1
Read all the instructions carefully
DY GPS
is a GPS module that allows you to capture the information of date, time and position from satellites. This information may be shared with DY365 device designed to interface with synchronization always perfect.
Code Model Description 2CSM250411R1000 DY GPS GPS module for external use
DY GPS
, so as to ensure a
DIMENSIONS (mm)
2
79
20
52
41
CONNECTION DIAGRAMS
3
I/O extension
port
DEVICE STATUS
4
• When you power on the led emits two red flashes as follows:
OFF ON OFF ON OFF
1 s 1 s 1 s
After the power on sequence, the DY GPS:
- acquires data of time, date, latitude, longitude and number of satellites received about every 30 seconds
- sends data of time, date, latitude, longitude to the I/O extension port (and to the connected devices) every 30 minutes
The flashing of the green led indicates the number of the received satellites
(the higher the number of satellites received, the better the reception of the information):
Number of satellites Green led sequence
0 - 2 500 ms 500 ms continuous 3 – 5 100 ms 300 ms 3 every 5 seconds 6 – 8 100 ms 300 ms 6 every 5 seconds
9 – 12 100 ms 300 ms 9 every 5 seconds
• Sending data to the I/O extension port (and to the connected devices) is signaled
by the red flashing of the led for 3 seconds as follows:
ON OFF ON OFF …..
100 ms 100 ms 100 ms 100 ms …..
Note: at any time you can force sending data to the I/O extension port by pressing
the key (accessible by removing the cover, see figure 2).
• Failure to receive the correct data for more than 60 seconds causes an auto-reset
of the device. After three fruitless recovery attempts, this condition is signaled by the red flashing of the led as follows:
ON OFF ON OFF …..
500 ms 500 ms 500 ms 500 ms …..
In this case, the DY GPS tries to restore the operation of the GPS module by
continuing signaling; in case it succeeds, it will return to normal operation (flashing of the led of green colour according to the number of the detected satellites).
• Failure to receive the correct data for more than 30 minutes causes an auto-
reset of the device with loading of factory settings and subsequent restart. This condition is signaled by the orange flashing of the led for 3 seconds as follows:
ON OFF ON OFF …..
300 ms 300 ms 300 ms 300 ms …..
ON OFF REPETITIONS
SAFETY WARNINGS
During product installation and operation it is necessary to observe the
following instructions:
1) The product must be installed by a qualified person, in strict compliance with the connection diagrams.
2) Do not power the instrument if any part of it is damaged.
3) The product must be installed and activated in compliance with current electric system standards.
4) The electrical system in the building in which the product is to be installed should have an over-current switch and a protection device.
5) Do not use the product for purposes different from the one specified.
6) In case of malfunction do not perform repairs and contact immediately the technical support.
7) The product can be used in environments with category of overvoltage III and pollution degree 2.
8) Before accessing the connection terminals, verify that the leads are not live.
9) After installation, inaccessibility to the connection terminals without appropriate tools must be guaranteed.
TECHNICAL CHARACTERISTICS
• Power supply: 12V DC (-20% ÷ +20%)
• Absorption: 30mA max (during receiving GPS)
• Wall or pole installation
• Wiring
– Cable length: 100m – Flexible cables section: 0.75 ÷ 1.5 mm – Sheathed cables maximum diameter: 3 mm
• Protection degree: IP54
• Operating temperature: 0 ÷ +50 °C
• Storage temperature: -25 ÷ +70 °C
• Operating humidity: 20÷90% non condensing
• Key to force sending data to the connected devices
• Red / green / orange led for signaling device status (Figure 1)
2
INSTALLATION
5
• Installation can be wall or pole (by using the adapter in the package)
• Remove the cover by leveraging the teeth on the sides of the product
• Pass the cables through the cable entry on the bottom side and connect the power and bus cables respecting the wiring diagram
• Tighten the cable gland and replace the cover.
Key to force sending data to the devices
Led for signaling device status
Figure 1 Figure 2
REFERENCE STANDARDS
Compliance with Community Directives: 2014/30/EU (EMCD) 2014/53/EU (RED) is declared with reference to the following harmonized standards:
• EN 60950-1
• ETSI EN 301 489-1, ETSI EN 301 489-3, ETSI EN 300 440-1, ETSI EN 300 440-2