Features and benefits .............................................................................................................................................................................. 3
IEC & NEMA Non-combination, non-reversing, three phase ........................................................................................................................ 7
IEC & NEMA Non-combination, non-reversing, single phase ....................................................................................................................... 8
IEC & NEMA Non-combination, non-reversing, three phase, non-fusible disconnect ................................................................................... 9
IEC & NEMA Non-combination, non-reversing, single phase, non-fusible disconnect ................................................................................ 10
IEC & NEMA Combination, non-reversing, three phase, fusible disconnect ............................................................................................... 11
IEC & NEMA Combination, non-reversing, single phase, fusible disconnect .............................................................................................. 12
IEC Combination, non-reversing, three phase, circuit breaker ................................................................................................................... 13
NEMA Combination, non-reversing, three phase, circuit breaker ............................................................................................................... 14
IEC & NEMA Combination, non-reversing, single phase, circuit breaker .................................................................................................... 15
Reversing Starters
IEC & NEMA Non-combination, reversing, three phase ............................................................................................................................. 16
IEC & NEMA Non-combination, reversing, three phase, non-fusible disconnect ........................................................................................ 17
IEC & NEMA Combination, reversing, three phase, fusible disconnect ...................................................................................................... 18
IEC Combination, reversing, three phase, circuit breaker .......................................................................................................................... 19
NEMA Combination, reversing, three phase, circuit breaker ...................................................................................................................... 20
Two speed one winding Starters
IEC Non-combination, two speed one winding, three phase ..................................................................................................................... 21
IEC Non-combination, two speed one winding, three phase, non-fusible disconnect ................................................................................ 22
IEC Combination, two speed one winding, three phase, fusible disconnect .............................................................................................. 23
IEC Combination, two speed one winding, three phase, circuit breaker .................................................................................................... 24
Two speed two winding Starters
IEC Non-combination, two speed two winding, three phase ..................................................................................................................... 25
IEC Non-combination, two speed two winding, three phase, non-fusible disconnect ................................................................................ 26
IEC Combination, two speed two winding, three phase, fusible disconnect .............................................................................................. 27
IEC Combination, two speed two winding, three phase, circuit breaker .................................................................................................... 28
Factory installed modifications
Pilot device kits ......................................................................................................................................................................................... 29
Control circuit transformer ........................................................................................................................................................................ 30
Field modifications kits
Pilot device kits ......................................................................................................................................................................................... 31
Control circuit transformer kits .................................................................................................................................................................. 32
General information
Motor data ............................................................................................................................................................................................... 33
Pilot device kits ......................................................................................................................................................................................... 46
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 36 & 37.
ContactorContinuous
Maximum motor horsepower ratings
200V230V460/575V
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the dash in the catalog number. Ex.: A 24V AC coil is
required for an AF26 starter: AF2612-1K
Coil voltage selection chart
Coil voltage
AC Volts, 40-60 Hz
24 AC100 - 250 AC250 - 500 AC
123
1) 24 AC coil voltage is available only with AF26 & AF30, AFN00 - AFN1,
For factory modifications, see pages 29 & 30.
Control transformer voltage selection
To select starter with control transformer, substitute the code from the control transformer voltage selector chart after the dash in the catalog number.
Ex.: A 480V primary voltage with a 120V secondary voltage is required for an
AF26 starter: AF2612-CK
∆ Overload relay suffix code. Select from the overload relay selection chart on page 36.
ContactorContinuous
Maximum motor horsepower
ratings
120V230V
Coil voltage selection 1)
All rated AC catalog numbers include a 120V AC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for
the suffix code after the dash in the catalog number. Ex.: A 24V AC coil is
required for an AF26 starter: AF261S2-1S
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Control transformer voltage selection
To select starter with control transformer, substitute the code from the control transformer voltage selector chart after the dash in the catalog number.
Ex.: A 230V primary voltage with a 120V secondary voltage is required for an
AF12 starter: AF121S2-BS
Coil voltage selection chart
Coil voltage
AC Volts, 40-60 Hz
24 AC100 - 250 AC
12
1) 24 AC coil voltage is available only with AF26 & AF30, AFN00 - AFN1.
For factory modifications, see page 29 & 30.
Control transformer voltage selection chart
Control Voltage
120V AC @ 50/60 HzB
24V AC @ 50/60 HzF
230-240
8 | IEC & NEMA Enclosed starters
IEC & NEMA Non-fusible disconnect switch
AF26 - AF750; AFN00 - AFN4
Non-reversing, three phase
IEC Non-fusible disconnect switch
Maximum ratings - UL ListedUL Type 1, 3R, 4, 12UL Type 4X
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 36 & 37.
ContactorContinuous
Maximum motor horsepower ratings
200V230V460/575V
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the dash in the catalog number. Ex.: A 24V AC coil is
required for an AF26 starter: AF261N2-1K
Coil voltage selection chart
Coil voltage
24 AC100 - 250 AC250 - 500 AC
123
1) 24 AC coil voltage is available only with AF26 & AF30, AFN00 - AFN1.
For factory modifications, see pages 29 & 30.
AC Volts, 40-60 Hz
Control transformer voltage selection
To select starter with control transformer, substitute the code from the control transformer voltage selector chart after the dash in the catalog number.
Ex.: A 480V primary voltage with a 120V secondary voltage is required for an
AF26 starter: AF261N2-CK
∆ Overload relay suffix code. Select from the overload relay selection chart on page 34.
Contactor Size
Maximum motor horsepower ratings
120V240V
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
NEMA Non-fusible disconnect switch
Maximum ratings - UL ListedUL Type 1, 3R, 4, 12UL Type 4X
NEMA
size
00AFN0091/31AFN001SN2-2∆A9N001SNX-2∆
0AFN01812AFN01SN2-2∆A16N01SNX-2∆
1AN12723AFN11SN2-2∆A26N11SNX-2∆
2AFN245–7.5AFN21SN2-2∆A50N21SNX-2∆
∆ Overload relay suffix code. Select from the overload relay selection chart on page 36.
ContactorContinuous
Maximum motor horsepower ratings
120V230V
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the last dash in the catalog number. Ex.: A 24V AC
coil is required for an AF12 starter: AF261SN2-1S
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Control transformer voltage selection
To select starter with control transformer, substitute the code from the Control transformer voltage selector chart for the two digits after the last dash
in the catalog number. Ex.: A 230V primary voltage with a 120V secondary
voltage is required for an AF26 starter: AF261SN2-BS
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection chart
Coil voltage
24 AC100 - 250 AC
12
1) 24 AC coil voltage is available only with AF26 & AF30, AFN00 - AFN1.
For factory modifications, see page 29 & 30.
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 34 & 35.
Contactor Size
200/208V230/240V460V/480V575/600V
Maximum motor horsepower ratings
Fuse clip rating
amp/volts
UL Type 1, 3R, 4, 12UL Type 4X
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
NEMA Fusible disconnect switch
Maximum ratings - UL Listed
NEMA
size
00AFN0091.51.5230/600AFN001F2-2∆1AFN001FX-2∆1
0AFN01833530/600AFN01F2-2∆1AFN01FX-2∆1
1AFN127——1030/600AFN11F2-2∆1AFN11FX-2∆1
1AFN1277.57.5—60/600AFN11F2-2∆2AFN11FX-2∆2
2AFN24510—2560/600AFN21F2-2∆2AFN21FX-2∆2
2AFN245—15—100/600AFN21F2-2∆3AFN21FX-2∆3
3AFN390253050200/600AFN31F2-2∆4AFN31FX-2∆4
4AFN41354050100400/600AFN41F2-2∆5AFN41FX-2∆5
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 36 & 37.
ContactorContinuous
Maximum motor horsepower ratings
200V230V460/575V
Fuse clip rating
amp/volts
UL Type 1, 3R, 4, 12UL Type 4X
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the last dash in the catalog number. Ex.: A 24V AC
coil is required for an AF12 starter: AF121F2-1R1
Coil voltage selection chart
Coil voltage
AC Volts, 40-60 Hz
24 AC100 - 250 AC250 - 500 AC
123
1) 24 AC coil voltage is available only with AF09 - AF30, AFN00 - AFN1.
For factory modifications, see page 29 & 30.
Control transformer voltage selection
To select starter with control transformer, substitute the code from the Control transformer voltage selector chart for the two digits after the last dash
in the catalog number. Ex.: A 480V primary voltage with a 120V secondary
voltage is required for an AF12 starter: AF121F2-CR1
∆ Overload relay suffix code. Select from the overload relay selection chart on page 36.
ContactorContinuous
Maximum motor horsepower ratings
120V230V
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
AFN001SFX-2∆
1
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the last dash in the catalog number. Ex.: A 24V AC
coil is required for an AF12 starter: AF121SF2-2R1
Coil voltage selection chart
Coil voltage
24 AC100 - 250 AC
12
1) 24 AC coil voltage is available only with AF09 - AF30, AFN00 & AFN1.
For factory modifications, see pages 29 & 30.
AC Volts, 40-60 Hz
Control transformer voltage selection
To select starter with control transformer, substitute the code from the Control transformer voltage selector chart for the two digits after the last dash
in the catalog number. Ex.: A 230V primary voltage with a 120V secondary
voltage is required for an AF12 starter: AF121SF2-BR1
Control transformer voltage selection chart
Control Voltage230-240
120V AC @ 50/60 HzB
24V AC @ 50/60 HzF
12 | IEC & NEMA Enclosed starters
IEC Circuit breaker type
AF26 - AF750
Non-reversing, three phase
Maximum ratings - UL ListedUL Type 1, 3R, 4, 12UL Type 4X
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 34 & 35.
Contactor Size
200/208V230/240V460V/480V575/600V
Maximum motor horsepower ratings
Circuit Breaker
Amp Rating
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog
number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select
other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the last dash in the catalog number. Ex.: A 24V AC
coil is required for an AF26 starter: AF261B2-1K1
Coil voltage selection chart
Coil voltage
AC Volts, 40-60 Hz
24 AC100 - 250 AC250 - 500 AC
123
1) 24 AC coil voltage is available only with AF26 & AF30,
For factory modifications, see pages 29 & 30.
Control transformer voltage selection
To select starter with control transformer, substitute the code from the Control transformer voltage selector chart for the two digits after the last dash
in the catalog number. Ex.: A 480V primary voltage with a 120V secondary
voltage is required for an AF26 starter: AF261B2-CK1
Control transformer voltage selection chart
Control Voltage200-208230-240460-480575-600
120V AC @
50/60 Hz
24V AC @
50/60 Hz
ABCD
EFGH
IEC & NEMA Enclosed starters | 13