3M 557 User Manual

Data Sheet
1
SCOTCHLOK557
IDC Electrical Tap Connector
Application:
Use part No. 557 to electrically connect two wire ends and insulate the connection.
Wire Range:
2
solid or
stranded and 1,5mm
2
solid )tinned or untinned copper con­ductors. For use with common thermoplastic insulated wires such as: T, TF, TFF, TFN, TFFN, AWN, TEW, SAE–GPT, with a maximum insulation diameter of .120 inches ( 3,0 mm ).
Maximum recommended current for general purpose applications: 22 AWG – 3 Amps, 20 AWG – 4 Amps, 18 AWG – 7 Amps, 16 AWG – 10 Amps
Construction:
U–Contact Tin plated brass, .02 inches thick ( 0,5 mm ) Insulator Flame retardant polypropylene,
color, Red.
Weight:
.0030 lbs. ( 1,37 gm )
Engineering Specification:
The connector shall be UL Listed and CSA Certified as a pressure cable connector for 600 volts maximum, building
wire; 1000 volts maximum, signs, fixtures and luminaries. The insulation shall be rated for 105°C. The connector shall also meet the intent of the Standard for Portable Electric Lamps, UL 153, specifically Paragraph 14.2, when housed within the body of the lamp.
Regulatory Agencies:
UL File No. E23438 Tested per UL Standard 486C CSA File No. LR15503, LR32411 Tested per CSA Standard C22.2 No. 188–M1983 ( Voltage rated at 600 volts maximum, building wire; 1000 volts maximum, sings, fixtures, and luminaires. T emperature rated 105°C. ) Federal Specification W – S – 610 * Commercial Packaging Only * Type Class Kind Style II I cu F
Installation Instruction:
Caution: – Turn power off before installing connectors.
All electrical work should be done according to appropriate electrical codes.
1. Insert unstripped wire completely and check their posi­tion in the inspection ports.
2. Hold tool perpendicular to the wire and make the con­nection by driving the u–connection down flush with the top of the insulator.
3. Close hinged top cover until latched.
IMPORTANT NOTICE:
All statements, technical information and recommendations related to the Seller’s products are based on information believed to be reliable, but the accuracy or completeness thereof is is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its intended use. The user assumes all risks and liability whatsoever in connection with such use.
All statements or recommendations of the seller which are not contained in the Seller’s current publications shall have no force or effect unless contained in an agreement signed by an authorized officer of the Seller. The statements contained herein are made in lieu of all warranties express or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are hereby expressly disclaimed.
SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT LIMITED TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECT OR CONSEQUENTIAL DAMAGES SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THE SELLER’S PRODUCTS.
3M Electrical Products Division
6801 River Place Blvd. Austin, Texas 78726–4599
1991 3M
7 / 26 / 91
314
22–14
314
22–14
557
22–16
558
22–16
560
18–14
560B 18–14
560N 18–14
562
12–10
564
18–14
905N 18–14run 22–18Tap
567 12–10run 18–14tap
905 18–14run 22–18Tap
951
22–18
952
18–14
953
12
UR 19–26 Solid
UB 22–26 Solid
Part # Wire Range
Type of Connector
Listed Certified
Part # Wire Range
Type of Connector
Listed Certified
NOTE: For complete wire combinations or other technical information see individual data sheets or contact Technical Service.