ABB Fusible disconnect switches Technical Data

Disconnect
Technical data
switches
Non-fusible
OETL-NF200 – OETL-NF3150 IEC
IEC
Catalog number 3 pole OETL-NF200A OETL-NF400 OETL-NF600A OETL-NF800A OETL-NF1200 OETL-NF1600 OETL-NF2000 OETL-NF3150
Rated voltage, Ue V/V 500/690 500/690 500/690 500/690 500/690 500/690 500/690 500/690
Rated conditional short-circuit current kA 100/50 100/50 100/50 50 50 63/50 63/50 63/50 Max. allowed fuse size, type OFAA A 400 800 800 — — — — —
Max. allowed cut-off current, peak value kA 45/35 70/63 70/63 — — — — —
Rated short-circuit making capacity,
prospective peak value, I
Rated short time withstand current,
cw
RMS l
cw
1.0s kA 8 17 17 50 2
RMS l
AC breaking capacity
pf = 0.35 415V
500V A 2000 4640 4800 6400 6400 6400 6400 6400 690V A 2000 2800 2800 2500 3 2500 3 4800 4 4800 4 4800 4
DC breaking capacity/poles in series
L/R = 15ms, 3 pole in series
110V A 1000/2 1 1 1 1 1 1 1 220V A 1000/2 1600/2 2000/2 1900/2 2600/2 2600/2 2600/2 2600/2 440V A 1000/3 1600 2000 1 1 1 1 1 750V A 1000/4 1 1 1 1 1 1 1 Capacitor ratings 400/415V kVar 110 300 330 1 1 1 1 1 Rated capacitor duty kA 170 450 500 1 1 1 1 1
Physical characteristics
Electrical endurance at rated operational
current, pf = 0.65
Mechanical endurance operations 16,000 10,000 10,000 10,000 10,000 6000 6000 6000
Weight 3 pole kg 3.0 6.2 6.2 16.3 17.5 37 37 37
4 pole kg 3.7 7.6 7.6 20.5 22.5 47 47 47
Dimension 3 pole H mm
W mm 219 260 304 363 363 468 468 468
D mm 92.5 130 130 125 125 271 271 271
Power loss per one pole W 5.5 22 40 40 67 90 90 140
Shaft size — square
Switch operating torque for
rotary 3 pole switches Nm 8.2 21 21 21 21 50 50 50
Suitable conductor cross section Cu
Bolt size 10 x 30 12 x 40 12 x 40 12 x 60 12 x 60 12 x 60 12 x 60 12 x 60
Auxiliary contacts OZXK-_ _ OZXK-_ _ OZXK-_ _ OZXK-_ _ OZXK-_ _ OZXK-_ _ OZXK-_ _ OZXK-_ _
Ratings according to IEC 947-5-1
Rated voltage, U
Thermal rated current, I
AC12/DC12 Ie, A U
125V A —/1.1 —/1.1 —/1.1 —/1.1 —/1.1 —/1.1 —/1.1 —/1.1
240V A 6/— 6/— 6/— 6/— 6/— 6/— 6/— 6/—
250V A —/0.55 —/0.55 —/0.55 —/0.55 —/0.55 —/0.55 —/0.55 —/0.55
400V A 4/— 4/— 4/— 4/— 4/— 4/— 4/— 4/—
415V A 4/— 4/— 4/— 4/— 4/— 4/— 4/— 4/—
440V A —/0.31 —/0.31 —/0.31 —/0.31 —/0.31 —/0.31 —/0.31 —/0.31
480V A 3/— 3/— 3/— 3/— 3/— 3/— 3/— 3/—
500V A 3/0.27 3/0.27 3/0.27 3/0.27 3/0.27 3/0.27 3/0.27 3/0.27
600V A —/0.2 —/0.2 —/0.2 —/0.2
690V A 2/— 2/— 2/— 2/— 2/— 2/— 2/— 2/—
500/690V kA 35 80 80 105 105 140/105 140/105 140/105
cm
0.2s kA 17 38 38 — — — — —
A 2000 5040 5760 6400 6400 6400 6400 6400
48V A 1000/2 1 1 1 1 1 1 1
operation cycles 1000 1000 500 500 500 100 5 100 5 100 5
162 216 216 372 372 546 546 546
mm 8 x 8 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12
2
mm
— — — — — — — —
VAC 690 690 690 690 690 690 690 690
i
A 10 10 10 10 10 10 10 10
th
= 120V A 8/— 8/— 8/— 8/— 8/— 8/— 8/— 8/—
e
—/0.2 —/0.2 —/0. 2 —/0.2
50 2
80 2
17
80 2
80 2
17
1 Not available at time of printing, please consult factory. 2 Maximum distance between busbar support and switch terminal 70 3 pf 0.95. 4 pf 0.65. 5 IEC 947-3, utilization category B, infrequent operation.
mm.
Load
2 poles in series
Load Load
3 poles in series
4 poles in series