pressure, a low pressure, on loss of loop
or off. The display will read either “LO”,
“HI”, LOOP or OFF; use the ▲ or ▼ arrow
key to make a selection and press ENTER.
If set for “HI”, the switch will change states
on increasing pressure at the setpoint
value. If set for “LO”, the switch will
change states on decreasing pressure at
the setpoint value. If set for “LOOP”, the
switch will change states on the loss of the
4-20 mA loop voltage/current. If set for
“OFF” the switch will be set to off or open
and will not change states. When set to
off, no further setpoint configurations will
be displayed; the display will show
“SAVE/donE” and return to the normal display screen.
SETPOINT INDICATION - When the setpoint indication is set to “On” and a setpoint is tripped, the display reading will
alternate between the pressure reading
and a setpoint label. The setpoint labels
are LO.1, LO.2, HI.1, HI.2, LP.1, and LP.2.
If the setpoint indication is set to “OFF”
and a setpoint is tripped, the display will
continuously read the input pressure.
Each setpoint can be individually configured to either show an indication or not.
Use the ▲ or ▼ arrow key to select “On”
or “OFF” and press ENTER to save.
NORMALLY OPEN OR NORMALLY
CLOSED - Each switch can be set to normally open “nO” or normally closed “nC”
for the normal or safe state. For example,
if set for normally open and a high setpoint, the switch will be open below the
pressure setpoint and close upon increasing pressure at the setpoint value. Use the
▲ or ▼ arrow key to select normally open
“nO” or normally closed “nC” and press
ENTER to save.
ADJUSTING SETPOINTS - With the set-
point value displayed, press the ▲ or ▼
arrow key to increase or decrease the
value until the desired trip point for that
switch is reached. Press ENTER to accept
the new value. The new setpoint value will
be saved to nonvolatile memory at the end
of the setpoint menu when the ENTER key
is pressed and the display shows
“SAVE/donE”. Pressing SETUP while in
this menu will cause the display to return
to the normal screen with no changes taking effect.
NOTE: When adjusting the setpoints, the
previous setpoint values are monitored,
and the new value is monitored only at the
end of the setpoint menu when the ENTER
key is pressed and the display reads
SAVE/donE. If no key is pressed for 15
seconds, the display will return to the normal mode and the configuration will revert
back to the previous parameters.
HYSTERESIS - Hysteresis sometimes is
referred to as a deadband value. It is the
numeric value above the low setpoint
value that the switch will clear, and below
the high setpoint value that the switch will
clear. The hysteresis value is displayed in
absolute pressure units that the gauge is
configured for. For example, if a 90 psi
high setpoint with a 10 psi hysteresis is
desired (80 psi release point), set the
"HySt" reset value at 10 psi. The hysteresis can be individually set for each switch.
Press ENTER and the display will show
"HySt" for one second and then display the
previously set hysteresis value. Use the
▲ or ▼ arrow key to increase or decrease
the hysteresis value and then press
ENTER to save the new value. The hysteresis value range for a low setpoint is
from the setpoint value up to 110% of full
scale, and for a high setpoint, from the setpoint value to absolute zero pressure units.
NOTE: If the hysteresis value is set so
that it cannot be cleared easily by gauge
pressure change, the setpoint can be
cleared manually by going to the setpoint
menu and turning the setpoint off. Make
sure the gauge pressure is below the high
setpoint or above the low setpoint and go
back into the setpoint menu and turn the
setpoint on again. Setting a large hysteresis value will in effect act like latching outputs.
KT-077
8/04
Page 7 of 20