Application
Use Part No. 314 to electrically connect two or three
wire ends, insulate the connection, and provide a
moisture resistant seal.
Wire Range
22-14 AWG Solid or stranded, tinned or untinned
(0,5-1.5 mm
2
) copper conductors. For use with
common thermoplastic insulated wires: T, TF, TFF,
TFN, TFFN, AWM, TEW, SAE-GPT with a maximum
insulation diameter of .150 inches (3,8 mm). Maximum
recommended current for general purpose applications:
22 AWG - 3 AMPS, 20 AWG - 5 AMPS, 18 AWG 7 AMPS, 16 AWG - 10 AMPS, 14 AWG - 15 AMPS.
Construction
U-contact - Tin plated brass, .02 in. (0,5 mm) thick
Insulator - Flame retardant nylon,
Color - cap/dk. blue, body/white
Sealant - Mineral Oil Base EG-3 Grease
Weight
.0077 lb. (3,49 gm)
Recommended Installation Tools
3M™Crimping Tool No. E-9BM
Mechanics (slip joint) Pliers
Installation Instructions
1. Insert 2 or 3 unstripped wires completely into
connector and check their position by looking
through the translucent connector body.
2. Hold tool perpendicular to the wires and make the
connection by driving the cap down flush with the
top edge of the connector body.
Regulatory Agencies
UL Listed - Tested per UL Standard 486C
UL file No. E23438
CSA certified - CSA Std. C22.2 No. 0. 188-MI983
CSA File No. LR15503
(Voltage rated at 600 volts maximum, building wire:
1000 volts maximum, signs, fixtures and luminaires.
Operating Temperature: 105˚C.)
Note: UL Listed and CSA Certified for AWG only.
Connector is not recommended for direct underground
burial or other submerged applications.
Scotchlok
™
314
Self-Stripping Moisture Resistant,
Electrical Pigtail Connectors
Data Sheet
WARNING
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electrical codes.