ABB COQ Instruction Leaflet

ABB Power T&D Company Inc.
Relay Division Coral Springs, FL 33065
Instruction Leaflet
I.L. 41-161J
Type COQ
Negative Sequence Generator Relay
Supersedes I.L. 41-161H Dated July 1984 ( | ) Denotes Change Since Previous Issue
CAUTION
!
Before putting protection relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment. Make sure that all moving parts operate freely. Inspect the contacts to see that they are clean and can close prop­erly. Operate the relay to check the settings and electrical connections.
1. APPLICATION
The COQ is used to prevent a synchronous machine from being damaged due to negative sequence fault currents. Two varieties are available, as shown in Figures 2 and 3, depending upon whether the neutral can be formed at the COQ or whether the neutral must be formed elsewhere. (See external schematic, Figures 8 and 9.)
2. CONSTRUCTION AND OPERATION
The COQ consists of an induction disc overcurrent unit, a negative sequence filter, and an indicating contactor switch (ICS).
2.1. Overcurrent Unit
This is an induction-disc type unit operated by nega­tive sequence quantities supplied to an electromag­net in the rear of the relay. A voltage is induced in the secondary coil of this electromagnet by transformer action of the main coil. Both coils are located on the center leg of the electromagnet. Current flow is from the secondary coil to coils on the outer legs of the
(50/60 Hertz)
electromagnet. The reaction between the outer leg coil fluxes and the main coil flux creates an operating torque on a spiral shaped aluminum disc mounted on a vertical shaft.
2.2. Indicating Contactor Switch Unit (ICS)
The dc indicating contactor switch is a small clapper type device. A magnetic armature, to which leaf­spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers on the arma­ture deflect a spring located on the front of the switch, which allows the operation indicator target to drop. The target is reset from the outside of the case by a push rod located at the bottom of the cover.
The front spring, in addition to holding the target, pro­vides restraint for the armature and thus controls the pickup value of the switch.
3. CHARACTERISTICS
3.1. Overcurrent Unit
The COQ negative sequence relay is available with the following negative sequence current taps:
3 3.25 3.5 3.8 4.2 4.6 5.0
These tap values represent the current transformer secondary amperes which correspond to one per unit generator current. At these values of negative sequence current, the moving contact will leave the time dial stop and reach the stationary contacts in a time as determined by the time dial setting and is as shown by Figure 7. For example, with a time dial
All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
I.L. 41-161J
TABLE 1
Typical Overcurrent Unit Burden And Thermal Rating
Input Continuous One Second Watts at Volt Amps Circuit Impedance
Condition Phase Rating Amps Rating Amps 5 Amps At 5 Amps Z ∠θ (R+jX)
Three A 5 100 8.3 8.3 0.33 0° (0.33+j 0.00)
Phase B 5 100 1.3 3.8 0.15 110° (-0.05+j 0.14)
C 5 100 2.9 4.7 0.19 52° (0.11+j 0.15)
PHASE-TO-PHASE FAULT CONDITION
Phase A-B 5 100 6.1 6.5 0.26 ∠−161.7° (-0.24-j 0.08)
To B-C 5 100 3.4 8.0 0.32 65° (0.13+j 0.29)
Phase C-A 5 100 10.2 11.5 0.46 ∠−152° (-0.41-j 0.22)
PHASE-TO-NEUTRAL FAULT CONDITION
Phase A-N 5 100 5.1 5.2 0.21 8.70° (0.20+j 0.03)
To B-N 5 100 3.5 3.8 0.51 24.3° (0.14+j 0.06)
Neutral C-N 5 100 4.8 5.5 0.22 29.0° (0.19+j 0.11)
setting of “4” the relay will close its contacts in 30 seconds with the above tap currents applied to the relay.
As shown by the curves of Figure 5, the relay’s char­acteristic is defined by a generator characteristic I22T = K. The relay characteristic is such that it coin­cides with the generator characteristic at 1 per unit negative sequence current but at higher values of negative sequence current, the relay characteristic is substantially parallel and slightly less than the gener­ator characteristic. In this manner, a suitable margin of safety is obtained between the two characteristics.
Figure 5 defines the relay characteristics for two gen­erators – one with a permissible constant of “30” and the other with a constant of “90”. The time dial set­tings for these constants are “4” and “11” respec­tively. Similar protection for other generators with I22T constants between “30” and “90” is obtained by settings of the time dial. Figure 4 shows the neces­sary time dial settings for various I22T constants. By referring to this figure, the time dial can be set so the relay protects different generators whose I22T con­stants range from “30” to “90”.
contact spacing. For this figure a tap setting of 3 is used with a machine full load current of 4.
Typical time-current curves of the relay are shown in Figure 7. Minimum pickup is approximately 0.6 of the tap value current. See Table 1 for burdens and termi­nal ratings.
3.2. Trip Circuit
The main contacts will safely close 30 amperes at 250 volts dc and the seal-in contacts of the indicating contactor switch will safely carry this current long enough to trip a circuit breaker.
The indicating contactor switch has two taps that pro­vide a pickup setting of 0.2 or 2 amperes. To change taps requires connecting the lead located in front of the tap block to the desired settings by means of a screw connection.
3.3. Indicating Contactor Switch (ICS)
0.2 ampere tap 6.5 ohms dc resistance
2.0 ampere tap 0.15 ohms dc resistance
4. SETTING CALCULATIONS
Figure 6 demonstrates the use of a tap setting lower than the full load current of the machine to accommo­date I22Tlimits from 5 to 10 while still providing wide
Determine from the machine manufacturer the per­missible I22T constant. From Figure 4, find the required time dial setting.
3
Loading...
+ 8 hidden pages