Application
Use Part No. 560N to electrically connect 2 (two)
through (run) wires and insulate the connection.
Wire Range
18-14 AWG solid or Stranded, tinned or untinned
(.75-1.5 mm
2
) copper conductors. For use with
common thermoplastic insulated wires such as: T, TF,
TFF, TFN, TFFN,AWM, TEW, SAE-GPT with a
maximum insulation diameter of .145 inches (3.5 mm).
Maximum recommended current for general purpose
applications: 18 AWG - 7 AMPS, 16 AWG - 10 AMPS,
14 AWG - 15 AMPS.
Construction
U-contact - Tin plated brass, .03 in. (.8 mm) thick
Insulator - Flame retardant polypropylene
Color - brown
Weight
.0032 lb. (1.45 gm)
Recommended Installation Tools
3M™Crimping Tool No. E-9BM
9” Linemans Pliers
Installation Instructions
1. Open connector to allow run wire insertion.
2. Insert unstripped run wires from side and close
connector firmly.
3. Hold tool perpendicular to the wires and make the
connection by driving the u-contact down flush with
the top of the plastic insulator.
4. Close hinged top cover until latched.
Regulatory Agencies
UL Listed - Tested per UL Standard 486C
UL file No. E23438
CSA certified - CSA Std. C22.2 No.188-MI983
CSA File No. LR15503
(Voltage rated at 600 volts maximum, building wire:
1000 volts maximum, signs, fixtures and luminaires.
Operating Temperature: 105˚C, 221˚F maximum)
Note: UL Listed and CSA Certified for AWG only.
Scotchlok
™
560N
Self-Stripping Electrical
Double Run Connectors
Data Sheet
WARNING
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electrical codes.