ABB CP-5/3.0, CP-6/3.0, CP-12/2.0, CP-24/3.0 Technical data

4
Primary switch mode power supplies CP-5/3.0, CP-6/3.0, CP-12/2.0 (adj), CP-24/3.0
Technical data
Type CP-5/3.0 CP-6/3.0 CP-12/2.0 CP-12/2.0adj CP-24/0.3
Input circuit L+, L-
DC 105-260 V DC
Frequency range AC 47-440 Hz
Supply voltage fail. bridging time at 100 % load min. 10 ms
Rated input current at 90 V AC 0.4 A 0.5 A 0.6 A 0.7 A 0.2 A
at 260 V AC 0.2 A 0.25 A 0.27 A 0.3 A 0.1 A
Inrush current at 25 °C ( 2 ms) 7.5 A 7.5 A 7.5 A 33 A 7.5 A
Internal input fuse 3 A (slow-acting)
Output circuit L, N
Rated output voltage 5 V DC 6 V DC 12 V DC 12 V DC 24 V DC
Tolerance of the output voltage ± 3 %
Adjustment range of the output voltage - - - 9-15 V DC
Rated output current
Residual ripple max. 50 mV
Input voltage regulation max. ± 0.5 % ± 0.5 % ± 0.1 % ± 0.5 % ± 0.5 %
Deviation with statical max. ± 2.5 % ± 2.5 % ± 0.5 %
load change 10-90 % dynamical max. 5 %
Short-circuit protection overcurrent switch-off with automatic restart
Overloaf protection overtemperature and overcurrent switch-off
Reset after thermal overload switch-off disconnection of AC input voltage 30 s min.
Input current harmonics no limitation
Indication of operational states green LED, output voltage OK
Standards
Electrical safety EN 50178 (VDE 0160) / UL 508 / CSA 22.2
Galvanic isolation, acc. to IEC 664-1 EN 60950 IEC 664-1 safe isolation DIN VDE 0106-101
Electromagnetic compartibility
Interference immunity EN 61000-6-2
electrostatic dischage (ESD) acc. to EN 61000-4-2 level 3 - 6/8 kV
electromagnetic fi eld acc. to EN 61000-4-3 level 3 - 10 V/m
fast transients (Burst) acc. to EN 61000-4-4 level 4 - 4 kV
powerful impulses (Surge) acc. to EN 61000-4-5 3 kV
HF line emission acc. to EN 61000-4-6 level 3 - 10 V
Interference emission EN 61000-6-4
Rated noise acc. to EN 55011 class B
Approvals / Marks
Approvals see tabel of approvals
Marks see tabel of approvals
General data
Effi ciency at nonimal AC load
Dimensions (W x H x D) mm
Weight approx. 0.22 kg (0.49 lb)
Minumim distance to other units horizontal / vertical 10 mm / 50 mm
Degree of protection terminals IP20
Protection class 1
Mounting DIN rail (EN 50022)
Mounting position horizontal
Wire size 2 x 2.5 mm
Environmental data
Temperature range operation 0...+55 °C
Clearances and creepage distances overvoltage category 2, pollution degree 2
Isolation data
Insulation voltage 2.5 kV AC (routine test), 3 kV AC (type test)
/ rated output power 3 A / 15 W 3 A / 18 W 2 A / 24 W 2 A / 24 W 0,3 A / 7 W
approx. 78 % approx. 80 % approx. 80-83 % approx. 79-84 % approx. 70 %
45 x 78 x 100 45 x 78 x 100 45 x 78 x 100 45 x 78 x 100 45 x 78 x 120
enclosure IP50 IP50 IP50 IP20 IP50
storage -25...+75 °C
50 mV
PP
300 mV
PP
2
(2 x 14 AWG)
max. 36 W
200 mV
PP
PP
-
100 mV
PP
174
2CDC110004C0203
Primary switch mode power supplies CP-24/0.5, CP-24/1.0, CP-24/1.5 adj, CP-24/2.0
Technical data
Type CP-24/0.5 CP-24/1.0 CP-24/1.5adj CP-24/2.0 CP-24/2.0
Input circuit L+, L-
Rated input voltahe AC 90-260 V AC 90-140 V AC 140-260 V AC
DC 105-260 V DC - 160-260 V DC
Frequency range AC 47-440 Hz 47-63 Hz 47-440 Hz
Supply voltage fail. bridging time at 100 % load min. 10 ms
Rated input current max. at 90 V AC 0,35 A 0,6 A 0,8 A 1 A -
max. at 140 V AC - - - - 0,65 A
max. at 260 V AC - 0,27 A 0,38 A - -
typ. at 115 V AC 0,27 A - - - -
typ. at 230 V AC 0,14 A - - - -
Inrush current at 25 °C ( 2 ms) at 140 V - - - 18 A -
at 260 V 33 A 7,5 A 33 A - 7,5 A
Internal input fuse
Output circuit L, N
Rated output voltage 24 V DC
Tolerance of the output voltage ± 3 %
Adjustment range of the output voltage - - 21-28 V DC
Rated output current / rated output power 0.5 A / 12 W 1 A / 24 W 1.5 A / 36 W 2 A / 48 W
Residual ripple max. 200 mV
Input voltage regulation max. ± 0.5 % ± 0.1 % ± 0.5 % ± 0.5 %
Deviation with statical max. ± 0.5 %
load change 10-90 % dynamical max. 5 %
Short-circuit protection overcurrent switch-off with automatic restart
Overload protection overtemperature and overcurrent switch-off
Reset after thermal overload switch-off
Input current harmonics no limitation
Indication of operational states green LED, output voltage OK
Standards
Electrical safety EN 50178 (VDE 0160) / UL 508 / CSA 22.2
Galvanic isolation, acc. to EN 60950 IEC 664-1 EN 60950 IEC 664-1 IEC 664-1 safety isolation DIN VDE 0106-101
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electroststic discharge (ESD) acc. to EN 61000-4-2 level 3 - 6/8 kV
elektromagnetic fi eld acc. to EN 61000-4-3 level 3 - 10 V/m
fast transients (Burst) acc. to EN 61000-4-4 level 4 - 4 kV
powerful impulses (Surge) acc. to EN 61000-4-5 2/4 kV 3 kV
HF line emission acc. to EN 61000-4-6 level 3 - 10 V
Interference emission EN 61000-6-4
Radiated noise acc. to EN 55011 class B
Approvals / Marks
Approvals see table of approvals
Marks see table of approvals
General data
Effi ciency at nominal AC-load ca. 80-84 % ca. 82-84 % ca. 83-85 % 86 %
Dimensions (W x H x D) mm
Weight approx. 0.22 kg (0.49 lb) 0.3 kg (0.66 lb)
Minumim distance to other units horizontal / vertical 10 mm / 50 mm
Degree of protection terminals IP20
enclosure IP20 IP50 IP20 IP20 IP20
Protection class 2 (terminal
Mounting DIN rail (EN 50022)
Mounting position horizontal
Wire size 2 x 2.5 mm
Environmental data
Temperature range operation 0...+55 °C
storage -25...+75 °C
Clearances and creepage distances overvoltage category 2, pollution degree 2
Isolation data
Insulation voltage 2.5 kV AC (routine test), 3 kV AC (type test)
0.8 A (slow-acting)
PP
automatic reset
after coling down
22.5 x 78 x 120
covers required)
300 mV
disconnection of AC input voltage 30 s min.
45 x 78 x 100 45 x 78 x 120
3 A (slow-acting)
max. 36 W
PP
2
(2 x 14 AWG)
--
200 mVPP 200 mV
1
PP
4
175
2CDC110004C0203
Loading...