ABB CP-S range, CP-C range Technical data

4
Primary switch mode power supplies CP-S and CP-C range - Standard and Comfort
Technical data
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Type CP-C 24/5.0
Input circuit L, N
Rated input voltage U
Input voltage range CP-C AC 85-264 V AC 85-264 V AC 85-264 V AC
Frequency range AC 47-63 Hz
Current consumption CP-C at 110-240 V AC approx. 2.2-1.2 A approx. 3.5-1.6 A approx. 5.5-2.5 A
Power consumption typ. 135 W typ. 269 W typ. 538 W Inrush current / I
Power failure buffering at rated load CP-C > 100 ms > 40 ms typ. > 40 ms
Starting time after applying supply voltage
Transient overvoltage protection varistors Internal input fuse (apparatus protection, not accessible) 4 A (slow-acting) 6.3 A (slow-acting) 12 A (fast-acting) Discharge current for PE < 3.5 mA
Indication of operational states
Operating status OUTPUT OK: green LED
Output circuit L+, L+, L-, L- short-circuit, no-load and overload proof
Rated output voltage 24 V DC Tolerance of the output voltage CP-C 1 %
Adjustment range of the output voltage
Rated output power 120 W 240 W 480 W Rated output current T Peack output current (power reserve) T Derating 60 °C < T Deviation with CP-C load change statical
Control time typ. < 1 ms Response time 10-90 % CP-C typ. < 30
Residual ripple and switching peaks 20 MHz typ. < 50 mV Parallel connection yes, up to 5 devices, to enable redundancy and to increase
Series connection to increase voltage yes, for decoupling Resistance to reverse feed yes, limited to approx. 35 V DC Power factor correction (PFC) CP-C yes
Output circuit - No-load, overload and short-circuit behaviour see also U/I and I/T curves
Output curve U/I curve with power reserve Current limitation at short circuit approx. 11 A approx. 19 A approx. 25 A Short-circuit protection continuous short-circuit stability Overload protection thermal protection Starting of capacitive loads unlimited
General data
Power dissipation typ. < 15 W typ. < 29 W typ. < 58 W Effi ciency > 88 % MTBF CP-C 500.000 h
IN
2
t ( cold start) CP-C
CP-C 110-240 V AC 110-240 V AC 110-240 V AC CP-S switch position 110 AC
switch position 230 AC 220-240 V AC
DC 100-350 V DC
CP-S switch position 110 AC
switch position 230 AC 184-264 V AC
DC 100-350 V DC
DC 0 Hz
CP-S at 110-120 V AC approx. 2.2-1.2 A approx. 4.2-4.0 A approx. 9.0-8.0 A
at 220-240 V AC - approx. 2.4-2.2 A approx. 4.5-4.0 A
CP-S
CP-S > 100 ms > 50 ms typ. > 50 ms CP-C < 100 ms < 5 ms typ. < 370 ms CP-S < 100 ms < 10 ms typ. < 20 ms
CP-S -1...+5 % CP-C 22-28 V DC, default setting 24 V 0.5 % CP-S fi xed
< 60 °C 5 A 10 A 20 A
a
< 40 °C typ. 7.25 A typ. 12.25 A typ. 22.5 A
a
< 70 °C 2.5 % per Kelvin temperature increase
a
CP-S load change statical typ. < 0.1 % typ. < 0.1 % typ. < 0.1 %
load change dynamical 10-90 % typ. < 3 %
change of the input voltage of 10 % typ. < 0,05 %
CP-S typ. < 30
CP-S no
CP-S 350.000 h
CP-S 24/5.0
110-240 V AC
1)
85-264 V AC
1)
2
< 23 A / approx. 0.9 A
< 23 A / approx. 0.9 A
typ. < 앐0.05 %
capacity, current not symmetrical (CP-S only redundancy)
s < 33 A / approx. 0.2 A2s < 40 A / approx. 1.9 A2s
2
s < 40 A / approx. 1.8 A2s < 70 A / approx. 8 A2s
ms ms typ. < 5 ms
CP-C 24/10.0 CP-S 24/10.0
110-120 V AC
100-350 V DC
1)
85-132 V AC
220-350 V DC
V: device in operation
typ. < 0.05 % typ. < 0.05 %
typ. < 4 ms typ. < 12 ms
PP
CP-C 24/20.0 CP-S 24/20.0
100-350 V DC
1)
typ. < 15 ms
1)
178 
2CDC110004C0204
Primary switch mode power supplies CP-S and CP-C range - Standard and Comfort
Technical data
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Type CP-C 24/5.0
Dimensions (W x H x D)
Weight CP-C
CP-S Minimum distance to other units horizontal / vertical 10 mm / 80 mm Degree of protection enclosure / terminals IP 20 / IP 20 Material of enclosure enclosure shell / cover aluminium / zinc-coated sheet steel Protection class (EN 61140) 1 Mounting DIN rail (EN 50022), snap-on mounting Mounting position horizontal
Electrical connection - Input circuit
Wire size fi ne-strand with wire end ferrule 0.2-2.5 mm
fi ne-strand without wire end ferrule 0.2-2.5 mm
rigid 0.2-2.5 mm Stripping length 7 mm (0.27 inch) 12 mm (0.47 inch) Torque 0.4 Nm 1.2-1.5 Nm
Electrical connection - Output circuit
Wire size fi ne-strand with wire end ferrule 0.12-2.5 mm
fi ne-strand without wire end ferrule 0,.2-2.5 mm2 (26-14 AWG)
rigid 0.12-2.5 mm Stripping length 8 mm (0.315 inch) 12 mm (0,47 inch) Torque 0.4 Nm 1.2-1.5 Nm
Environmental data
Ambient temperature range operation -25...+70 °C
full load 0...+60 °C (without derating)
storage -40...+85 °C Humidity ( Climatic category (IEC/EN 60721) 3K3 Vibration (IEC/EN 60068-2-6) 1-57 Hz, amplitude 0.075 mm / 57-100 Hz, 5 g Shock (IEC/EN 60068-2-27) 30 g all directions
Isolation data
Rated impulse withstand voltage U (type test)
Power-frequency withstand voltage test (routine test)
Pollution degree (EN 50178) 2
Standards
Product standard EN 61204 Low Voltage Directive 73/23/EEC EMC directive 89/336/EEC Electrical safety EN 50178, EN 60950, UL 60950, UL 508 Protective low voltage SELV (EN 60950)
Electromagnetic compatibility
Interference immunity IEC/EN 61000-6-2
Interference emission IEC/EN 61000-6-3
1)
at U > 264 V use additionally an appropriate external fuse
2)
with lateral screw
3)
pluggable connecting terminals, actuate only when power is off
IEC/EN 60068-2-3)
imp
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 4 (8 kV / 15 kV) electromagnetic fi eld (HF radiation resistance) fast transients (Burst) IEC/EN 61000-4-4 Level 4 (4 kV) powerful impulses (Surge) IEC/EN 61000-4-5 Level 4 (2 kV symmetrical, level 3 - 3 kV asymmetrical) HF line emission IEC/EN 61000-4-6 Level 3 (10 V)
electromagnetic fi eld (HF radiation resistance) HF line emission IEC/CISPR 22, EN 55022 Class B
IEC/CISPR 22, EN 55022 Class B
input / output 3 kV AC
input / PE 1.5 kV AC
input / output 1.2 kV AC
input / PE 1.2 kV AC
output / PE 350 V AC
IEC/EN 61000-4-3 Level 3 (10 V/m)
CP-S 24/5.0
2)
56.5 (60
) mm x 130 mm x
137 mm [2.22 (2.36 2)) inch x
5.12 inch x 5.39 inch]
approx. 0.96 kg / 2.11 lb approx. 1.34 kg / 2.95 lb approx. 3.15 kg / 6.94 lb
approx. 0.96 kg / 2.11 lb approx. 1.07 kg / 2.35 lb approx. 2.83 kg / 6.23 lb
3) 3)
3) 3)
93 % at +40 °C, no condensation
CP-C 24/10.0 CP-S 24/10.0
90 (93.5 2)) mm x 130 mm x
137 mm [3.54 (3.68 2)) inch x
5.12 inch x 5.39 inch]
2
(22-14 AWG)
2
(22-14 AWG)
C
(22-14 AWG)
2
(26-14 AWG
2
(26-14 AWG)
)
CP-C 24/20.0 CP-S 24/20.0
200 (203.5 2)) mm x 130 mm x
137 mm [7.87 (8.01 2)) inch x
5.12 inch x 5.39 inch]
-
2
2.5-10 mm
0.5-10 mm2 (20-8 AWG)
0.5-16 mm
2.5-10 mm2 (14-8 AWG
0.5-10 mm2 (20-8 AWG)
0.5-16 mm2 (20-6 AWG)
(14-8 AWG)
2
(20-6 AWG)
-
)
4
 179
2CDC110004C0204