ABB competence serving the most
demanding customers
Suitability for disconnection and switching, effective heat
dissipation and certified compliance with several international
standards are mandatory requirements to meet the needs of the
most demanding customers. ABB has dedicated its designers’
passion, competence and creativity to the development of E 90
range of disconnectors and fuseholders, of E 90 50/125 series
designed to ensure isolation and protection of circuits in big
industrial plants, E 90 CC and E 90 J series specifically designed for
the NAM markets. The result is the first AC-22B fuse disconnector,
certified up to 32 A by the most outstanding marks and approvals
all over the world.
2 | E 90 range of fuse disconnectors and fuseholders
Page 3
The new ABB standard
Certified according to the most important
international marks
A passport to the world.
International quality marks, naval type-approvals and UL certification
make E 90 the ideal range for designers and manufacturers of
switchboards and installations “without frontiers”.
E 90 range of fuse disconnectors and fuseholders | 3
Page 4
E 90 range
Designed by ABB for the most demanding
customers
Industrial automation
E 90 fuse switch
disconnectors
– One module per pole
– Versions 1, 1N, 2, 3, 3N, 4
– AC-22B according to IEC 60947-3
– Rated current 20 A and 32 A
– Rated voltage 400 V AC-22B and 690 V AC-20B
– Can be equipped with 8.5 x 31.5 mm and 10.3 x 38 mm
aM and gG fuses
– Designed for isolation and switching under load and for
protection of secondary circuits of industrial plants
– All the versions are available with optical blown fuse indicator
– Compatible with ABB busbars of S 200 series and Unifix
plug-in system
– cURus certification
Distribution switchboards
E 90h fuseholders
– One pole plus neutral in one module
– Versions 1N, 3N
– Certified according to IEC 60269-3
– Rated current 20 A and 32 A
– Rated voltage 400 V AC
– Can be equipped with 8.5 x 31.5 mm and 10.3 x 38 mm
aM and gG fuses
– Designed for instruments and auxiliaries protection
in switchboards and consumer units
– All the versions are available with optical blown fuse indicator
– Compatible with ABB busbars of SN 201 series and Unifix
plug-in system
4 | E 90 range of fuse disconnectors and fuseholders
Page 5
Photovoltaic installations
Industrial circuit protection
E 90 PV fuse disconnectors
– One module per pole
– 1 and 2-pole versions
– DC-20B according to IEC 60947-3
– Rated current 32 A
– Rated voltage 1000 V DC
– Can be equipped with 10.3 x 38 mm gPV fuses
– Designed for isolation and protection of circuits in
photovoltaic installations up to 1000 V DC
– All the versions are available with optical blown
fuse indicator
– Certified according to UL 4248-18
E 90 50/125
fuse-disconnector/fuseholder
– Versions 1, 1N, 2, 3, 3N
– AC-20B according to IEC 60947-3
– Rated current 50 and 125 A
– Rated voltage 690 V AC
– Can be equipped with any type of cylindrical fuses 14x51
(E 90/50) and 22x58 mm (E 90/125)
– Specifically designed for industrial circuit protection
– All the versions are also available with optical blown
fuse indicator
– Certified according to UL 4248-1
E 90 range of fuse disconnectors and fuseholders | 5
Page 6
E 90 range
Designed by ABB for the most demanding
customers
For the American market
E 90 CC fuseholders
– One module per pole
– Versions 1, 1N, 2, 3, 3N, 4 poles
– Rated current 30 A
– Rated voltage 600 V AC/DC
– Can be equipped with Class CC fuses
– All the versions are available with optical blown
fuse indicator
– Certified according to UL 4248-4
– Rejection member feature according to UL 4248-4
Industrial installation
in the NAM market
E 90 30/60 J fuseholders
– 1, 2 and 3 poles versions
– Rated current 30 and 60 A
– Rated voltage 600V AC
– Can be equipped with Class J fuses
– All the versions are also available with
optical blown fuse indicator
– UL listed according to UL 4248-8
6 | E 90 range of fuse disconnectors and fuseholders
Page 7
Choosing the best
ABB experience sets a new leading-edge
performance standard
Tip-top
performance
E 90 fuseholders with rated
current up to 32 A can be used
in any applications where
you need to ensure electrical
protection, isolation and
switching under load of
inductive or resistive loads in
compliance with IEC 60947-3
Standard. Utilization category of
this series is AC-22B up to
400V. The technology
solutions applied to reduce
power dissipation help to
minimize module heating.
Completeness
The fuse tripping can be easily
displayed, thanks to the special
blown fuse indicator light.
Reliability
Venting grooves and cooling
chambers improve heat
dissipation even in multiple-pole
configurations. The reduced
operating temperature inside
fuseholders ensures durability and
reliability of the devices over time.
Compactness
The compact dimensions enable
to close the switchboard door
even when the fuseholder is open,
thus ensuring total safety during
maintenance.
1P+N versions in one module
only and 3P+N in three
modules only are available.
Ease of installation.
E 90 fuseholders are fully compatible
with the Unifix-L wiring system
Universal use
Screw holes have increased
diameter to accommodate
insulated screwdrivers and electric
screwdrivers. In addition, with the
Pozidrive PZ2 screws tightening
can be performed by exerting less
torque than conventional screws,
and the same electric screwdriver
can be used for all terminals.
Moreover, the PS connection
busbars facilitate the connecting
operations, making the wiring both
simple and safe and providing
complete integration with S 200 and
SN 201 System pro M compact
circuit-breakers.
E 90 range of fuse disconnectors and fuseholders | 7
®
Page 8
E 90 safe and smart range is designed for quick, flexible and
error-proof installation, to ease the everyday use of devices.
Thanks to its unique features, E 90 series sets a new safety
standard.
Reliable connections
Wide terminals allow the use of cables with
section up to 25 mm
knurling on the terminal cages ensures safe and
reliable connections.
2
, whereas the antivibration
Ease of use
Fuseholder profile has been
designed for maximum ease
of use: the 90° flip hinge with
ergonomic knob, makes the
replacement of fuses easier
even in small spaces or when
wearing protective gloves.
Safety
To ensure protection and safety
during maintenance operations
and avoid any accidental switching,
fuseholders can be sealed in
closed position, and padlocked
in open position. The protection
degree is IP20 when the unit is
installed behind the switchboard
slotting.
Environmental protection.
The fuseholders are compliant with RoHS (Restriction of Hazardous Substances)
European directive, which prohibits the use of hazardous substances in the
manufacture of electrical and electronic equipment.
8 | E 90 range of fuse disconnectors and fuseholders
Page 9
Smart protection for installations
with E 90s
The whole E 90 series is available with optical blown fuse
indicator light. In particular E 90s PV is the first fuse disconnector
for photovoltaic installations with optical blown fuse indicator,
which efficiently monitors DC installations up to 1000 V.
Flexible
E 90: 24 to 690 V operation in
AC networks. Can be powered
from both the load side and
the supply side.
E 90 PV: 24 to 1000 V
operation in DC networks with
upstream supply.
Simple
No need for auxiliary supply
or specific wiring.
Effective
Local fuse tripping signal.
Allows the faulty phase
to be immediately detected.
E 90 range of fuse disconnectors and fuseholders | 9
Page 10
Results you can trust
High performance of E 90
fuse disconnectors
10 | E 90 range of fuse disconnectors and fuseholders
Page 11
E 90 protection and control
A range developed for automation
and industry
Applications
- Automation switchboards
- On-board switchboards
- OEM
Main functions:
- Protection of terminal circuits
- Switching of loads, even
inductive
- Selectivity
E 90 fuse disconnectors are designed for switching
under load, ensuring isolation and protection against
short circuit and overload, in compliance with the
IEC 60947-3 Standard.
E 90 range is designed to comply with the strictest requirements
of OEMs and panel builders. They are ideally installed in
industrial automation switchboards to protect secondary circuits,
primary and secondary of transformers, motors and other
resistive or inductive loads. Due to the AC-22B utilization
category up to 400 V, according to the IEC 60947-3 Standard,
E 90 fuse disconnectors are convenient, simple and reliable
devices for loads switching and protection.
Fuse disconnectors ensure selectivity, if equipped with
appropriate fuses. Since they are uURus type-approved, they
can be installed in UL-certified machines designed for the
American market.
Application example
Here you can find a typical industrial control application. According to
IEC60364-1 Standard, the secondary winding of a control transformer must
be protected against short circuits and overload. The transformer provides
dedicated 230VAC power supply to a battery of industrial contactors.
E 90 range of fuse disconnectors and fuseholders | 11
Page 12
Industrial distribution
E 90h fuseholders:
ideal for distribution switchboards
12 | E 90 range of fuse disconnectors and fuseholders
Page 13
E 90h fuseholders
Compact protection of electric auxiliaries
in distribution switchboards
Applications
- Distribution switchboards
- Consumer units
Terminal protection of:
- Electric auxiliaries
- Switchboard instrumentation
- Surge arresters
E 90 Fuseholders – 1P+N in one module and 3P+N in
three modules, respectively – are very compact in size
and are the most suitable solution for protection of
circuits and devices inside switchboards.
E 90h range is designed for protecting electrical devices both
in single phase and in three-phase networks with neutral.
They are particularly suitable inside switchboards and
consumer units for protecting lighting circuits, modular sockets
and electrical devices for monitoring, measuring and signalling.
Application example
Here you can find a typical application inside a secondary distribution
switchboard. Following the manufacturer’s instruction, the voltmetric
inputs of the multimeter are protected with fuses.
E 90 range of fuse disconnectors and fuseholders | 13
Page 14
E 90 PV fuse disconnectors
for photovoltaic applications
Designed for industry professionals
Features
- For 10.3 x 38 mm fuses
- Rated voltage 1000 V DC
- Rated current 32 A
- DC-20B Utilization category
- Reference standards:
IEC 60947-3 UL 4248-18
E 90 PV fuse disconnectors have been specifically
designed for photovoltaic applications. Thanks to their
rated voltage up to 1000VDC they are the ideal solution
for protecting cells, inverters or surge arresters. In case of
maintenance, they ensure isolation of circuits and strings
up to 1000V in direct current, in total safety.
14 | E 90 range of fuse disconnectors and fuseholders
Page 15
Isolation and protection
of strings up to 1000 V
Application examples
String protection
To prevent damage to the equipment in the direct current
lines of photovoltaic installations and ensure that it remains
isolated when maintenance work is performed, E 90 PV fuse
disconnectors can be installed downstream of the inverter so
as to protect each string. The fuses must be selected to suit
the rated current of the line.
Surge arrester back-up
When the Icc short-circuit current at the installation point
exceeds 100 A DC, OVR PV surge arresters require back-up
protection with a specific gR-type fuse.
DC side of the inverter
In small photovoltaic installations, E 90 PV fuse disconnectors
can be used to protect the direct current side of the inverter.
Fuse cartridges should be selected according to the inverter
rated current.
E 90 range of fuse disconnectors and fuseholders | 15
Page 16
E 90 50/125 fuse disconnectors
Protection for industrial circuits
16 | E 90 range of fuse disconnectors and fuseholders
Page 17
Perfect integration,
guaranteed innovation
Features
- For 14x51
and 22x58 mm fuses
- Rated voltage
690V AC according to IEC
and 600V AC/DC
according to UL
- UR type-approved
E 90 50/125 fuse disconnectors are specifically designed
for protecting industrial circuits thanks to aM and gG
cylindrical fuses with 50 A and 125 A ratings and ensuring
disconnection properties according to IEC 60947-3.
(The usage of 125 A fuses within E 90/125 fuseholder is
allowed only in case the fuse power dissipation is lower
than the maximum acceptable power dissipation value of
the fuseholder - for more detail refers to section "Question
and answers").
The E 90/50 and E 90/125 fuse disconnectors have been
specifically designed to be used in all applications which
require protection and isolation of high-current loads: thanks
to their compatibility with gG and aM cylindrical fuses, they
offer maximum flexibility in terms of protection of installation
with rated currents up to 125 A.
The possibility to be padlocked in open position, ensures the
safety of personnel who carry out maintenance operations.
Furthermore the availability of optical blown fuse indicator in
all versions of the new E 90 50/125 enables to easily and
efficiently monitor distribution networks with high current
ratings.
Application examples
OVR PV back-up protection, shown on the left, is a typical application
for the fuseholder of the E 90 50/125 series.
They can also be used as protection of motors and transformers,
as protection against overloads and short circuits in low voltage installations
where currents are up to 125 A and in control circuits.
E 90 range of fuse disconnectors and fuseholders | 17
Page 18
Quality also speaks American
E 90 CC fuseholders,
designed for the North American market
18 | E 90 range of fuse disconnectors and fuseholders
Page 19
E 90 CC fuseholders
Specifically developed for branch
circuit protection
Features
- UL Listed according to
UL 4248-1 and UL 4248-4
- Can be equipped only with
Class CC fuses
- Rated voltage 600 V AC/DC
- Rated current 30 A
- Versions 1, 1N, 2, 3, 3N, 4 poles
- Rejection member to
allow just the insertion
of a class CC fuse
E 90 CC range has been designed to comply with North
American market regulations and to enable worldwide
manufacturers to sell their equipment in conformity with
safety requirements also in these countries.
Class CC fuses have limiting characteristics dedicated to
terminal protection of components and equipments against
short-term overloads and dedicated to motors' protection
against short-circuit. Maximum rated current of a Class CC fuse
is 30 A, whereas the maximum rated voltage is 600 V.
The breaking capacity reaches 200 kA. The limiting properties
of the Class CC fuses are particularly appreciated in the North
American market, allowing suitable protection even of equipment
with limited resistance to short-circuit. The use of Class CC
fuses is continuously increasing in the American market, since
the safety and reliability prescriptions of end users have become
stricter and do not tolerate any permanent damage to motor
starts.
Application examples
E 90 CC fuseholders have been developed to host Class CC fuses only.
They are used in the NAM markets mainly as branch circuit protection.
Here on the right side, an application example is showed.
E 90 range of fuse disconnectors and fuseholders | 19
Page 20
A new range for the North American market
E 90 30/60 J fuseholders
20 | E 90 range of fuse disconnectors and fuseholders
Page 21
E 90 J fuseholders
Specifically designed to be equipped
with class J fuses
Features:
- UL listed according to 4248-8
- Can be equipped only with
Class J fuses
- Rated voltage 600 V AC
- Rated current up to 60 A
- Versions with 1, 2 and 3 poles
E 90 J range has been designed to comply with North
American market regulations. The E 90 J fuse carriers are
the ideal solution for industrial installation, motors and
transformers protection, heating systems and control
circuits.
In accordance with the reference standard UL 4248-8, they
come in voltage and current ratings up to 600V and 30/60A,
respectively.
The breaking capacity reaches 200 kA. Fuseholders of the
E 90 J series are available in multipole configuration, from 1 to 3
poles. Versions with blown fuse indicator light provide a visual
signal of the fuse break condition allowing a faster and safer
maintenance of the installation. They can be padlocked open
and sealed closed to ensure operator safety during maintenance
operations.
Application examples
On the left side, is showed a typical example of motors protection,
E 90 J fuseholders are mainly used in the North American market as motors,
alternators and transformers protection or as feeding, heating and light
circuits protection.
E 90 range of fuse disconnectors and fuseholders | 21
Page 22
Technical data
E 90 series
Data according to IEC
TypeE 90/20E 90/32 E 90hN/20 E 90hN/32 E 90/32 PVE 90/50E 90/125
Rated current[A]203220323250100
Type of currentACACACACDCACAC
Fuse[mm]8.5 x 31.510.3 x 388.5 x 31.510.3 x 3810.3 x 3814 x 5122 x 58
Marks and approvalsE 90/20E 90/32 E 90hN/20 E 90hN/32 E 90/32 PVE 90/50E 90/125
IMQ•*
NF•**
CCC - Cina•*
RINA•*
LLOYD•*
BV•
EAC•••••••
GOST - Ukraina••••
•*= without LED version
•** = no neutral and without LED version
•*** = dedicated range with neutral on the left side
**** = IP20 also as standalone device installed on DIN rail, with respect to cables with a cross-section area ≥ 10 mm
(1) = certified AC-22B at 400 V in compliance with IEC 60947-3
(2) = according to IEC 60296-2
(2b) = with aM-type fuses and in combination with a device that ensures overload protection
(1)
(1)
(1)
(1)
(1)
(1)
2
•*
•**
•*
•*
•*
•
(1)
(1)
(1)
(1)
(1)
(1)
22 | E 90 range of fuse disconnectors and fuseholders
Page 23
400400–––
•*•*••
•***•***
•*•*•••
•*•*••
•*•*••
•••••
(2)
/125
(2b)
E 90 range of fuse disconnectors and fuseholders | 23
(1) = certified at 600 V in compliance with UL 4248-1
(2) = certified at 1000 V in compliance with UL 4248-18
(3) = certified at 600 V in compliance with UL 4248-8
(4) = certified at 600 V in compliance with UL 4248-4
***** IP20 also as standalone device installed on DIN rail, with respect to cables with a cross-section area ≥ 10 mm
(1)
(2)
(1)
•
2
24 | E 90 range of fuse disconnectors and fuseholders
Page 25
(4)
•
(1)
•
Shock and vibration
(3)
•
(3)
•
Vibration withstand on the 3 main axis:
– Sinusoidal vibration testing according to IEC 60068-2-6
2 to 13 Hz x= 1 mm peak
13 to 100 Hz y= 0.7 g peak
– Random vibration testing according to IEC 61373
Category 1 Class B
Shock withstand on the 3 main axis:
– Shock testing according to IEC 60068-2-27 15g/11ms/18
shocks
– Shock testing according to IEC 61373 Category 1 Class B
E 90 range of fuse disconnectors and fuseholders | 25
Page 26
Order codes
E 90 series
38ø 10.3
31.5ø 8.5
PolesRated
current
In [A]
E 90 fuse disconnectors for 10.3 x 38 mm fuses
1321009238E 91/322CSM200923R18010.0616
1321024835E 91/32s*2CSM202483R18010.0626
1+N32 2008934E 91N/322CSM200893R18010.1303
1+N322515036E 91N/32s*2CSM251503R18010.1313
2322008835E 92/322CSM200883R18010.1223
2322514930E 92/32s*2CSM251493R18010.1233
3323047537E 93/322CSM204753R18010.1832
3323020639E 93/32s*2CSM202063R18010.1842
3+N324047339E 93N/322CSM204733R18010.2521
3+N324514831E 93N/32s*2CSM251483R18010.2541
4324047230E 94/322CSM204723R18010.2441
4324020530E 94/32s*2CSM202053R18010.2451
E 90 fuse disconnectors for 8.5 x 31.5 mm fuses
1201009832E 91/202CSM200983R18010.0616
1201024231E 91/20s*2CSM202423R18010.0626
2202009535E 92/202CSM200953R18010.1223
2202896234E 92/20s*2CSM289623R18010.1233
3203009436E 93/202CSM200943R18010.1832
3203896135E 93/20s*2CSM289613R18010.1842
*s: version with blown fuse indicator
ModulesBbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Pack
unit pcs
38ø 10.3
31.5ø 8.5
PolesRated
current
In [A]
E 90h fuseholders for 10.3 x 38 mm fuses
1+N 321009139E 91hN/322CSM200913R18010.0706
1+N321065739E 91hN/32s*2CSM206573R18010.0716
3+N323047438E 93hN/322CSM204743R18010.1922
3+N323743439E 93hN/32s*2CSM274343R18010.1932
E 90h fuseholders for 8.5 x 31.5 mm fuses
1+N201009634E 91hN/202CSM200963R18010.0706
1+N201007036E 91hN/20s*2CSM200703R18010.0716
3+N203009337E 93hN/202CSM200933R18010.1922
3+N203896036E 93hN/20s*2CSM289603R18010.1932
*s: version with blown fuse indicator
ModulesBbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Pack
unit pcs
26 | E 90 range of fuse disconnectors and fuseholders
Page 27
38ø 10.3
PolesRated
current
In [A]
ModulesBbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
E 90 PV fuse disconnectors for 10.3 x 38 mm fuses (DC-20B)
1321047131E 91/32 PV2CSM204713R18010.0616
1321046936E 91/32 PVs*2CSM204693R18010.0626
2322047032E 92/32 PV 2CSM204703R18010.1223
2322569138E 92/32 PVs* 2CSM256913R18010.1233
*s: version with blown fuse indicator
Pack
unit pcs
51
58ø 22
ø 14
PolesRated
current
In [A]
ModulesBbn
8012542
EAN
DescriptionPiece
TypeABB code
E 90/50 fuseholders for 14 x 51 mm fuses (AC-20B)
1501.5
1501.5
1+N503
1+N503
2503
2503
3504.5
3504.5
3+N506
3+N506
790228
372028
779827
023920
779728
070320
779629
574828
779520
563020
E 91/502CSM279022R18010.0954
E 91/50s*2CSM237202R18010.0954
E 91N/502CSM277982R18010.192
E 91N/50s*2CSM202392R18010.192
E 92/502CSM277972R18010.192
E 92/50s*2CSM207032R18010.192
E 93/502CSM277962R18010.2851
E 93/50s*2CSM257482R18010.2851
E 93N/502CSM277952R18010.381
E 93N/50s*2CSM256302R18010.381
E 90/125 fuseholders for 22 x 58 mm fuses (AC-20B)
11002
11002
1+N1004
1+N1004
21004
21004
31006
31006
3+N1008
3+N1008
775720
896326
773528
049425
771326
049326
775027
049227
965329
049128
E 91/1252CSM277572R18010.1354
E 91/125s*2CSM289632R18010.1354
E 91N/1252CSM277352R18010.272
E 91N/125s*2CSM204942R18010.272
E 92/1252CSM277132R18010.272
E 92/125s*2CSM204932R18010.272
E 93/1252CSM277502R18010.4051
E 93/125s*2CSM204922R18010.4051
E 93N/1252CSM296532R18010.541
E 93N/125s*2CSM204912R18010.541
*s: version with blown fuse indicator
weight
[kg]
Pack
unit pcs
E 90 range of fuse disconnectors and fuseholders | 27
Page 28
Order codes
E 90 series
38.1ø 10.4
57ø 21
60ø 27
PolesRated
current
In [A]
E 90 CC fuseholders for Class CC 10.4 x 38.1 mm fuses
1301998723E 91/302CSM299872R1801 0.0616
1301998822E 91/30s*2CSM299882R1801 0.0626
1+N302998921E 91N/302CSM299892R1801 0.133
1+N302999027E 91N/30s*2CSM299902R1801 0.1313
2302999126E 92/302CSM299912R1801 0.1223
2302999225E 92/30s*2CSM299922R1801 0.1233
3303999324E 93/302CSM299932R1801 0.1832
3303999423E 93/30s*2CSM299942R1801 0.1842
3+N304999522E 93N/302CSM299952R1801 0.2521
3+N303999621E 93N/30s*2CSM299962R1801 0.2531
4304999720E 94/302CSM299972R1801 0.2441
4304999829E 94/30s*2CSM299982R18010.2451
*s: version with blown fuse indicator
PolesRated
current
In [A]
E 90 J fuseholders for Class J 21 x 57 mm fuses
1302048220 E 91/30 J2CSM204822R18010.1354
2304048121 E 92/30 J2CSM204812R18010.272
3306048022 E 93/30 J2CSM204802R18010.4051
1302047926 E 91/30s J *2CSM204792R18010.1354
2304047827 E 92/30s J *2CSM204782R18010.272
3306047728 E 93/30s J *2CSM204772R18010.4051
E 90 J fuseholders for Class J 27 x 60 mm fuses
1602.5047629 E 91/60 J2CSM204762R18010.1753
2605049821 E 92/60 J2CSM204982R18010.351
3607.5049722 E 93/60 J2CSM204972R18010.5251
1602.5049623 E 91/60s J *2CSM204962R18010.1753
2605049524 E 92/60s J *2CSM204952R18010.351
3607.5738824 E 93/60s J *2CSM273882R18010.5251
*s: version with blown fuse indicator
ModulesBbn
8012542
EAN
ModulesBbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
DescriptionPiece
TypeABB code
[kg]
weight
[kg]
Pack
unit
pcs
Pack
unit
pcs
28 | E 90 range of fuse disconnectors and fuseholders
Page 29
Wiring diagrams
and overall dimensions
E 90 series
E 90 wiring diagrams
1P
1P+N
2P
3P
E 90 CC wiring diagrams
1P
1P+N
2P
3P
3P+N
3P+N
4P
4P
E 90 h wiring diagramsE 90 PV wiring diagrams
1P+N1P3P+N2P
E 90 range of fuse disconnectors and fuseholders | 29
Page 30
+–
~
–+
~
~
~
Wiring diagrams
and overall dimensions
E 90 series
Wiring connection E 90
–
+
+–
Wiring diagram for DC networksWiring diagram for AC networks
Overall dimensions
1P
1P+N (E 91h)
1P+N, 2P3P, 3P+N (E 93h)3P+N, 4P
–+
17.5
30 | E 90 range of fuse disconnectors and fuseholders
3552.5
85
70
64
45
Page 31
Wiring diagrams
and overall dimensions
E 90 50/125 series
Wiring diagrams
1P1P+N2P3P3P+N
Overall dimensions
E 90/50
1P+N
1P
26.753.480.1106.853.8
E 90/125
1P
2P
1P+N
2P
3P
3P
3P+N
96.5
3P+N
73.26
43.5
73.26
43.5
112.5
53.81407035105
E 90 range of fuse disconnectors and fuseholders | 31
Page 32
Wiring diagrams
and overall dimensions
E 90 30/60 J series
Wiring diagrams
1P2P3P
Overall dimensions
E 90/30 J
1P
E 90/60 J
1P
2P
2P
3P
3P
73.26
43.5
112.5
1057035
53.8
74.05
43.5
32 | E 90 range of fuse disconnectors and fuseholders
121.5
73.261208040
Page 33
How to choose the protection system
Maximum rated current
value of the fuse
The maximum rated current values of the fuse that can
be installed in the fuseholder are given in the table below.
These values depend on the rated voltage of the network
and conform to the maximum limits of the power dissipated
by the protection system, formed by the fuse and fuseholder.
ABB fuses and fuseholders allow all the requirements
established by the standards to be met in full safety.
The performance provided by ABB products allows a fuse with
a rated current that exceeds the limit dictated by standard
IEC 60269-2-1 to be installed in certain situations.
Fuseholders
Rated
voltage
400 V AC gG
500 V AC gG
690 V AC gG
* = to be used in combination with a device which guarantees protection
against overload.
Fuse
curve
aM
aM
aM
E 90/20
8.5 x 31.5
mm
20 A
10 A
-
-
-
-
E 90/32
10.3 x 38
mm
32 A
32 A
25 A
20 A
-
-
E 90/50
14 x 51
mm
50 A
50 A
25 A
25 A
E 90/125
22 x 58
mm
100 A
125 A*
80 A
80 A
Derating values
for E 90 fuseholders
The derating parameters in the table must be considered if
several poles are installed side by side or if the equipment is
installed in unusual climatic conditions.
Installation of single poles side by side
E 90/32E 91hN/32E 90 50/125
PolesMaximum
current
1…4In1…3In1…3In
5…70.8 x In4…90.7 x In4…60.95 x In
More than 70.7 x InMore than 100.6 x InMore than 70.9 x In
Climatic conditions
E 90/32E 90 50/125
Maximum
temperature
20° CIn20° CIn
30° C95%30° C95%
40° C90%40° C90%
50° C80%50° C85%
Poles Maximum
Maximum
current
current
Maximum
temperature
PolesMaximum
current
Maximum
current
E 90 range of fuse disconnectors and fuseholders | 33
Page 34
E 9F gG cylindrical fuses
The fastest protection for industrial
automation switchboards
E 9F gG series fuses are the best way to protect against overloads and short-circuits together
with series fuse E90. They feature a fast tripping curve that is ideal for protecting electronic
devices, transformers and electric cables. The E 9F gG series is available for all the main sizes
(8.5 x 31.5 mm, 10.3 x 38 mm, 14 x 51 mm e 22 x 58 mm) and with a wide range of rated
current values (from 1 A to 125 A and up to 690 V AC).
All the E 9F series fuses conform to the RoHS directive and are type-approved in accordance
with the most important international naval marks.
31.5ø 8.5
38ø 10.3
E 9F 8 gG 8.5 x 31.5 mm cylindrical fuses
Rated
current
In [A]
1 575733 E 9F8 GG1 2CSM257573R1801 0.004 10
2 563938 E 9F8 GG2 2CSM256393R1801 0.004 10
4 586630 E 9F8 GG4 2CSM258663R1801 0.004 10
6 574835 E 9F8 GG6 2CSM257483R1801 0.004 10
8 563037 E 9F8 GG8 2CSM256303R1801 0.004 10
10 775737 E 9F8 GG10 2CSM277573R1801 0.004 10
12 773535 E 9F8 GG12 2CSM277353R1801 0.004 10
16 771333 E 9F8 GG16 2CSM277133R1801 0.004 10
20 775034 E 9F8 GG20 2CSM277503R1801 0.004 10
E 9F 10 gG 10.3 x 38 mm cylindrical fuses
Rated
current
In [A]
0.5 773337 E 9F10 GG05 2CSM277333R1801 0.007 10
1 771135 E 9F10 GG1 2CSM277113R1801 0.007 10
2 587231 E 9F10 GG2 2CSM258723R1801 0.007 10
4 575436 E 9F10 GG4 2CSM257543R18010.007 10
6 563631 E 9F10 GG6 2CSM256363R18010.007 10
8 586333 E 9F10 GG8 2CSM258633R1801 0.007 10
10 574538 E 9F10 GG10 2CSM257453R1801 0.007 10
12 562733 E 9F10 GG12 2CSM256273R1801 0.007 10
16 775430 E 9F10 GG16 2CSM277543R1801 0.007 10
20 773238 E 9F10 GG20 2CSM277323R1801 0.007 10
25 771036 E 9F10 GG25 2CSM277103R1801 0.007 10
32 587132 E 9F10 GG32 2CSM258713R1801 0.007 10
Bbn
8012542
EAN
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
DescriptionPiece
TypeABB code
[kg]
weight
[kg]
Package
Package
34 | E 90 range of fuse disconnectors and fuseholders
Page 35
51ø 14
58ø 22
E 9F 14 gG 14 x 51 mm cylindrical fuses
Rated
current
In [A]
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
2 775232 E 9F14 GG2 2CSM277523R1801 0.018 10
4 773030 E 9F14 GG4 2CSM277303R1801 0.01810
6 770831 E 9F14 GG6 2CSM277083R1801 0.018 10
8 910039 E 9F14 GG8 2CSM291003R1801 0.018 10
10 909835 E 9F14 GG10 2CSM290983R1801 0.018 10
12 909637 E 9F14 GG12 2CSM290963R1801 0.018 10
16 587835 E 9F14 GG16 2CSM258783R1801 0.018 10
20 576037 E 9F14 GG20 2CSM257603R1801 0.018 10
25 564232 E 9F14 GG25 2CSM256423R1801 0.018 10
32 586937 E 9F14 GG32 2CSM258693R1801 0.018 10
40 575139 E 9F14 GG40 2CSM257513R1801 0.018 10
50 563334 E 9F14 GG50 2CSM256333R1801 0.018 10
E 9F 22 gG 22 x 58 mm cylindrical fuses
Rated
current
In [A]
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
4 571834 E 9F22 GG4 2CSM257183R1801 0.048 10
6 592839 E 9F22 GG6 2CSM259283R1801 0.048 10
8 581031 E 9F22 GG8 2CSM258103R1801 0.048 10
10 569237 E 9F22 GG10 2CSM256923R1801 0.048 10
12 594031 E 9F22 GG12 2CSM259403R1801 0.048 10
16 582236 E 9F22 GG16 2CSM258223R1801 0.048 10
20 570431 E 9F22 GG20 2CSM257043R1801 0.048 10
25 595335 E 9F22 GG25 2CSM259533R1801 0.048 10
32 583530 E 9F22 GG32 2CSM258353R1801 0.048 10
40 571735 E 9F22 GG40 2CSM257173R1801 0.048 10
50 593935 E 9F22 GG50 2CSM259393R1801 0.048 10
63 582137 E 9F22 GG63 2CSM258213R1801 0.048 10
80 570332 E 9F22 GG80 2CSM257033R1801 0.048 10
100 595236 E 9F22 GG100 2CSM259523R1801 0.048 10
125 583431E 9F22 GG125 2CSM258343R1801 0.048 10
Technical specifications
Rated voltage [V]400, 500, 690 AC
Rated current [A] 0.5…125
Breaking capacity [kA] 20, 120
Overall dimensions [mm]8.5 x 31.5, 10.3 x 38, 14 x 51, 22 x 58
Weight [g] 4, 7, 18, 48
MarksLLOYD, BV
StandardsIEC 60269-2; ROHS 2002/98/CE
E 90 range of fuse disconnectors and fuseholders | 35
Page 36
E 9F gG cylindrical fuses
The fastest protection for industrial
automation switchboards
E 9F 8 gG 8.5 x 31.5 mm cylindrical fuses
TypeRated current
[A]
E 9F8 GG1140020
E 9F8 GG2240020
E 9F8 GG4440020
E 9F8 GG6640020
E 9F8 GG8840020
E 9F8 GG101040020
E 9F8 GG121240020
E 9F8 GG161640020
E 9F8 GG202040020
E 9F 14 gG 14 x 51 mm cylindrical fuses
TypeRated current
[A]
E 9F14 GG22690120
E 9F14 GG44690120
E 9F14 GG66690120
E 9F14 GG88690120
E 9F14 GG1010690120
E 9F14 GG1212690120
E 9F14 GG1616690120
E 9F14 GG2020690120
E 9F14 GG2525690120
E 9F14 GG3232500120
E 9F14 GG4040500120
E 9F14 GG5050500120
Rated voltage
[V AC]
Rated voltage
[V AC]
Breaking
capacity
[kA]
Breaking
capacity
[kA]
E 9F 10 gG 10.3 x 38 mm cylindrical fuses
TypeRated current
[A]
E 9F10 GG050.5500120
E 9F10 GG11500120
E 9F10 GG22500120
E 9F10 GG44500120
E 9F10 GG66500120
E 9F10 GG88500120
E 9F10 GG1010500120
E 9F10 GG1212500120
E 9F10 GG1616500120
E 9F10 GG2020500120
E 9F10 GG2525500120
E 9F10 GG3232400120
E 9F 22 gG 22 x 58 mm cylindrical fuses
TypeRated current
[A]
E 9F22 GG44690120
E 9F22 GG66690120
E 9F22 GG88690120
E 9F22 GG1010690120
E 9F22 GG1212690120
E 9F22 GG1616690120
E 9F22 GG2020690120
E 9F22 GG2525690120
E 9F22 GG3232690120
E 9F22 GG4040690120
E 9F22 GG5050690120
E 9F22 GG6363690120
E 9F22 GG8080690120
E 9F22 GG100100500120
E 9F22 GG125125500120
Rated voltage
[V AC]
Rated voltage
[V AC]
Breaking
capacity
[kA]
Breaking
capacity
[kA]
36 | E 90 range of fuse disconnectors and fuseholders
Page 37
Power dissipation [W]
In
[A]
0.50.55
10.350.070.60
20.450.450.75
40.060.501.101.25
60.830.851.251.40
810.951.451.60
101.201.301.651.90
121.301.401.802
161.701.902.352.50
2022.402.753.40
252.402.703.103.50
322.803.603.70
4044.30
504.805.30
636.30
807.40
1008.3
12511.3
Size [mm]
8.5 x 31.510.3 x 38 14 x 51 22 x 58
It is important to make sure that the
power dissipated by the fuse does not
exceed the limit imposed by the
fuseholder in which it is installed.
The maximum power dissipation values,
in accordance with the specifications
of the E 90 fuseholders series and
IEC 60269-2 standard, are highlighted
in green.
E 90 range of fuse disconnectors and fuseholders | 37
Page 38
E 9F gG cylindrical fuses
The fastest protection for industrial
automation switchboards
38 | E 90 range of fuse disconnectors and fuseholders
Page 39
Maximum length [m] of the copper conductors
Copper
conductor section
[mm²]
1.599/11386/8740/5921/2913/167/9
2.5134110/12267/8441/5125/3313/208/11
4183139108/11967/8446/5824/3214/177.3/10
621416513994/11355/7033/4120/27
1027522617213090/10857/70
16283217168128
25336257197
35367283
50379
Rated current In [A] of gG fuses
1620253240506380100125
Use this table to find the cable length,
in meters, that is protected by a fuse.
Just cross the rated current of the fuse (in the columns)
with the section of the conductor (on the lines).
The resulting number corresponds to the protected length
of the conductor: for example, a 32 A fuse can protect up
2
to 214 meters of 6 mm
section cable. When there are two
values, it means that the maximum length of the cable is
between the two numbers given in the table.
E 90 range of fuse disconnectors and fuseholders | 39
Page 40
E 9F aM cylindrical fuses
Delayed protection for motor starts
E 9F aM series fuses are the best way to protect against overloads and short-circuits together
with series fuse E90. They feature a delayed tripping curve and are therefore ideal for protecting
industrial motors that require high inrush current during the starting phase.
The E9FaM series is available for all the main sizes (8.5x31.5mm, 10.3x38mm,
14x51mm e 22x58mm) and with a wide range of rated current values (from 1A to 125A
and up to 690VAC). All the E9F series fuses conform to the RoHS directive and are
type-approved in accordance with the most important international naval marks.
E 9F 8 aM 8.5 x 31.5 mm cylindrical fuses
31.5ø 8.5
Rated
current
In [A]
1 772835 E 9F8 AM1 2CSM277283R1801 0.004 10
2 770633 E 9F8 AM2 2CSM277063R1801 0.004 10
4 587439 E 9F8 AM4 2CSM258743R1801 0.004 10
6 575634 E 9F8 AM6 2CSM257563R1801 0.004 10
8 563839 E 9F8 AM8 2CSM256383R1801 0.004 10
10 586531 E 9F8 AM10 2CSM258653R1801 0.004 10
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
38ø 10.3
E 9F 10 aM 10.3 x 38 mm cylindrical fuses
Rated
current
In [A]
0.5 574736 E 9F10 AM05 2CSM257473R1801 0.007 10
1 562931 E 9F10 AM1 2CSM256293R1801 0.007 10
2 775638 E 9F10 AM2 2CSM277563R1801 0.007 10
4 773436 E 9F10 AM4 2CSM277343R1801 0.007 10
6 771234 E 9F10 AM6 2CSM277123R1801 0.007 10
8 587330 E 9F10 AM8 2CSM258733R1801 0.007 10
10 575535 E 9F10 AM10 2CSM257553R1801 0.007 10
12 563730 E 9F10 AM12 2CSM256373R1801 0.007 10
16 586432 E 9F10 AM16 2CSM258643R1801 0.007 10
20 574637 E 9F10 AM20 2CSM257463R1801 0.007 10
25 562832 E 9F10 AM25 2CSM256283R1801 0.007 10
32 775539 E 9F10 AM32 2CSM277553R1801 0.007 10
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
40 | E 90 range of fuse disconnectors and fuseholders
Page 41
51ø 14
58ø 22
E 9F 14 aM 14 x 51 mm cylindrical fuses
Rated
current
In [A]
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
1 575337 E 9F14 AM1 2CSM257533R1801 0.018 10
2 563532 E 9F14 AM2 2CSM256353R1801 0.018 10
4 586234 E 9F14 AM4 2CSM258623R1801 0.018 10
6 574439 E 9F14 AM6 2CSM257443R1801 0.018 10
8 562634 E 9F14 AM8 2CSM256263R1801 0.018 10
10 775331 E 9F14 AM10 2CSM277533R1801 0.018 10
12 773139 E 9F14 AM12 2CSM277313R1801 0.018 10
16 770930 E 9F14 AM16 2CSM277093R1801 0.018 10
20 587033 E 9F14 AM20 2CSM258703R1801 0.018 10
25 575238 E 9F14 AM25 2CSM257523R1801 0.018 10
32 563433 E 9F14 AM32 2CSM256343R1801 0.018 10
40 586135 E 9F14 AM40 2CSM258613R1801 0.018 10
45 574330 E 9F14 AM45 2CSM257433R1801 0.018 10
50 562535 E 9F14 AM502CSM256253R1801 0.018 10
E 9F 22 aM 22 x 58 mm cylindrical fuses
Rated
current
In [A]
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[kg]
Package
6 586036 E 9F22 AM6 2CSM258603R1801 0.048 10
8 574231 E 9F22 AM8 2CSM257423R1801 0.048 10
10 562436 E 9F22 AM10 2CSM256243R1801 0.048 10
12 775133 E 9F22 AM12 2CSM277513R1801 0.048 10
16 772934 E 9F22 AM16 2CSM277293R1801 0.048 10
20 770732 E 9F22 AM20 2CSM277073R1801 0.048 10
25 774938 E 9F22 AM25 2CSM277493R1801 0.048 10
32 772736 E 9F22 AM32 2CSM277273R1801 0.048 10
40 770534 E 9F22 AM40 2CSM277053R1801 0.048 10
50 594130 E 9F22 AM50 2CSM259413R1801 0.048 10
63 582335 E 9F22 AM63 2CSM258233R1801 0.048 10
80 570530 E 9F22 AM80 2CSM257053R1801 0.048 10
100 595434 E 9F22 AM100 2CSM259543R1801 0.048 10
125 583639 E 9F22 AM125 2CSM258363R1801 0.048 10
Technical specifications
Rated voltage [V] 400, 500, 690 AC
Rated current [A] 0.5…125
Breaking capacity [kA] 20, 120
Overall dimensions [mm] 8.5 x 31.5, 10.3 x 38, 14 x 51, 22 x 58
Weight[g] 4, 7, 18, 48
MarksLLOYD, BV
Standards IEC 60269-2; ROHS 2002/98/CE
E 90 range of fuse disconnectors and fuseholders | 41
Page 42
E 9F aM cylindrical fuses
Delayed protection for motor starts
E 9F 8 aM 8.5 x 31.5 mm cylindrical fuses
Type Rated current
[A]
E 9F1 AM1140020
E 9F8 AM2240020
E 9F8 AM4440020
E 9F8 AM6640020
E 9F8 AM8840020
E 9F8 AM101040020
E 9F 14 aM 14 x 51 mm cylindrical fuses
Type Rated current
[A]
E 9F14 AM11690120
E 9F14 AM22690120
E 9F14 AM44690120
E 9F14 AM66690120
E 9F14 AM88690120
E 9F14 AM1010690120
E 9F14 AM1212690120
E 9F14 AM1616690120
E 9F14 AM2020690120
E 9F14 AM2525690120
E 9F14 AM3232500120
E 9F14 AM4040500120
E 9F14 AM5050500120
Rated voltage
[V AC]
Rated voltage
[V AC]
Breaking
capacity
[kA]
Breaking
capacity
[kA]
E 9F 10 aM 10.3 x 38 mm cylindrical fuses
Type Rated current
[A]
E 9F10 AM050.5500120
E 9F10 AM11500120
E 9F10 AM22500120
E 9F10 AM44500120
E 9F10 AM66500120
E 9F10 AM88500120
E 9F10 AM1010500120
E 9F10 AM1212500120
E 9F10 AM1616500120
E 9F10 AM2020500120
E 9F10 AM2525400120
E 9F10 AM3232400120
Rated voltage
[V AC]
Breaking
capacity
[kA]
E 9F 22 aM 22 x 58 mm cylindrical fuses
Type Rated current
[A]
E 9F22 AM66690120
E 9F22 AM88690120
E 9F22 AM1010690120
E 9F22 AM1212690120
E 9F22 AM1616690120
E 9F22 AM2020690120
E 9F22 AM2525690120
E 9F22 AM3232690120
E 9F22 AM4040690120
E 9F22 AM5050690120
E 9F22 AM6363690120
E 9F22 AM8080690120
E 9F22 AM100100500120
E 9F22 AM125125500120
Rated voltage
[V AC]
Breaking
capacity
[kA]
42 | E 90 range of fuse disconnectors and fuseholders
Page 43
It is important to make sure that the
power dissipated by the fuse does not
exceed the limit imposed by the
fuseholder in which it is installed.
The maximum power dissipation values,
in accordance with the specifications
of the E 90 fuseholders series and
IEC 60269-2 standard, are highlighted
in green.
Power dissipation [W]
In
[A]
0.50.70
10.090.100.13
20.150.140.18
40.260.280.28
60.350.380.420.45
80.470.550.550.60
100.550.620.650.75
120.70.820.750.85
160.871.051.15
201.051.301.35
251.201.551.70
321.802.052.20
402.652.70
452.85-
502.953.60
634.80
806.20
1006.65
1259.90
Size [mm]
8.5 x 31.510.3 x 38 14 x 51 22 x 58
E 90 range of fuse disconnectors and fuseholders | 43
44 | E 90 range of fuse disconnectors and fuseholders
Page 45
Maximum cable length according to the rated current and section of the conductor
Copper
conductor section
[mm²]
1.555/6437-4525/3015/20
2.511684/9458/6840/4926/3217/20
418114711884/9558/6842/4828/3318/23
6273223178139105/11779/8955/6437/4226/3114/20
10227181147113/12580/9457/6940/47
1623618915112083/97
25231185147
35262210
Rated current In [A] of aM fuses
1620253240506380100125
Use this table to find the cable length,
in meters, that is protected by a fuse.
Just cross the rated current of the fuse (in the columns)
with the section of the conductor (on the lines).
The resulting number corresponds to the protected length
of the conductor: for example, a 32 A fuse can protect up
2
to 139 meters of 6 mm
section cable. When there are two
values, it means that the maximum length of the cable is
between the two numbers given in the table.
E 90 range of fuse disconnectors and fuseholders | 45
Page 46
E 9F gPV cylindrical fuses
The best protection for direct current
photovoltaic installations
The E 9F PV series of cylindrical fuses has been specifically designed for protecting direct
current circuits up to 1000 V.
Available in the 10.3 x 38 mm size for up to 30 A rated current values, they are the best way
to protect the strings, inverters and surge arresters in photovoltaic installations according
to IEC 60269-6 "Supplementary requirements for fuse-links for the protection of solar
photovoltaic energy systems".
E 9F gPV 10.3 x 38 mm cylindrical fuses
38ø 10.3
38ø 10,3
Rated
current
In [A]
1 134565E 9F1 PV 2CSM213456R18010.007 10
2 134664E 9F2 PV 2CSM213466R18010.007 10
3 134763E 9F3 PV 2CSM213476R18010.007 10
4 134862E 9F4 PV 2CSM213486R18010.007 10
5 134961E 9F5 PV 2CSM213496R18010.007 10
6 135067E 9F6 PV 2CSM213506R18010.007 10
7 135166E 9F7 PV 2CSM213516R18010.007 10
8 135265E 9F8 PV 2CSM213526R18010.007 10
10 135364E 9F10 PV 2CSM213536R18010.007 10
12 135463E 9F12 PV 2CSM213546R18010.007 10
15 135562E 9F15 PV 2CSM213556R18010.007 10
20 135661E 9F20 PV 2CSM213566R18010.007 10
25 135760E 9F25 PV 2CSM213576R18010.007 10
30 135869E 9F30 PV 2CSM213586R18010.007 10
Bbn
8012542
EAN
DescriptionPiece
weight
TypeABB code
[Kg]
Package
Technical specifications
Rated voltage [V]1000 DC
Rated current [A]1...30
Breaking capacity [kA]10
Minimum breaking capabilityfrom 1A to 7A = 1.3 x In
Dimensions[mm]10.3 x 38
Weight [g]7
Standards IEC 60269-6; ROHS 2002/98/CE
46 | E 90 range of fuse disconnectors and fuseholders
from 8A to 30A = 2.0 x In
Page 47
E 9F gPV 10.3 x 38 mm cylindrical fuses
TypeRated
current
[A]
Dissipated
power 0.7
In [W]
Dissipated
power 0.8
In [W]
Dissipated
power
In [W]
E 9F1 PV10.1250.1750.25
E 9F2 PV20.1600.2500.32
E 9F3 PV30.660.871.36
E 9F4 PV40.690.81.25
E 9F5 PV50.590.731.12
E 9F6 PV60.420.671.05
E 9F7 PV70.400.641
E 9F8 PV80.770.881.48
E 9F10 PV100.670.91.5
E 9F12 PV120.7211.8
E 9F15 PV150.91.32.2
E 9F20 PV201.11.52.8
E 9F25 PV251.31.83
E 9F30 PV301.51.93.7
The power dissipation of the fuse cannot exceed the maximum power
dissipation accepted by the fuseholder.
Time/current tripping characteristics
Derating in combination with Ambient Temperature
1.4
1.2
1.0
0.8
Derating Coefficient
0.6
0.4
-30
-10
10
Ambient temperature [°C]
30
50
70
t [S]
4
10
10
10
10
10
10
1 A
2 A
4 A
6 A
7 A
5 A
3 A
3
2
1
0
-1
0
10
1
10
2
10
lp [A]lp [A]
3
10
4
10
t [S]
4
10
3
10
2
10
1
10
0
10
-1
10
0
10
8 A
10 A
15 A
25 A
30 A
20 A
12 A
1
10
2
10
3
10
4
10
E 90 range of fuse disconnectors and fuseholders | 47
Page 48
Questions & answers
Technical and regulatory details
concerning the E 90 range
IEC 60947-3: switches, disconnectors,
switch-disconnectors and fuse-combination units
This standard establishes the requirements of a device to
ensure its suitability for disconnection and operation.
Disconnector:
A disconnector is a mechanical control device which, when
open, meets the prescriptions for the disconnection function
laid down by the international IEC 60947-3 standard.
Opening a disconnector ensures that downstream the circuit
is electrically isolated from upstream. This condition is
necessary if you need to operate on a network component,
e.g. during maintenance. Pursuant to the IEC 60364
standard, any maintenance operations on the installation are
prohibited unless circuits have been previously disconnected.
Fuse-disconnector:
This defines a fuseholder that also performs disconnecting
functions. Not all fuseholders are also disconnectors: to meet
this definition they must meet the requirements and pass the
tests provided for in the IEC 60947-3 standard.
Fuse-switch-disconnector:
According to the IEC 60947-3 standard, this definition
concerns a fuse-disconnector that enables switching under
load. Not all fuse-disconnectors enable this operation: to be
considered as a fuse-switch-disconnector a device must have
utilization category equal to AC-21B or above.
Utilization categories:
Not all devices intended for disconnection have the same
performance. The type of operation allowed depends on a
designation that specifically defines the methods of use,
i.e. the utilization category.
This identifies:
a. The nature of current (AC/DC)
b. The type of switching allowed (no load, resistive loads,
highly inductive loads, etc.)
c. The operation frequency
E 90 fuse-switch-disconnectors have AC-22B utilization
category up to 400V and utilization category AC-20B up to
690 V. The E 90 PV fuse-disconnectors have DC-20B
utilization category. E 90 50/125 fuse-disconnectors have
utilization category AC-20B.
Current
nature
Alternating
current
Direct
current
Which loads can be disconnected using a product with
AC-22B utilization category?
The AC-22B utilization category allows occasional operation
of mixed, resistive and inductive loads with moderate
overloads in alternating current circuits. Mixed loads include:
transformers, corrected motors, capacitor batteries, discharge
lamps, heating, etc.
Utilization category Typical applications
AB
AC-20AAC-20BConnecting and disconnetting under
no-load conditions
AC-21AAC-21BSwitching of resistive loads including
moderate overloads
AC-22AAC-22BSwitching of mixed resistive
and inductive loads, including
moderate overload
AC-23AAC-23BSwitching of motor loads or other
highly inductive loads
DC-20ADC-20BConnecting and disconnecting
under no-load conditions
DC-21ADC-21BSwitching of resistive loads including
moderate overloads
DC-22ADC-22BSwitching of mixed resistive and
inductive loads, including moderate
overloads (e.g. shunt motors)
DC-23ADC-23BSwitching of highly inductive loads?
(e.g. series motors)
48 | E 90 range of fuse disconnectors and fuseholders
Which loads can be disconnected using a product with
AC-20B utilization category?
The AC-20B utilization category does not allow operation
under load. Disconnection is possible only by first
disconnecting the load through an appropriate switch.
Page 49
IEC 60269-1: Fuses with voltage not exceeding 1000V
in alternating current and 1500V in direct current
This standard establishes the requirements of low voltage
fuses, and as a result the requirements of fuseholders as
devices intended to accommodate fuses.
This standard includes two different sections, with different
requirements depending on the type of individual using the
equipment:
IEC 60269-2: supplementary requirements for fuses for use
by skilled persons (mainly for industrial
application).
IEC 60269-3: supplementary requirements for fuses for use
by unskilled persons (mainly for household and
similar applicationss).
What is the difference between a IEC 60947-3-compliant
fuseholder and a IEC 60947-2-compliant fuseholder?
These are two complementary standards: IEC 60269-2
establishes the characteristics of fuses, and, from these
general requirements for fuseholders are derived. It is the
reference standard for overcurrent protection but not for
disconnection and switching.
Are fuseholders marked UR and UL equivalent to each
other?
They are different products and they comply with equally
different requirements. E 90/32 switch disconnectors conform
to IEC standards and accommodate midget fuses. However,
since they are recognized by the UL laboratories, by means of
the UR mark, they can be used as components in UL-certified
machines designed for the American market.
On the other hand, E 90/30 CC fuseholders are specifically
designed and tested in accordance with the American
standards. They are able to accommodate Class CC
cylindrical fuses, which possess particular limitation
characteristics. This means that it is forbidden to use
10.3 x 38 fuses that conform to IEC standards in E 90/30 CC
fuseholders.
E 90 range of fuse disconnectors and fuseholders | 49
Page 50
Questions & answers
Technical and regulatory details
concerning the E 9F range
Maximum rated current for cylindrical fuses according
to IEC 60269-2
Size of fuse
[mm]
8.5 x 31.52512----
10.3 x 38323225201612
14 x 51--50505040
22 x 58--1001008080
Maximum rated current for fuse holders according
to IEC 60269-2
Fuse size [mm]In [A]
8.5 x 31.525
10.3 x 3832
14 x 5150
22 x 58100
The E 90 series were designed and certified in
accordance with the IEC 60269-2 standard which sets forth
the maximum rated current values envisaged for fuses and
fuseholders as summarized in the tables above.
Therefore, the characteristics according to which the units
were certified are shown on their rating plates.
400 V a.c.500 V a.c.690 V a.c.
gGaMgGaMgGaM
A
I
n
Can fuses with rated current values higher than the
one indicated in the table be used?
For example, can a 22 x 58 mm 125 A fuse be used in a
E 90/125 fuseholder?
Yes, in compliance with the instructions provided by the
manufacturer, a fuse with a higher rated current than the one
indicated in the tables above can be used: it is necessary
to verify that the power dissipation value of the fuse does
not exceed the maximum acceptable power value of the
fuseholder. In this specific case, if a 22 x 58 mm fuse used at
125 A dissipates a maximum power which is equal to or less
than 9.5 W, it can be used in an E 90 125 fuseholder at a
rated current of 125 A.
Since the above statement is generally valid for aM-type
fuses, it has not to be forgotten the need to associate to it
an overload protection devices. In fact, the aM-type fuses,
unlike the gG-type ones, are designed to provide protection
only against short-circuits and would act on overloads only
after a long time, thus pushing the product beyond its own
physical limits, beyond which it would no longer be possible
to guarantee its proper operation.
Can instead, a 10.3 x 38 mm 32 A gG fuse be used in a
10.3 x 38 mm E 90/32 fuseholder with a rated voltage
exceeding 400 V?
In this specific case, an E 9F10 GG32 fuse dissipates 2.8 W
at 400 V rated voltage. Since an E 90/32 series fuseholder for
10.3 x 38 mm fuses achieves 3 W thermal dissipation, the
fuse in question can be used at 400 V rated voltage or less.
On the other hand, use of rated voltage exceeding 400 V fails
to allow the equipment to comply with the maximum
dissipated power limit.
50 | E 90 range of fuse disconnectors and fuseholders
Page 51
Maximum values of rated power dissipation of a fuse-link
according to IEC 60269-2.
Characteristic
curve
gG2.5 W3 W5 W9.5 W
aM0.9 W1.2 W3 W7 W
gPV3 W
The table above gives the maximum dissipated power values
of the fuses, considering their size and characteristic curve,
and ate the same time the minimum power acceptace to be
tolerated by a fuseholder.
The rated acceptable power dissipation of a fuseholder is
displayed in the next table.
Size of fuse
8.5 x 31.510.3 x 3814 x 5122 x 58
Size of fuse [mm]8.5 x 31.510.3 x 38 14 x 5122 x 58
Maximum acceptable
power dissipation
2.5 W3 W5 W9.5 W
E 90 Wizard
E 90 Wizard is an APP to easily select fuse and fuse holder
codes in few simple steps wherever you are.
E 90 Wizard helps you to select ABB codes for E 90 and E 9F
series for all the applications: industrial, residential, photovoltaic
and North American markets.
In few taps E 90 Wizard can provide you the right code, listing
you technical characteristics and documentation links.
E 90 range of fuse disconnectors and fuseholders | 51
Page 52
Contact us
The data and illustrations are not binding. We reserve
the right to modify the contents of this document on the
basis of technical development of the products,
without prior notice.
Copyright 2014 ABB. All rights reserved.
2CSC444002B0204 - 11/2014 - 2.000 CAL.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.