ABB D-3 Instructions Manual

Page 1
Page 2
41-151.1H Type D-3 Direct Current Relay
Sketch 205342
182A787
Figure 1: Schematic Drawing of Magnetic Circuit of Type
D-3 Relay (Top View). Moving Coil Bearing Sup­ports, Springs and Contacts Omitted.
2.2 MOVING COIL
The moving coil rotates in the air gap between the core and the iron frame. Electrical connections are made to the coil through two springs located at the top of the element. One end of each spring is con­nected through a lever am to a head of the coil. cache other end of each spring is fastened to posts mounted in a circular insulation plate. This plate can be rotated to permit adjustment of the zero position of the moving element.
A third spiral spring located at the bottom of the ele­ment provides a current path to the moving contact.
2.3 AUXILIARY SWITCH (CS-1) (WHEN USED)
The auxiliary switch is a small solenoid type switch. A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid. As the plunger travels upward the disc bridges three silver stationary contacts.
2.4 OPERATION INDICATOR (WHEN USED)
The operation indicator consists of a small solenoid coil mounted in a steel frame, a spring restrained armature and a white flag. The indicator is reset by a push rod in the cover.
Figure 2: Internal Schematic of the Type D-3 Relay in the
Type FT-21 Case.

3.0 OPERATION

The D-3 relay operates on the principle of a current carrying conductor (moving coil) located in a mag­netic field (permanent magnet). When a current is applied to the coil of the relay, a torque is produced that rotates the moving coil until the electrical torque is equal to the torque of the restraining spring. The moving contact will assume a position in its travel that is proportional to the current applied to the mov­ing coil.
The direction of movement of the moving coil is determined by the polarity of the current applied to
the roil. In the left zero and suppressed zero D-3 relays, the contacts will move to the right when a cur­rent of the proper magnitude and polarity is applied to the relay. On the other hand, the contact of the center zero relay will move either left or right depending on the polarity and magnitude of the applied current.

4.0 CHARACTERISTICS

The type D-3 relay is supplied in the standard ranges listed in the table below. The numbers on the scale indicate in millivolts the potential required at the relay base terminals to operate the moving element to the indicated scale position.
2
Page 3
Type D-3 Direct Current Relay 41-151.1H
183A342
Figure 3: External Schematic Diagram for Overload or Re-
verse Current Protection, using the Type D-3 Re­lay.
MOVING COIL CIRCUIT
Ranges in
Millivolts, dc
Resistance in Ohms at 25°C
0-10
5-0-5
40-80
100-0-100
0-200
* Other ranges can also be supplied.
Average
0.3
0.3
1.2
6.0
6.0
As shown in the above Table, the D-3 relay is avail­able with a left zero,” “suppressed zero and center zero scale. In the left zero and the “suppressed zero relays the moving contact is located in the extreme left hand position of the scale when the relays are deenergized. The suppressed zero relay is held in this position with considerable more force than the left zero relay. When the relays are ener­gized with voltages of the proper magnitude and polarity, the moving contact moves to the right.
183A343
Figure 4: External Schematic Diagram for Overload Protec-
tion where Trip Currents in Excess of One Ampere Rating Require Use of an Auxiliary Relay.
In the center zero relay, the moving contact is located in the center of the scale when the relay is deenergized. When the relay is energized, the con­tact will move either to the right or left depending upon the polarity of the applied voltage.
A modification of the D-3 relay, in which a rectifier is mounted internally, makes it suitable for ac opera­tion. Full scale deflection can be obtained with 6 milli­amperes ac Relays modified for AC volts can also be supplied.
The relay has a slight time-delay, with inverse char­acteristics. In the usual application the moving coil terminals are connected across a shunt, and this results in longer delay for both operating and reset times. When a shunt is used the operating time for full scale travel at 125% of the full scale operating current is about 4 seconds, while at 1000% it is about .25 second. In applications where no shunt is used, the operating times for the same conditions are about
1.25 and .15 second respectively. When the relay is deenergized, the time required for it to reset from the full scale position to the 10% position is approxi-
3
Page 4
41-151.1H Type D-3 Direct Current Relay
183A344
Figure 5: External Schematic Diagram for Use of External
Auxiliary Relay to Prevent Pumping of the Type D­3 Relay when used for Overload Protection.
mately 5 seconds when a shunt is used, and 2 sec­onds when there is no shunt.
Continuous maximum overload is approximately 1500% of full scale.
The minimum setting which D-3 Relay can accom­modate is 5% of the full scale.

5.0 SETTINGS

For reverse-current protection a sensitivity of 2 per cent is obtained when using a standard 50 milli-volt shunt and setting the relay at 1 millivolt. A 10 per cent sensitivity is obtained by setting the relay at 5 millivolts. These values of sensitivity can be doubled by using a 100 millivolt shunt.
For overload protection the relay is set at the index setting which, with respect to the millivolt drop of the shunt, will operate at desired per cent of overload.
182A785
Figure 6: Internal Schematic of the Type D-3 Relay in the
Type FT-21 Case with Self-Contained Auxiliary Relay used to Prevent Pumping on Overload Pro­tection.
5.1 TRIP CIRCUIT
Amperes contacts will:
(non-inductive load)
Contacts
D-3 relay
contactor switch (when supplied)
dc control
voltage open close
125 V 250 V
125 V 250 V
0.04
0.02
3.5
1.0
1.0
1.0
3.0
3.0
carry
continuously
-------------
-------------
5.0
5.0

6.0 INSTALLATION

The relays should be mounted on switchboard pan­els or their equivalent in a location free from dirt, moisture, excessive vibration, and heat. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mounting or by means of the rear mounting stud or studs for projection mount­ing. Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical
4
Page 5
Type D-3 Direct Current Relay 41-151.1H
182A786
Figure 7: Internal Schematic of the Type D-3 in the Type
FT-21 Case with Two Self-Contained Auxiliary Relays used to Increase Contact Capacity.
connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal studs furnished with the relay for thick panel mounting. The terminal studs may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench.
For detailed FT. case information refer to Instruction Leaflet 41-076.
Standard D-3 relays are calibrated in millivolts mea­sured at the relay terminals. Hence, the resistance of the leads between the relay and the ammeter shunt must be sufficiently low to avoid introducing an excessive error in the relay indication. With the 0-10 or 5-0-5 millivolt relays, leads 8 feet long of 910 B&S gauge copper wire will reduce the relay indication by approximately 5%. if the lead length is less or the conductor size is larger, the error will be correspond­ingly reduced. Relays with higher millivolt ranges have proportionally greater internal resistances, and consequently error due to lead resistance is reduced. For example, a 0-100 millivolt relay with leads as described above would have an error of 0.5% due to lead resistance.
182A788
Figure 8: Internal Schematic of the Type D-3 Relay in the
Type FT-21 Case, Modified for ac Operation.
basis of 1000 amp. per square inch, at .20°C, 6 feet of copper bus-bar will give 50 millivolts drop.

7.0 ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct operations have been made at the factory. Upon receipt of the relay, no customer adjustments, other than those covered under “SETTINGS” should be required.

7.1 ACCEPTANCE CHECK

Check the scale markings by setting either of the two adjustable contacts at a value marked on the scale. Then alternately apply this voltage plus and minus 3%. The contacts should make and break.

7.2 ROUTINE MAINTENANCE

The use of standard ammeter shunts may be avoided by connecting the moving element leads over an equivalent length of bus-bar or cable. On a
All contacts should be cleaned periodically. A contact burnisher S#182A836H0I is recommended for this purpose. The use of abrasive material for cleaning
5
Page 6
41-151.1H Type D-3 Direct Current Relay
contacts is not recommended because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact.
If the moving element should be removed, the bear­ing end-play should be checked when replacing it.
This should be from .020 inch to .025 inch, and can be measured by inserting a feeler gauge between the upper bearing screw and the shoulder on the moving element shaft.
The core and moving coil assembly should not be removed from the frame casting of the D-3 relay unless a keeper having the same radius on the core is placed on the core in such manner as to bridge the iron pole pieces as the core is withdrawn from the bore of the casting. It is necessary also to insert spacers in the air gap so that the core will remain approximately centered when the mounting screws are removed, to prevent damaging the coil winding when sliding the assembly out of the casting.
7.3 AUXILIARY SWITCH (CS-1)
Adjust the stationary core of the switch for a clear­ance between the stationary core and the moving core when the switch is picked up. This can be done by turning the relay upside-down. Then screw up the core screw until the moving core starts rotating. Now back off the core screw until the moving core stops rotating. This indicates the points when the play in the assembly is taken up, and where the moving core just separates from the stationary core screw. Back
off the core screw approximately one turn and lock in place. This prevents the moving core from striking and sticking to the stationary core because of resid­ual magnetism. Adjust the contact clearance for 3/64 by means of the two small nuts on either side of the Micarta disc.
Block main contacts closed and energize trip circuit with rated voltage. Contacts of auxiliary switch (CS-1) should make.
7.4 OPERATION INDICATOR
The operation indicator (when used) consists of a small solenoid coil mounted in a steel frame, a spring restrained armature and a white flag. The indicator is reset by a push rod in the cover. Block the CS-1 aux­iliary relay contacts closed and pass 0.2 amperes AC or DC through the indicator. The white target should fall into view.
The coil has a dc resistance of approximately 2.8 ohms and a continuous current carrying capacity of
0.6 amperes.

8.0 REPAIRS AND RENEWAL PARTS

Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be fur­nished to the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data.
6
Page 7
Type D-3 Direct Current Relay 41-151.1H
Figure 9: Type D-3 Relay without case. 1- Moving Coil. 2 - Current-carrying restraining springs. 3- Permanent Magnet.
4- Iron-Frame. 5- Scale. 6- Moving Contact. 7- Stationary Contacts.
7
Page 8
Loading...