ABB DRAF enclosed direct-on-line starters Catalog Page

Page 1
9/6 ABB MOTOR PROTECTION AND CONTROL
DRAF enclosed direct-on-line starters
Experience reliable and easy to install motor starting
Improve installation efficiency
• Easy to connect and to operate
• Pre-wired control circuit and easy to follow wiring instructions
• Coil energy consumption down by 80%.
Reliable in harsh condition
High number of electrical and mechanical operations
• Robust IP66 and type 4X enclosure
• Double electrical insulation.
09
Continuous operation
• AF contactors manage voltage fluctuation, chattering free
• Protected motor with thermal overload relay
• Safety through coordinated product.
For machine or wall mounting
Main applications
Control of stand alone motors like for heat pumps, air conditioning units, small machine tools, compressors, pumping, irrigation...
1SBC133007S0201
Page 2
ABB MOTOR PROTECTION AND CONTROL 9/7
Motor starting solutions up to 7.5 kW and 10 hp
AF 3-pole contactor with
4 cable entries
holding contact
Start contact block
1 PE and 1 neutral terminal
TF42 thermal overload relay
"I" ON button
"0" OFF/RESET button
09
1SBC133008S0201
Page 3
9/8 ABB MOTOR PROTECTION AND CONTROL
DRAF09 … DRAF16 enclosed direct-on-line starters
Up to 7.5 kW and 10 hp, protected by thermal overload relays AC operated
Enclosed direct-on-line (DOL) starters are used for controlling 3-phase asynchronous motors up to 690 V AC.
Each starter is delivered assembled and wired. It contains:
• IP66 and type 4X plastic enclosure with double insulation, equiped with:
- 1 green flush "I" ON button and 1 red protruding "O" OFF/RESET button
- 4 cable inlets and outlets via knockouts.
• 1 AF 3-pole contactor with holding contact
• 1 CB5-10 start contact block
• 1 PE and 1 neutral terminal.
Control supply wiring:
IEC starters type: phase-to-phase, separate supply or phase-to-neutral.
1SBC13300 5V0014
UL starters type: separate supply.
09
DRAF + TF42 to be ordered separatel y
TF42 thermal overload relay to be ordered separately and choses according to motor's nominal
current (see table in the next page).
DRAF enclosed DOL starters
IEC - AC-3 Control supply Rated operational
power max.
220 V 230 V 240 V
kW kW kW kW A V 50/60 Hz kg
380 V 400
500 V 690 V
V
current
θ Ue=400 V
wiring
≤ 40 °C
Rated control circuit voltage
c m
in ... Uc max
U
(1)
Typ e Order code Weight
Pkg
(1 pce)
IEC starters type
2.2 4 5.5 5.5 9 Separate supply 24…60 DR AF0 9-11S 1SBK134237R1100 0.820
3 5.5 7.5 7.5 12 Separate supply 24…60 DRAF12-11S 1SBK154237R1100 0.820
4 7.5 9 9 18 Separate supply 24…60 DR AF16 -11S 1SBK174237R1100 0.820
(1) Select DR AF..S with s eparate suppl y for 24...60 V DC control c ircuit volt age (change A2 - Us wire to b lue color acc. to IEC 609 47-4-1).
Phase-to-neutral 100...250 DR AF0 9-13N 1SBK134137R1300 0.820 Phase-to-phase 250...500 DR AF0 9-14P 1SBK134037R1400 0.820
Phase-to-neutral 100...250 DRAF12-13N 1SBK154137R1300 0.820 Phase-to-phase 250...500 DR AF12-14P 1SBK154037R1400 0.820
Phase-to-neutral 100...250 DR AF16 -13N 1SBK174137R1300 0.820 Phase-to-phase 250...500 DR AF16 -14P 1SBK174037R1400 0.820
UL starter type with separate control supply wiring
UL / CSA Rated control Horse power ratings
Single phase motor Three phase motor
120 V 240 V 200 V
208 V
hp hp hp hp hp hp V 50/60 Hz kg
0 V
22 240 V
440 V 480 V
550 V 600 V
circuit voltage
c m
in ... Uc max
U
Typ e Order code Weight
Pkg
(1 pce)
UL starters type
0.75 1.5 2 2 5 7.5 24…60 DRAF0 9-11U 1SBK134238R1100 0.820
1 2 3 3 7.5 10 24…60 DRAF12-11U 1SBK154238R1100 0.820
1.5 3 5 5 10 15 24…60 DR AF16 -11U 1SBK17423 8R110 0 0.820
100...250 DR AF0 9-13U 1SBK134238R1300 0.820
250...500 DRAF09-14U 1SBK134238R1400 0.820
100...250 DRAF12-13U 1SBK154238R1300 0.820
250...500 DRAF12-14U 1SBK154238R140 0 0.820
100...250 DR AF16 -13U 1SBK1742 38R1 300 0.820
250...500 DRAF16-14U 1SBK17423 8R14 00 0.820
1SBC133006S0201
Page 4
ABB MOTOR PROTECTION AND CONTROL 9/9
DRAF09 … DRAF16 enclosed direct-on-line starters
Up to 7.5 kW and 10 hp, protected by thermal overload relays AC operated
TF42 thermal overload relays to be ordered separately
ip class Type Order code Weight
Tr
TF42
Setting range Short-circuit
A kg
2CDC231006V0013
0.10 ... 0.13 0.5 A, Fuse type T 10 TF42-0.13 1SAZ721201R1005 0.130
0.13 ... 0.17 1.0 A, Fuse type T 10 TF42 -0.17 1SAZ721201R1008 0.130
0.17 ... 0.23 1.0 A, Fuse type T 10 TF42-0.23 1SAZ721201R1009 0.130
0.23 ... 0.31 1.0 A, Fuse type T 10 TF42- 0.31 1SAZ721201R1013 0.130
0.31 ... 0.41 2.0 A, Fuse type gG 10 TF42-0.41 1SAZ721201R1014 0.130
0.41 ... 0.55 2.0 A, Fuse type gG 10 TF42-0.55 1SAZ721201R1017 0.130
0.55 ... 0.74 4.0 A, Fuse type gG 10 TF4 2-0 .74 1SAZ721201R1021 0.130
0.74 ... 1.00 6.0 A, Fuse type gG 10 TF42-1.0 1SAZ721201R1023 0.130
1.00 ... 1.30 6.0 A, Fuse type gG 10 TF42-1. 3 1SAZ721201R1025 0.130
1.30 ... 1.70 10.0 A, Fuse type gG 10 TF42-1.7 1SAZ721201R1028 0.130
1.70 ... 2.30 10.0 A, Fuse type gG 10 TF42-2.3 1SAZ721201R1031 0.130
2.30 ... 3.10 10.0 A, Fuse type gG 10 TF42-3.1 1SAZ721201R1033 0.130
3.10 ... 4.20 20.0 A, Fuse type gG 10 TF42-4.2 1SAZ721201R1035 0.130
4.20 ... 5.70 20.0 A, Fuse type gG 10 TF42-5.7 1SAZ721201R1038 0.130
5.70 ... 7.60 35.0 A, Fuse type gG 10 TF 42-7.6 1SAZ721201R1040 0.130
7.60 ... 10.0 35.0 A, Fuse type gG 10 TF42-10 1SAZ721201R1043 0.130
10.0 ... 13.0 40.0 A, Fuse type gG 10 TF42-13 1SAZ721201R1045 0.130
13.0 ... 16.0 40.0 A, Fuse type gG 10 TF42-16 1SAZ721201R1047 0.130
16.0 ... 20.0 63.0 A, Fuse type gG 10 TF42-20 1SAZ721201R1049 0.145
protective device
(1 pce)
Empty enclosure with push-button
Empty enclosure with push-button
mm cable inlet/outlet suitable for IEC starter types FR16AF-12 1SBN101337R1000 0.53 Inch cable inlet/outlet suitable for UL starter types FR16AF-12U 1SBN101338R10 00 0.53
To be completed with AF cont actor, TF42 thermal ove rload relay and CB5-10 (1SBN0100 13R1010) st art contact b lock.
1SBC13300 4V0014
09
1SBC133004S0201
Page 5
9/10 ABB MOTOR PROTECTION AND CONTROL
1L13L25
L3
2T14T26
T3
L1 L2 L3
I
O
R
A1
A2
Uc = V
N
U
c
U
V
A1
A2
Uc= U
s
DRAF
A1
A2
Uc= U
s
A1
A2
Uc = V
A1
A2
Uc= U
s
I
DRAF..P
A
M
RESET
STOP
FR1
9596
1314
-3
-4
KM1
KM1
A1+A2-
-
+
107 4.22"
Ø 22.3
131.5 5.18"
2 x Ø 5.5 .22"
218 8.58"
DRAF09 … DRAF16 enclosed direct-on-line starters
Control supply wiring versions
09
DR AF.. S DR AF..U
DR AF.. N DR AF.. P
Phase-to-phasePhase-to-neutralSeparate supply
A1
Uc= U
A2
Wiring diagram
Power circuit AC local control
3-phase motor Phase-to-phase
Single phase motor
Phase-to-neutral Single phase motor
DRAF..P DRAF..N
DRAF..S DRAF..U
DRAF..U DRAF..S DRAF..N
KM1: 5/L3
Us
Us
N
KM1: 3/L2
RESET
STOP
A
M
9596
FR1
-7 1314
I
KM1
-8
A1A2
KM1
.88"
DRAF09, DRAF12, DRAF16
Main dimensions mm, inches
126.5 4.98"
60 2.36"
8 .32"
M5
IEC starter types - ISO M20
Cable inlet Cable outlet
Enclosure top Enclosure bottom
2 x ø 20 mm 2 x ø 20 mm 2 x ø 0.79" 2 x ø 0.79"
UL starter types - NPT
230 9.06"
Cable inlet Cable outlet
Enclosure top Enclosure bottom
1 x 3/4" 1 x 3/4" 1 x 1/2" 1 x 1/2"
1SBC133005S0201
Loading...