to be suitable to the particular application.
All contacts should be periodically cleaned. A contact burnisher Style # 182A836H01 i s recommended for this purpose.
ing contacts is not recommended
danger of embedding small particles in the face of the soft silver and thus impairing the contact.
7.1. CALIBRATION
Use the following procedure for calibrating the relay if the relay has been taken apart for repairs or the adjustments have been disturbed. This procedure should not be used unless it is apparent that the relay is not in proper working order. (See “Acceptance Check”).
7.1.1. Overcurrent Unit
The upper bearing screw should be screwed down until there is appr oximately 1/6 4” clearanc e between it and the top of the shaft bearing. Securel y lock in position with the lock nut. T he lower bearing po sition is fixed and cannot be adjusted.
The use of abrasive mater ial for clean-
, because of the
7
41-923.4M
With the moving contact in the normally closed posi­tion, i.e., against the right side of the bridg e, screw i n the stationary conta ct until both contacts just close . Then screw in the stationary contact a pproximately one-quarter turn farther to provide the correct amount of follow for KR & TC type carrier, one-half turn for TA-3 tones.
The clamp holding the stationary contact housing need not be loosened for the adjustment since the clamp utilizes a spring- type action i n holding the s ta­tionary contact in position.
The sensitivity adjustment is made by varying the tension of the spiral spring attached to the moving element assembly. The spring is adjusted by pl acing a screwdriver or simila r tool into one of the notches located on the periphery of the spring adjuster and rotating it. The spring adjuster is located on the underside of the bridge and is held in place by a spring type clamp that d oes no t have to be lo osene d prior to making the necessary adjustments.
Pass 0.5 amp of ac t hrough relay terminals 16 and
17. Adjust the spring until the contact just opens. In a similar manner the pick- up value can be adjusted for any value between .5 and 1.0 amp.
250-volt relay. These units have an interm ittent rat­ing, and should not be energized for more than a few seconds.
7.1.3. Squelch Unit
Check operation with timer. Adjust series resistor to measure approximately 5000 ohms for 125 Vdc relays and for 13000 ohms for 250 Vdc relay. With armature closed, adjust the residual air gap to be .002” – .003”. Contact gap should measure from .020” to .035”. Check for dropout time betwe en .140 and .160 seconds. If ne cessary dropout ti me can be adjusted by changing the residu al air gap. After final adjustment the gap should be at lease .002”. The pickup time should be below 16 milliseconds at -20% rated dc voltage. If nec essary readjust series resis­tor.
7.1.4. Operation Indicator
The operation indicator s hould pickup and drop the indicator target when the current is between 1 and
1.2 amperes dc.
Make sure that the target drops freel y when the uni t operates.
7.1.2. Auxiliary Units (CSP and CSG)
The two contactor switches, CSP and CSG, have adjustable plunger trave l. Adjust the stationary core and the moving core of 1/64” when the switch is picked up. This can be done by turning the relay upside-down and screwing up the core screw of the switch until the conta cts just separate. Then back off the core screw approximately one turn and lock in place. This prevents the moving core from striking and sticking to th e stationary core beca use of resid­ual magnetism. Adjust the contact clearance for approximately 1/32” by me ans of the two small nuts on either side of the Micarta disc.
Each contactor switch has a section of a tapped resistor in series with it, and will pick up positively when rated trip circuit voltages is applied across the coil and its section of the resi stor.
The units should operate at 24 volts for the 48-volt relay, 60 volts for the 125-volt rel ay and 120 v olts for
7.2. ZENER DIODE TEST
7.2.1. F orw ard Chara ct eri st ics
Pass 200 mA of dc current through terminals 8 and 9 with positive on terminal 8. Measure voltage drop across terminal s 8 an d 9 with pos i tiv e o n 9 . T he vo lt­age drop should not exceed 3.5 volts.
7.2.2. Reverse Characteristics – Breakdown Voltage
The breakdown Voltage is determined by increas ing voltage across terminal s 8 and 9 with positive on 9. Place 10,000 ohm resistor in series with ammeter. Increase voltage until current reads .25 mA. Measure dc voltage across terminals 8 and 9. The voltage should be between 16 0 a nd 2 40 v olts for 48 an d 12 5 Vdc rated relay s; and 320 to 480 volts for 250 Vdc rated relays. circuit.
DO NOT
exceed 3.0 mA current in the
8
41-923.4M
7.3. FOR RELAY TO BE USED WITH TC-TYPE CARRIER
7.3.1. Receiver Unit
Back off contact screws so that they do not make contact. Screw magnetic shunts into the all- out posi­tion (5 or 6 screw threads showing.) The armature should remain against whichever side it is pushed with this adjustment.
Adjust the stationary contacts for a contact gap of approximately .020” . This can be done by inse rting a .010” steel thickness gage between the large rivet head on the moving armature and the right-hand pole face (a .010” travel of the rivet hea d is eq ual to .02 0” travel of the moving contacts). Using an indicating light in each contact circuit, adjust the upper and lower stationary contacts to touch the moving contact at the same time. W it h th e fe el er ga uge r emo ved th e contact gap is 0.20” and the moving contacts close simultaneously.
Connect a jumper between the middle and left-hand contact connection of the CS G or CSP switch. The CSG switch is located on the right-hand pedestal and CSP is located on the right-hand pedestal of the relay (front view). Apply rated voltage across the RRT coil and the RRT coil resistor observing p olarity as shown in the internal schematic diagram. The armature should move to the left.
To the holding coil, RRH, a pply 100 to 200 milliam­peres dc current observing correct polarity. The armature should no w move to the right. Deenergiz e both coils and see that the armature stays up against the right-hand side.
Run both shunt screws all the way in, and the n back out the left-hand shunt scr ew approximately 6 turns. Back out the right-hand shun t screw appr oximate ly 9 turns.
Re-energize the operating coil with rated voltage and the holding coil wi th 40 milliamperes dc. Adjust the right-hand shunt scre w until the armature moves to the left. If the armature moves to the left, at a value of holding coil current gre ater tha n 40 millia mpere s, the right-hand shunt sc rew sho uld be turned out to lower this value to the correct 40 milliampere point.
Increase the holding coil curren t to 60 milliamperes and adjust the left -hand shunt screw unti l the arma­ture resets, or moves to the right. If the armature resets at a value of current less than 60 milliam­peres, the left-hand shunt screw should be turned out. This will increase the reset value of the armature and provide for the correct 60 milliampere reset value.
Minor adjustments of both shunt screws must be made several times until the desire d oper ating poi nts are obtained, since the adjustments of one shunt screw affect the adjustment on the other shunt screw.
7.3.2. Alarm Unit
The contacts should close with 80 milliamperes dc
±
5% applied to the alarm coil. Adjust the contact screws to obtain an .050” contact gap such tha t the armature motion between the left and right-hand con­tacts is in the central part of the air gap betw een the pole faces. Tighten the contact locking nuts. Approxi­mate adjustments of the two magne tic shunt screws are as follows:
Turn both shunt screws all the way i n. Th en back out both shunt screws app roximately seven tu rns. Apply 80 milliamperes dc to the coil, observing correct polarity, and screw in the left-hand shunt screw until the armature moves to the right. If the armature moves to the right at a value of current less than 80 milliamperes, screw the left -hand shunt out until the armature moves to the right at 80 milliamperes. Check the dropout poi nt by reducing the dc cu rrent. The armature should move to the left between the limits of 40 and 60 milliamperes. If it fai ls to do so, adjust the right-hand shunt screw until it does. It will then be necessary to recheck the pickup and dropout points again and make any minor adjustmen ts to the shunt screws that may be necessary until correct cal­ibration is obtained.
In general, screwing in the left-hand shunt screw reduces the pickup current of the relay. Screwing in the right-hand shunt screw increases the dropout current. This will in turn cause a change in the pickup current, making necessary several slight readjust­ments of both shunt screws to obtain the desired cal­ibration. The armature as finally calibrated should pickup and dropout with a snappy action.
9
41-923.4M
7.4. FOR RELAYS TO BE USED WITH KR-TYPE CARRIER OR TA-3 TONES
7.4.1. Receiver Unit
Calibrate as outlined under TC Type Carrier. Apply 15 mA dc cu r re nt fo r po la ri t y check. Th e pi ck up v al ue should be 4 milliamperes dc ( armature moves to left) instead of 40 mA. T he calibration of re set (armature moves to the right) should be done at 6 milliam peres instead of 60 mA.
7.4.2. Alarm Unit
Calibrate as outlined under TC-type Carrier. Check pick-up at 8 mA ±5% instead of 80 mA. Dropout should be between 4 and 6 mA ins tead o f 40 an d 60 mA.

8.0 RENEWAL PARTS

Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be fur­nished to the custom ers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data.

9.0 ENERGY REQUIREMENTS

9.1. CURRENT BURDEN AT 60 CYCLES
Power
Current
Amperes
0.5
5 20 40 60
Current lagging voltage
††
Current leading voltage.
9.2. RATING OF OVERCURRENT UNIT
Continuous rating 5 amperes. One second rating 100 amps.
Volt
Amperes
2.2
43
394 1240 2760
.
Factor
Angle
33°
70°
††
49°
39.2°
32.5°
†† ††
10
THIS P AGE LEFT BLANK
41-923.4M
11
41-923.4M
12
Sub 4 5307D96
Figure 8. Typical External Schematic of a KA-4 Relay in a KD-4/TC Blocking System
41-923.4M
Figure 8. Typical External Schematic of a KA-4 Relay in a KD-4/TC Blocking System
Sub 4 5307D96
13
41-923.4M
14
Figure 9A. Typical External Schematic of a KA-4 Relay in a KD-10/TC Blocking System
41-923.4M
Figure 9B. Typical External Schematic of a KA-4 Relay in a KD-10/TC Blocking System
15
Loading...