ABB Electronic safety relays Catalog Page

Electronic
7
Safety relays
7
• Solid-state control of actuators, therfore no wear
• No contact failure at currents of 17V, 1mA
• Short circuit proof
• High switching frequencies
• 24VDC sensor supply
• Economical
Internal standard circuit diagram of a safe circuit in accordance to C 6700
24V DC
ON
EMERGENCY­STOP
M
Internal standard circuit diagram of safety relay C 6701with solid-state output.
L1L2 L3
Y33 Y34
Y12
Y11
A1
POWER RUN Fail
C6700
A2
Y21 Y22
11
12
Y20
consumer
Electronic safety relays
with soid state output C67xx
Electronic safety relays with solid-state output C 67xx
• Solid-state outputs – no contacts – no wear
• Low weight & small size – Space and weight advantage
• Positively guided standard contactors operate as switching elements
C 67xx safety relays are solely used to monitor the sensors connected (e.g. limit switches resp. EMERGENCY-STOP­buttons) and actuators (positively guided standard contactors).
The basic unit C 6700 itself does not feature safe outputs. Only when the unit is used together with positively guided actuators (e.g. contactors B6, B7) the complete circuit fulfi lls up to category 3 to EN 954-1. Us = 24VDC; Ue = 24VDC; Ie = 0.5ADC 13.
The safety relay C 6701 with solid-state outputs can be used directly to switch off connected devices up to category 3 or 4 to EN 954-1. Us = 24VDC; Ue = 24VDC; Ie = 1.5ADC 13.
The safety relay C 6702 with solid-state outputs can also be used to directly switch off connected devices up to category 3 to EN 954-1 and stop categories 0 and 1 at a width of 22.5 mm only. Time delay settable from 0.05-3 or 0.5-30s. Us = 24VDC; Ue = 24VDC; Ie = 1.5ADC 13.
Type Supply voltage Package Weight Catalog List Vc unit 1 piece number Price piece kg/lb
C 6700 1SAR 510 120 R 0003 C 6701 C 6702 1SAR 543 320 R 0003 factory
24VDC 1 0.150/0.33
C 6702 1SAR 513 320 R 0003
Technical data
C 6700 C 6701 C 6702
Permissible ambient temperature TU Operation / storage -25...+60 °C / -40...+80 °C Degree of protection acc. to EN 60 529 IP40, IP20 at terminals Rated insulation voltage Vi 50V
Rated impulse withstand voltage V Rated control supply voltage VS 24VDC 24VDC 24VDC
imp
Rated power consumption 1.5W 1.3W 1.3W Operational voltage range 0.9...1.15 x VS 0.9...1.15 x V Shock resistance (half-sine) acc. to IEC 60068 8g/10ms 8g/10ms 8g/10ms Weight 150g/0.33lb 150g/0.33lb 150g/0.33lb Recovery time after EMERGENCY STOP min. 20ms min. 30ms min. 30ms Recovery time after power failure — 7 s — Release time after EMERGENCY STOP < 30ms min. 30ms 30ms / 0.05...3s or 0.5...30s adjustable Recovery time after power failure max. 25ms — — Response time — max. 40ms max. 40ms Response time monitored start < 125ms — — Response time Auto-start < 250ms — — Short circuit protection no fusing necessary no fusing necessary no fusing necessary
Utilization category acc. to IEC 60947-5-1: Rated operational Rated operational voltage Ve current I
C 6700 DC-13 24V 0.5A (per output, 60 °C) C 6701 DC-13 24V 2.0A C 6702 DC-13 24V 2.0A
1SAR 511 320 R 0003 Consult
500V 2kV 2kV
e
0.9...1.15 x V
S
S
Emergency
stop
7.32 Low Voltage Products & Systems
AC 1000 - 11/03
On
Discount schedule AR