ABB Enclosed switches Technical Data

Technical data
Enclosed switches
Enclosed disconnect switches eOT16 eOT32 eOT45 eOT63 eOT30 eOT60 eOT100
Approvals 3pole UL 508 UL 508 UL 508 UL 508 UL 98 UL 98 UL 98
UL Amperage Rating 16 40 60 80 30 60 100
Max Horsepower rating
Three Phase
200V-208V HP 3 10
240V HP 6 10 15 20 10 20 30
480V HP 10 20 30 40 20 40 50
600V HP 10 25 30 40 30 40 50
Single Phase
120V HP 1 2 2 2 2 3 5
240V HP 2 5 7.5 10 5 7.5 15
Interrupting Capacity (SCCR) with fuse
Fuse Type CC kA 10/- 10/-
Fuse Type J kA 10/10 10/10 100/- 100/- 50/200 50/200 50/200
Fuse Type T kA 10/10 10/10 100/- 100/- 50/200 50/200 50/200
Fuse Type RK1 kA 10/- 10/- -/- -/-
Fuse Type RK5 kA 5/5 5/5 10/5 10/5
Fuse Type L kA -/- -/- -/- -/-
Fuse Type H kA -/- -/- -/5 -/5
Maximum Fuse Size A 30/60
Endurances
Min. electrical endurance power
factor
0.75...0.8 op. cycles 6000 6000
0.40...0.50 op. cycles 1000 1000 1000 1000
Mechanical endurance operations 20000 20000 20000 20000 20000 20000 20000
Switch operating torque lbs. in. 8.8 8.8 10.5 10.5 17.6 17.6 17.6
Knock-outs Plastic enclosure Ends 4x1/2” or 4x3/4” 4x1/2" or 4x 3/4" 4x3/4" or 4x1" 4x1" or 4x1 1/4"
Metallic enclosure Ends 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" + 4x3/4" or 4x1/2" +
2x1" or 2x3/4" 2x1" or 2x3/4" 2x1" or 2x3/4" 2x1" or 2x3/4" 2x1" or 2x3/4" 2x1" or 2x3/4" 2x1" or 2x3/4"
Terminal Lug Kits Not required Not required Not required Not required Not required Not required Not required
Wire Range AWG #18-8 #18-8 #14-4 #14-4 #14-4 #14-4 #8-1/0
Wire Tightening Torque lbs. in. 7 7 18 18 55 55 55
Lug Mounting lbs. in. Integral Integral Integral Integral Integral Integral Integral
Auxiliary Contacts
Auxiliary Contacts Plastic enclosure OA1G_ or OA2G11 OA1G_ or OA2G11
Metallic enclosure OA1G_ OA1G_ OA1G_ OA1G_ OA1G_ OA1G_ OA1G_
NEMA ratings, AC AC600 AC600 AC600 AC600 AC600 AC600 AC600
AC rated voltage VAC 600 600 600 600 600 600 600
AC rated thermal current A 10 10 10 10 10 10 10
AC maximum volt-ampere
making
AC maximum volt-amperage
breaking
NEMA ratings, DC R300 R300 R300 R300 R300 R300 R300
DC rated voltage VDC 300 300 300 300 300 300 300
DC thermal rated current A 1 1 1 1 1 1 1
DC maximum make-break VA 28 28 28 28 28 28 28
Torque: wire tightening lbs. in. 7 7 7 7 7 7 7
Wire Range AWG #18-14 #18-14 #18-14 #18-14 #18-14 #18-14 #18-14
1)
Fuse size 70A for RK5
VAC 7200 7200 7200 7200 7200 7200 7200
VAC 720 720 720 720 720 720 720
1)
30/60
1)
4 | Enclosed switches - eOT
-/- -/-
100/150 100/150 60/60 150/60 150/100
6000 6000 6000 6000 6000
OA1G_ or OA2G11 OA1G_ or OA2G11 OA1G_ OA1G_ OA1G_
Enclosed switches - eOT | 5