ABB 2CCS800900R0161, 2CCS800900R0011, 2CCS862001R0804, 2CCS863001R0824, 2CCS862001R0634 User Manual

...
ABB
Technical Manual
ABB Schweiz AG
Please use also the assembly instruction S800-RSU-H Remote Switching Unit for S800 2CCC413020M0204
Functi onal Descr iption for S800-RSU-H / S800W-RSU
2CCC413022M0205
SUBJECT TO ALTERATIONS
09.04.2014
Page:
Index
1 Functionality 2
1.1 Operation and control 2
1.2 Environment 2
1.3 Functional Requirement 3
2 External Connections 4
2.1 Operating voltage 4
2.2 Inputs 4
2.3 Outputs 5
2.4 Circuit times 5
2.5 Pin assignment 6
2.5.1 In- and Output Allocation 6
2.5.2 Simplified Diagram of the control 7
3 Timing diagrams 8
3.1 OFF – ON / ON – OFF / ON – ON / OFF - OFF 8
3.2 Power up if contacts are open resp. closed 9
3.3 ON – Trip / Trip – OFF / Trip – ON / Power up - Trip 10
ABB Switzerland Ltd.
Fulachstrasse 15 0 CH-82 01 Schaffhausen Phone: +41 58 586 41 11 Fax: +41 58 586 42 22 E-mail: administration@ch.abb.com / www.abb.com
S800-RSU Technial Manual Page 2 / 10

1 Functionality

1.1 Operation and control

The intention is the fast, secure and energy-awa re moving of the lever of S800 High Performance MC B. Th e controller interprets the two command inputs ON and OFF. The controller does a switching command when a positive edge at one of the two command inputs is detected and the signal is for at least 10ms stable. Once the home position is reached after switching operation, the corresponding feedback signal is activated. Once the home position is reached and the feedback signal is turned on, a new control command can be initiated. When the S800 triggers due to overload, short circuit or manual activation, this is registered and issued by activating the "TRIP". A "ON" or "OFF" switching command can be triggered directly from the "TRIP" position. When detection a trip movement the motor moves into OFF-position to secure the contact opening and to prevent a subsequent manually switching of the S800 via lever. Under normal operation, it is always only one output active. If the motor is in motion, no output is active. The motor switches powerless after executing the control c ommand. Thus a twist of the spindle to snap the external safety lock or manual actuation by screwdriver is possible. If the spindle is moved by more than one rotation from the current positi on, all o utputs are turned on. If the spindle o nly slightly rotated manually (> 7.5°) for 10 seconds no commands will be accepted. The initialization takes place when a switching command is detected only. The switching command is executed after initialization. Until the beginning of the initializati on, all ou tputs are active.

1.2 Environment

Operating Voltage +24 VDC +10 % / -15 % Cur rent C onsumption 2,5 A
ABB recommends: ABB switching power supply CP-S 24/5.0 (The power supply needs at least a nominal current rating of 5A. Furthermore it must be able to cover short spikes above the rated current rating without decreasing the input voltage under 20V DC)
Load Peaks 8A for 0.1ms at power up
3.5A for 250ms during operation Standby Current < 50 mA Ambient operation temperature Coldness Dry heat Dam p heat Relative humidi ty < 85 % at 45 °C (No bedewing) Dimensions Depth Height Unit width Contact trip indicator Yes (ON – TRIP – OFF) Trip position of actuating lever Yes Mechanical Fixing Field mountable and wireable on High Performance MCBs S802…,
Up to -25 °C according to IEC 60068-2-1:2007 Up to +70 °C according to IEC 60068-2-2:2007 Up to +55°C by 95% rel. hum. acc. to IEC 60068-2-30:2005
134,2 mm (5,28 in) 100,6 mm (3,96 in) 54 mm (2,13 in)
S803…, S804 via Allen head screw size 3 and mounting bracket. Required tightening torque 3 Nm
S800-RSU Technial Manual Page 3 / 10
Maximum Cable length Power supply: up to 10m with 0.5 mm2(32 feet 9.7 in with AWG20)
Control supply: up to 10m with 0.5 mm2(32 feet 9.7 in with
AWG20) Guidelines RoHS Reference standards IEC 60947-2 Annex N
- IEC 61000-4-2
- IEC 61000-4-3
- IEC 61000-4-4
- IEC 61000-4-5
- IEC 61000-4-6
- IEC 61000-4-11
IEC / CISPR 22
EN 61000-6-2
- IEC 61000-4-8
EN 61000-6-4
- IEC / CISPR 16-2-3
- IEC / CISPR 22
EN 61000-4-16 (from 20kHz)
UL489 sections 14, 16
60068-2-1
60068-2-2
60068-2-30

1.3 Functional R equire ment

Maintenance: Maintenance free during lifetime Maximum number of switching cycles: 10.000 mechanical switching operations if mounted on S800 High
Performance MCB
Manual switch OFF: If manual use is detected (> 7.5°), inputs will be deactivated for 10
seconds. Outputs re main unchanged. If spindle is being turned
more than once, all outputs become active until next command is
accepted. Intuitive manual switch-off via lever is possible.
Manual switch ON: If manual use is detected (> 7.5°), inputs will be deactivated for 10
seconds. Outputs re main unchanged. If spindle is being turned
more than once, all outputs become active until next command is
accepted. Intuitive manual switch-on via lever is not possible.
Mechanical lock:
Referencing by startup
Mechanical fixation by secured lock slider blocking the actuation
spindle independent of its position
By startup the S800-RSU-H / S800W-RSU refers unique
Referencing after voltage interruption
When operating voltage is restored a unique referencing take
place. Regardless of the switching position of the High
Performance MCB S800 the referencing held in the OFF position.