AF, AFZ, and EK 4-pole
Across the line
1
Contactors
AF09(Z)...AF16(Z) AF26(Z)...AF38(Z) AF45...AF75 EK175...EK210
Electrical ratings 1
IEC/EN 60947-4-1
Rated operational current Ie, AC-1 (A) AC general purpose ratings, 600V (A) NO NC NO NC
Type AF, electronic AC/DC controlled
25 25
30 30
45 45
55 55
70 65
100 80 4 - - - AF50-40-00-Δ
125 105
Type EK, AC or DC controlled
Type AFZ, electronic AC/DC controlled, low consumption
200 170 4 - 1 1 EK110C4P-ΔL
250 200 4 - 1 1 EK150C4P-ΔL
300 250 4 - 1 1 EK175C4P-ΔL
350 300 4 - 1 1 EK210C4P-ΔL
550 420 4 - 1 1 EK370C4P-ΔL
800 540 4 - 1 1 EK550C4P-ΔL
1000 - 4 - 1 1 EK1000C4P-ΔL
25 25
30 30
45 45
55 55
For resistive & slightly inductive applications up to 1000 A
AC & DC control
4-pole (4 NO & 2 NO / 2 NC)
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
R
Main (power) pole
conguration 2
Standard auxiliary
contacts
4 - - - AF09-40-00-Δ
2 2 - - AF09-22-00-Δ
4 - - - AF16-40-00-Δ
2 2 - - AF16-22-00-Δ
4 - - - AF26-40-00-Δ
2 2 - - AF26-22-00-Δ
4 - - - AF38-40-00-Δ
2 2 - - AF38-22-00-Δ
4 - - - AF45-40-00-Δ
2 2 - - AF45-22-00-Δ
4 - - - AF75-40-00-Δ
2 2 - - AF75-22-00-Δ
4 - - - AF09Z-40-00-Δ
2 2 - - AF09Z-22-00-Δ
4 - - - AF16Z-40-00-Δ
2 2 - - AF16Z-22-00-Δ
4 - - - AF26Z-40-00-Δ
2 2 - - AF26Z-22-00-Δ
4 - - - AF38Z-40-00-Δ
2 2 - - AF38Z-22-00-Δ
Catalog
number
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3
12…20V DC - 20 - -
20...60V DC 11 21 72 -
24...60V AC 11 21 - 24V AC, 60 Hz - - - F
24V DC - - - Y
48...130V AC/DC 12 22 69 110V 50 Hz, 120V 60 Hz - - - 1
125V DC - - - Q
100...250 VAC/DC 13 23 70 220V DC - - - R
240V AC, 60 Hz - - - 2
250...500 V AC/DC 14 - - 480V AC, 60 Hz - - - 4
600V AC, 60 Hz - - - 6
AF09…
AF38
1.32 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
AF09Z…
AF38Z
AF45…
AF75
EK110…
EK1000
Example(s):
24V DC input voltage: EK110C4P-YL
120V AC input voltage: AF75-40-11-70
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 2 NO & 2 NC contactors are not suitable for a reversing starter or wye-delta starter or for con-
trolling a single load from 2 separate supplies. Please see technical data.
3 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.