Defi nite purpose
Technical data
contactors
30A – 60A 1, 2, 3, & 4 Pole
1
30A – 40A — 1 & 2 pole
Coil technical data DP30C1P DP30, DP40C2P
Nominal coil voltage 24 120 208/240 277 24 120 208/240 277
Maximum pickup volts 18 88 177 221 18 88 177 221
Drop-out volts range 6 – 15 20 – 70 40 – 170 50 – 165 6 – 15 20 – 70 40 – 140 50 – 165
Nominal inrush VA 50 Hz 31 31 35 31 22 22 22 22
Nominal inrush VA 60 Hz 28 28 32 28 20 20 20 20
Nominal sealed VA 50 Hz 6 6 7 6 5.5 5.5 5.5 5.5
Nominal sealed VA 60 Hz 5 5 6 5 4.5 4.5 4.5 4.5
Nominal DC resistance Ohms 17.5 450 1800 2252 13 275 1056 1772
Other specifi cations DP30C1P DP30, DP40C2P
Line and load terminals # 10 – 32 screw
Wire size AWG min – max 16 – 8
Tightening torque (recommended) 25 in. lbs. 40 in. lbs
Coil termination Dual .250 QC (2) Dual .250 QC (2)
Quick connects .250 std. 1 – 1.5 pole Quad Quad
Quick connects .250 std. 2 pole Dual or quad Dual or quad
Covers Optional Standard
Insulation system 130° C Class B 130° C Class B
30A- 60A — 3 pole
Coil technical data DP30, DP40C3P DP60C3P
Nominal coil voltage 24 120 208/240 277 480 24 120 208/240 277 480
Maximum pickup volts 18 88 177 220 384 18 93 177 235 374
Drop-out volts range 6 –15 20 – 70 40 – 140 65 – 185 150 – 270 6 – 15 20 – 70 40 – 135 50 – 180 150 – 286
Nominal inrush VA 50 Hz 65 65 65 65 65 140 140 140 140 140
Nominal inrush VA 60 Hz 60 60 60 60 60 132 132 132 132 132
Nominal sealed VA 50 Hz 7.5 7.5 7.5 7.5 7.5 20 20 20 20 20
Nominal sealed VA 60 Hz 6 6 6 6 6 14 14 14 14 14
Nominal DC resistance Ohms 6.6 165 660 880 1320 2.4 45 180 280 852
Other specifi cations DP30C3P DP40C3P DP60C3P
Line and load terminals # 10 – 32 Screw 1 Box lug 1 Box lug 1
Wire size AWG min – max 16 – 8
Tightening torque (recommended) 25 in. lbs 40 in.lbs 50 in. lbs
Quick connects: power terminals Dual.250 QC Dual.250 QC Dual.250 QC
Coil terminals Dual .250 QC (2) Dual .250 QC (2) #6 – 35 screw & .250 QC (2)
Covers Optional Standard Standard
Insulation system 130° C Class B 130° C Class B 130° C Class B
2 14 – 7 Cu/Al 14 – 2 Cu/Al
1 Box lug 1
2 14 – 4 Cu/Al
1
30A – 40A — 4 Pole
Coil technical data DP30, DP40C4P
Nominal coil voltage 24 120 208/240 277 480
Maximum pickup volts 19.2 88 177 220 384
Drop-out volts range 6 – 15 20 – 70 40 – 140 65 – 185 150 – 270
Nominal inrush VA 50 Hz 68 68 58 58 48
Nominal inrush VA 60 Hz 60 60 55 52 52
Nominal sealed VA 50 Hz 14 14 11 11 11
Nominal sealed VA 60 Hz 9 9 9.5 9.5 9
Nominal DC resistance Ohms 5 148 550 750 2100
Other specifi cations DP30C4P DP40C4P
Line and load terminals # 10 – 32 screw 1 Box Lug
Wire size AWG Min – Max 16 – 8
Tightening torque (recommended) 22 in. lbs 40 in. lbs
Quick connects: power terminals Dual .250 QC Dual .250 QC
Coil terminals Dual .250 QC (2) Dual .250 QC (2)
Covers Optional Standard
Insulation system 130° C Class B 130° C Class B
1 See page 1.82 to 1.85 for description and approximate dimensions.
2 Stranding must be split for #8 wire.
Low Voltage Products & Systems 1.99
ABB Inc. • 888-385-1221 • www.abb-control.com AC 1000 - 11/03
2 14 – 4 Cu/AL