York YCAL0014SC, YCAL0080SC User Manual

0 (0)

MILLENNIUM ®

AIR-COOLED LIQUID CHILLERS

HERMETIC SCROLL

INSTALLATION, OPERATION, MAINT. Supersedes: 150.62-NM1 (899)

Form 150.62-NM1 (700)

YCAL0014SC - YCAL0080SC

29224(R)A

200-3-60

230-3-60

380-3-60

460-3-60

575-3-60 MODELS ONLY

Standard, Glycol & Metric Models, Combined

IMPORTANT!

READ BEFORE PROCEEDING!

GENERAL SAFETY GUIDELINES

This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if mis-used or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site.

This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual possesses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.

SAFETY SYMBOLS

The following symbols are used in this document to alert the reader to areas of potential hazard:

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

2

YORK INTERNATIONAL

FORM 150.62-NM1

CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually an instruction will be given, together with a brief explanation.

NOTE is used to highlight additional information which may be helpful to you.

CHANGEABILITY OF THIS DOCUMENT

In complying with YORK’s policy for continuous product improvement, the information contained in this document is subject to change without notice. While YORK makes no commitment to update or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest YORK Engineered Systems Service office.

It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in question. If there is any question in the mind of operating/service personnel as to the applicability of these documents, then prior to working on the equipment, they should verify with the owner whether the equipment has been modified and if current literature is available.

YORK INTERNATIONAL

3

TABLE OF CONTENTS AND TABLES

 

 

 

 

 

PAGE

PRODUCT IDENTIFICATION NUMBER ..........................................................

7

REFRIGERANT FLOW DIAGRAM ...................................................................

9

 

 

 

 

 

SECTION

1

 

INSTALLATION ..........................................................................

10

ELECTRICAL DATA .......................................................................................

20

OPERATIONAL LIMITATIONS .......................................................................

30

PHYSICAL DATA ............................................................................................

34

DIMENSIONS & CLEARANCES ....................................................................

38

PRE-STARTUP CHECKLIST .........................................................................

54

INITIAL STARTUP ..........................................................................................

55

UNIT OPERATING SEQUENCE ....................................................................

57

 

 

 

 

 

SECTION

2

 

UNIT CONTROLS ......................................................................

58

STATUS KEY..................................................................................................

60

DISPLAY/PRINT KEYS ..................................................................................

66

ENTRY KEYS .................................................................................................

73

SETPOINTS KEY ...........................................................................................

74

UNIT KEYS

....................................................................................................

81

UNIT OPERATION .........................................................................................

85

 

 

 

 

 

SECTION

3

 

SERVICE AND TROUBLESHOOTING ......................................

95

OPTIONAL PRINTER INSTALLATION .........................................................

104

TROUBLESHOOTING CHARTS ..................................................................

105

MAINTENANCE ...........................................................................................

108

ISN CONTROL .............................................................................................

109

 

 

 

 

 

SECTION

4

 

WIRING DIAGRAMS ...............................................................

112

 

 

 

 

 

 

SECTION

5

 

APPENDIX 1 – ISOLATORS ....................................................

128

YORK APPLIED SYSTEMS FIELD OFFICE LISTING .................................

134

TABLES

 

 

 

 

1

MICROPANEL POWER SUPPLY ............................................................

20

2

STANDARD SINGLE POINT POWER .....................................................

21

3

STANDARD DUAL POINT POWER ................................................

22 – 23

4

OPTIONAL SINGLE POINT POWER ..............................................

24 – 25

5

OPTIONAL SINGLE POINT POWER ..............................................

26 – 27

6

OPTIONAL SINGLE POINT POWER ..............................................

28 – 29

7

TEMPERATURES AND FLOWS (ENGLISH) ..........................................

30

8

VOLTAGE LIMITATIONS (ENGLISH) .......................................................

30

9

COOLER PRESSURE DROPS (ENGLISH) .............................................

31

10

ETHYLENE GLYCOL CORRECTION FACTORS ....................................

31

11

TEMPERATURES AND FLOWS (METRIC) ............................................

32

12

VOLTAGE LIMITATIONS (METRIC) ........................................................

32

4

YORK INTERNATIONAL

FORM 150.62-NM1

 

TABLES AND FIGURES

 

 

 

PAGE

TABLES

 

13

COOLER PRESSURE DROPS (METRIC).............................................

33

14

ETHYLENE GLYCOL CORRECTION FACTORS ..................................

33

15

PHYSICAL DATA (ENGLISH) ........................................................

34 – 35

16

PHYSICAL DATA (METRIC) ..........................................................

36 – 37

17

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (ENGLISH) .............

39

18

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (ENGLISH) .............

41

19

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (ENGLISH) .............

43

20

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (ENGLISH) .............

45

21

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (METRIC) ...............

47

22

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (METRIC) ...............

49

23

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (METRIC) ...............

51

24

WEIGHT DISTRIBUTION/CENTER OF GRAVITY (METRIC) ...............

53

25

SETPOINT ENTRY LIST .......................................................................

54

26

STATUS KEY MESSAGES ....................................................................

65

27

OPERATOR DATA QUICK REFERENCE ..............................................

69

28

COOLING SETPOINTS PROGRAMMABLE LIMITS & DEFAULTS

....... 76

29

PROGRAM KEY LIMITS & DEFAULTS .................................................

79

30

SETPOINTS KEY QUICK REFERENCE ...............................................

80

31

UNIT KEYS QUICK REFERENCE .........................................................

84

32

LEAVING CHILLED LIQUID CONTROL – 6 COMPRESSORS .............

86

33

LEAVING CHILLED LIQUID CONTROL – 4 COMPRESSORS .............

86

34

LEAVING CHILLED LIQUID CONTROL – 3 COMPRESSORS .............

87

35

LEAVING CHILLED LIQUID CONTROL – 2 COMPRESSORS .............

87

36

COMPRESSOR STAGING FOR RETURN WATER CONTROL ............

89

37

RETURN CHILLED LIQUID CONTROL – 6 COMPRESSORS ..............

89

38

RETURN CHILLED LIQUID CONTROL – 4 COMPRESSORS ..............

89

39

CONDENSER FAN CONTROL USING OUTDOOR AMBIENT

 

 

TEMPERATURE AND DISCHARGE .....................................................

90

40

CONDENSER FAN CONTROL USING DISCHARGE ONLY .................

90

41

LOW AMBIENT CONDENSER FAN CONTROL – AMBIENT

 

 

TEMPERATURE AND DISCHARGE PRESSURE CONTROL .............

91

42

LOW AMBIENT CONDENSER FAN CONTROL – DISCHARGE

 

 

PRESSURE CONTROL .......................................................................

91

43

COMPRESSOR OPERATION – LOAD LIMITING .................................

92

44

MICROBOARD BINARY INPUTS ..........................................................

97

45

MICROBOARD ANALOG INPUTS ........................................................

97

46

MICROBOARD OUTPUTS ....................................................................

97

47

OUTDOOR AIR SENSOR VALUES .......................................................

99

YORK INTERNATIONAL

5

 

TABLES/FIGURES

 

 

 

PAGE

TABLES

 

48

ENTERING & LEAVING CHILLED LIQUID TEMPERATURE

 

 

SENSOR VALUES ............................................................................

100

49

KEYPAD PIN ASSIGNMENT MATRIX .................................................

103

50

TROUBLESHOOTING CHARTS ...............................................

105 – 107

51

ISN RECEIVED DATA ..........................................................................

109

52

ISN TRANSMITTED DATA ..................................................................

109

53

ISN TRANSMITTED DATA ..................................................................

110

54

ISN OPERATIONAL & FAULT CODES .................................................

111

FIGURES

 

1

REFRIGERANT FLOW DIAGRAM ..........................................................

9

2

STANDARD POWER SUPPLY WIRING ................................................

14

3

OPTIONAL SINGLE POINT POWER SUPPLY WIRING .......................

15

4

OPTIONAL SINGLE POINT POWER SUPPLY WIRING –

 

 

N-F DISC SW OR CIRC BKR .............................................................

16

5

CONTROL WIRING ..............................................................................

17

6

LEAVING WATER TEMPERATURE CONTROL –

 

 

COMPRESSOR STAGING ..................................................................

86

7

FIELD & FACTORY ELECTRICAL CONNECTIONS –

 

 

REMOTE TEMPERATURE RESET BOARD .......................................

94

8

MICROBOARD LAYOUT .......................................................................

98

9

MICROBOARD RELAY CONTACTS ARCHITECTURE .......................

103

10

PRINTER TO MICROBOARD ELECTRICAL CONNECTIONS ...........

104

11

ELEMENTARY DIAGRAM ...................................................................

112

12

ELEMENTARY DIAGRAM – POWER CIRCUIT ..................................

114

13

ELEMENTARY DIAGRAM ...................................................................

116

14

ELEMENTARY DIAGRAM – POWER CIRCUIT ..................................

118

15

ELEMENTARY DIAGRAM ...................................................................

120

16

ELEMENTARY DIAGRAM – POWER CIRCUIT ..................................

122

17

ELEMENTARY DIAGRAM ...................................................................

124

18

ELEMENTARY DIAGRAM – POWER CIRCUIT ..................................

126

19

TYPE CP 1 ...........................................................................................

130

20

TYPE CP 2 ...........................................................................................

130

21

R SPRING SEISMIC ISOLATOR .........................................................

131

22

TYPE CP MOUNTING .........................................................................

132

23

“AEQM” SPRING-FLEX MOUNTING ...................................................

133

6

YORK INTERNATIONAL

FORM 150.62-NM1

PRODUCT IDENTIFICATION NUMBER (PIN)

EXAMPLES:

1

2

3

4

5

6

7

8

9

10

11

12

13 14

15

Y C A S 1

3

8

5

E A 5

0

Y

F A

Y C A L

0

0

8

0

S C 4

6

X

A A

BASIC MODEL NUMBER

YCAL0080SC46xAA

1

 

2

 

3

 

4

 

5

6

7

8

 

9

 

10

 

11

12

13

14

15

 

BASE PRODUCT TYPE

NOMINAL CAPACITY

UNIT DESIGNATOR

REFRIGERANT

VOLTAGE/STARTER

DESIGN/DEVELOPMENT LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

: YORK

 

0

 

 

#

 

#

 

#

 

S

: Standard Unit

 

C

: R-22

 

 

1

 

7

 

 

: 200 / 3/ 60

 

A

 

 

 

 

: Design Series A

 

 

 

 

C

 

 

 

 

 

: Chiller

1

#

#

#

 

 

 

 

 

 

 

 

 

2

8

 

 

: 230 / 3 / 60

 

 

 

 

 

A : Engineering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

: Air-Cooled

 

 

 

Even Number: 60 HZ Nominal Tons

 

 

 

 

 

4

0

 

 

: 380 / 3 / 60

 

 

 

 

 

 

 

Change

 

 

 

 

 

 

 

U

 

 

: Condensing

 

 

 

Odd Number: 50 HZ Nominal kW

 

 

 

 

 

4

6

 

 

: 460 / 3 / 60

 

 

 

 

 

 

 

or PIN Level

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

0

 

 

: 380-415 / 3 /

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

: Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

8

 

 

 

 

: 575 / 3 / 60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X : Across the Line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YORK INTERNATIONAL

7

8

INTERNATIONAL YORK

OPTIONS MODEL NUMBER

16 17 18 19

 

20 21 22 23 24 25 26 27 28

 

29 30 31 32 33 34 35 36 37

 

 

 

POWER

FIELD

 

CONTROLS FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR / PIPING FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: SP Supply TB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Low Ambient Kit (factory)

# #

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

 

 

 

: MP Supply TB

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: High Ambient Kit (factory)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:Leaving Supply Temp.

 

 

S

X

 

 

 

: SP Supply TB

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Both Low / High Ambient (factory)

 

 

 

 

C

 

 

 

 

 

 

:Chicago Relief Code

 

 

S

D

 

 

 

: SP NF Disconnect Switch

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: BAS/EMS Temp. Reset / Offset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

X

 

 

 

: SP Circuit Breaker w/ Lockable Handle

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Spanish LCD & Keypad Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: French LCD & Keypad Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Control Transformer (factory)

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: German LCD & Keypad Display

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

:Hot Gas By-Pass

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Discharge Pressure Transducers/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(# circuits)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C : Power Factor Capacitor

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Readout Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

:Compressor External

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Suction Pressure Transducers /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MP = Multiple Point

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Readout Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Both Discharge & Suction Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP = Single Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transducers / Readout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NF = Non-Fused

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: N. American Safety Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB = Terminal Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

(cU.L./cE.T.L.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ser. = Service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

: No Listing (typically 50 HZ non-C.E.,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ind. Sys. Brkr. & L. Ext. Handles = Individual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

non-U.L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

Breaker & Lockable External

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

: Remote Control Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Handle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S : Sequence Control & Automatic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lead Transfer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

39

40

41

42

43

44

45 46

47

 

48

49

50

51

52

53

54

 

EVAP. FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER FIELD

 

CABINET FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: 300 PSIG DWP Waterside

 

X

 

 

 

 

: Aluminum

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Wire Condenser Headers Only (factory)

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Double Thick Insulation

 

C

 

 

 

: Copper

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Wire (Full Unit) Enc. Panels (factory)

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

: Weld Flange Kit

 

B

 

 

 

: Black Fin

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Wire (Full Unit) Enc. Panels (field)

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

: Victaulic Flange Kit

 

P

 

 

 

 

: Phenolic

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Wire/Louvered Enc. Panels (factory)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Flow Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Wire/Louvered Enc. Panels (field)

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X : TEAO Fan

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

: ASME Pressure Vessel &

 

 

 

 

 

 

 

 

 

Motors

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Louvered (Cond. Only) Enc. Panels (factory)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Associated Codes

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Louvered (Cond. Only) Enc. Panels (field)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

: Remote DX Cooler

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Louvered (Full Unit) Enc. Panels (factory)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Louvered (Full Unit) Enc. Panels (field)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Acoustic Sound Blanket

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Low Sound Fans

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 : 1" Deflection

S : Seismic

N : Neoprene Pads

55

EXTENDED FIELD

X : 1st Year Parts Only

B: 1st Year Parts & Labor

C: 2nd Year Parts Only

D: 2nd Year Parts & Labor

E : 5

Year Compressor Parts Only

NOTES:

 

F : 5

Year Compressor Parts & Labor Only

1. Q

:DENOTES SPECIAL / S.Q.

G : 5

Year Units Parts Only

2.

#

:DENOTES STANDARD

H : 5

Year Unit Parts & Labor

3. X

:w/in OPTIONS FIELD, DENOTES NO OPTION SELECTED

 

 

4.

Agency Files (i.e. U.L. / E.T.L.; C.E.; ARI; ETC.) will contain info. based on the first 14 characters only.

C T D S

X X X X

 

EXAMPLES:

 

 

19 18 17 16

 

 

 

 

 

 

A

X

 

 

 

 

20

 

 

T

X

 

 

 

 

21

 

 

S

X

 

 

 

 

22

 

 

R

X

 

 

 

 

23

 

 

D 3 X X X X 1 X C 5 2 S R P X L

X X X X X X X X X X X X X X X L

 

 

IDENTIFICATION PRODUCT

 

39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 X X B X R A S W

X X X X X X A X X

 

 

(PIN) NUMBER

 

48 47 46 45 44 43 42 41 40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

X

 

 

 

 

49

 

 

X

X

 

 

 

 

50

 

 

X

X

 

 

 

 

51

 

 

L

X

 

 

 

 

52

 

 

X

X

 

 

 

 

53

 

 

S

X

 

 

 

 

54

 

 

D

X

 

 

 

 

55

 

 

 

 

 

 

 

 

FORM 150.62-NM1

REFRIGERANT FLOW DIAGRAM

AIR COOLED CONDENSERS

 

 

YCAL REFRIGERANT FLOW DIAGRAM

 

(INCLUDING TEMPERATURE SENSORS & PRESSURE TRANSDUCERS)

 

 

NOTE: YCAL0040-0080 HAVE TWO REFRIGERANT

 

 

SYSTEMS AND ONE DX COOLER.

 

 

* HOT GAS OPTION - SYSTEM 1 ONLY

 

 

 

SIGHT GLASS /

 

LIQUID LINE FILTER / DRIER

MOISTURE INDICATOR

 

 

LIQUID LINE

 

 

 

SERVICE VALVE

 

 

LIQUID LINE

 

 

SOLENOID VALVE

HOT DISCHARGE

 

 

 

GAS LINE

 

 

 

DISCHARGE LINE

 

* SOLENOID OPERATED

BALL VALVE

 

 

 

HOT GAS BY PASS VALVE

OPTIONAL DISCHARGE

 

 

TXV

PRESSURE TRANSDUCER

 

 

 

SERVICE VALVE

 

 

EQUALIZER

SUCTION LINE

 

LINE

 

 

 

HIGH PRESSURE

BALL VALVE

 

 

 

 

 

CUTOUT SWITCH

 

RELIEF VALVE

 

 

 

 

 

 

300 PSIG

 

 

 

(20.68 BARG)

 

SERVICE

 

 

 

VALVE

 

DX COOLER

 

 

 

 

LOW PRESSURE SWITCH OR

 

 

RETURN WATER

SUCTION PRESSURE TRANSDUCER

 

 

 

 

TEMP. SENSOR

 

 

 

 

 

LEAVING

ENTERING CHILLED WATER

 

 

CHILLED WATER

 

 

LEAVING CHILLED WATER

TEMP. SENSOR

 

OIL EQUALIZING

 

 

 

LINE

 

 

 

2 OR 3 COMPRESSORS PER SYSTEM

LD03844

FIG. 1 – REFRIGERANT FLOW DIAGRAM

YORK INTERNATIONAL

9

Installation

INSTALLATION

To ensure warranty coverage, this equipment must be commissioned and serviced by an authorized YORK service mechanic or a qualified service person experienced in chiller installation. Installation must comply with all applicable codes, particularly in regard to electrical wiring and other safety elements such as relief valves, HP cut-out settings, design working pressures, and ventilation requirements consistent with the amount and type of refrigerant charge.

Lethal voltages exist within the control panels. Before servicing, open and tag all disconnect switches.

INSTALLATION CHECK LIST

The following items, 1 thru 5, must be checked before placing the units in operation.

1.Inspect the unit for shipping damage.

2.Rig unit using spreader bars.

3.Open the unit only to install water piping system. Do not remove protective covers from water connections until piping is ready for attachment. Check water piping to insure cleanliness.

4.Pipe unit using good piping practice (see ASHRAE handbook section 215 and 195.

5.Check to see that the unit is installed and operated within limitations (Refer to LIMITATIONS).

The following pages outline detailed procedures to be followed to install and start-up the chiller.

HANDLING

These units are shipped as completely assembled units containing full operating charge, and care should be taken to avoid damage due to rough handling.

The unit should be lifted by inserting hooks through the holes provided in unit base rails. Spreader bars should be used to avoid crushing the unit frame rails with the lifting chains. See below.

29224(RIG)A

INSPECTION

Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage is evident, it should be noted in the carrier’s freight bill. A written request for inspection by the carrier’s agent should be made at once. See “Instruction” manual, Form 50.15-NM for more information and details.

LOCATION AND CLEARANCES

These units are designed for outdoor installations on ground level, rooftop, or beside a building. Location should be selected for minimum sun exposure and to insure adequate supply of fresh air for the condenser. The units must be installed with sufficient clearances for air entrance to the condenser coil, for air discharge away from the condenser, and for servicing access.

In installations where winter operation is intended and snow accumulations are expected, additional height must be provided to insure normal condenser air flow.

Clearances are listed under “Notes” in the “DIMENSIONS” section.

10

YORK INTERNATIONAL

FOUNDATION

The unit should be mounted on a flat and level foundation, floor, or rooftop capable of supporting the entire operating weight of the equipment. See PHYSICAL DATA for operating weight. If the unit is elevated beyond the normal reach of service personnel, a suitable catwalk must be capable of supporting service personnel, their equipment, and the compressors.

GROUND LEVEL LOCATIONS

It is important that the units be installed on a substantial base that will not settle. A one piece concrete slab with footers extended below the frost line is highly recommended. Additionally, the slab should not be tied to the main building foundations as noise and vibration may be transmitted. Mounting holes are provided in the steel channel for bolting the unit to its foundation. (See DIMENSIONS.)

For ground level installations, precautions should be taken to protect the unit from tampering by or injury to unauthorized persons. Screws and/or latches on access panels will prevent casual tampering. However, further safety precautions such as a fenced-in enclosure or locking devices on the panels may be advisable.

ROOFTOP LOCATIONS

Choose a spot with adequate structural strength to safely support the entire weight of the unit and service personnel. Care must be taken not to damage the roof.

Consult the building contractor or architect if the roof is bonded. Roof installations should have wooden beams (treated to reduce deterioration), cork, rubber, or vibration isolators under the base to minimize vibration.

NOISE SENSITIVE LOCATIONS

Efforts should be made to assure that the chiller is not located next to occupied spaces or noise sensitive areas where chiller noise level would be a problem. Chiller noise is a result of compressor and fan operation. Considerations should be made utilizing noise levels published in the YORK Engineering Guide for the specific chiller model. Sound blankets for the compressors and low sound fans are available.

FORM 150.62-NM1

SPRING ISOLATORS (OPTIONAL)

When ordered, four (4) isolators will be furnished.

Identify the isolator, and locate at the proper mounting

point, and adjust per instructions. See Appendix 1.

1

COMPRESSOR MOUNTING

The compressors are mounted on four (4) rubber isolators. The mounting bolts should not be loosened or adjusted at installation of the chiller.

REMOTE COOLER OPTION

For units using remote cooler option, refer to instructions included with miscellaneous cooler parts kit.

The unit is shipped with a 6 lb. (2.7 kg) holding charge. The remainder of the charge must be weighed-in according to the operating charge listed under Physical Data. Additional charge must also be added for the refrigerant lines.

CHILLED WATER PIPING

General – When the unit has been located in its final position, the unit water piping may be connected. Normal installation precautions should be observed in order to receive maximum operating efficiencies. Piping should be kept free of all foreign matter. All chilled water evaporator piping must comply in all respects with local plumbing codes and ordinances.

Since elbows, tees and valves decrease pump capacity, all piping should be kept as straight and as simple as possible possible. All piping must be supported independent of the chiller.

Consideration should be given to compressor access when laying out water piping. Routing the water piping too close to the unit could make compressor servicing/replacement difficult.

YORK INTERNATIONAL

11

Installation

Hand stop valves should be installed in all lines to facilitate servicing.

Piping to the inlet and outlet connections of the chiller should include high-pressure rubber hose or piping loops to insure against transmission of water pump vibration. The necessary components must be obtained in the field.

Drain connections should be provided at all low points to permit complete drainage of the cooler and system water piping.

A small valve or valves should be installed at the highest point or points in the chilled water piping to allow any trapped air to be purged. Vent and drain connections should be extended beyond the insulation to make them accessible.

The piping to and from the cooler must be designed to suit the individual installation. It is important that the following considerations be observed:

1.The chilled liquid piping system should be laid out so that the circulating pump discharges directly into the cooler. The suction for this pump should be taken from the piping system return line and not the cooler. This piping scheme is recommended, but is not mandatory.

2.The inlet and outlet cooler connection sizes are 3" (YCAL0014 - 0030), 4" (YCAL0034 - 0060), or 6" (YCAL0064 - 0080).

3.A strainer, preferably 40 mesh, must be installed in the cooler inlet line just ahead of the cooler. This is important to protect the cooler from entrance of large particles which could cause damage to the evaporator.

4.All chilled liquid piping should be thoroughly flushed to free it from foreign material before the system is placed into operation. Use care not to flush any foreign material into or through the cooler.

5.As an aid to servicing, thermometers and pressure gauges should be installed in the inlet and outlet wa-

ter lines.

6.The chilled water lines that are exposed to outdoor ambients should be wrapped with supplemental heater cable and insulated to protect against freezeup during low ambient periods, and to prevent formation of condensation on lines in warm humid locations.

7.A chilled water flow switch, (either by YORK or others) MUST be installed in the leaving water piping of the cooler. There should be a straight horizontal run of at least 5 diameters on each side of the switch. Adjust the flow switch paddle to the size of the pipe in which it is to be installed. (See manufacturer’s instructions furnished with the switch.) The switch is to be wired to terminals 13 – 14 of CTB1 located in the control panel, as shown on the unit wiring diagram.

The Flow Switch MUST NOT be used to start and stop the chiller (i.e. starting and stopping the chilled water pump). It is intended only as a safety switch.

WIRING

Liquid Chillers are shipped with all factory mounted controls wired for operation.

Field Wiring – Power wiring must be provided through a fused disconnect switch to the unit terminals (or optional molded disconnect switch) in accordance with N.E.C. or local code requirements. Minimum circuit ampacity and maximum dual element fuse size are given in the Tables 2 – 6.

A 120-1-60, 15 amp source must be supplied for the control panel through a fused disconnect when a control panel transformer (optional) is not provided. Refer to Table 1 and Figures 2 - 4.

See Figures 2 - 5 and unit wiring diagrams for field and power wiring connections, chilled water pump starter contacts, alarm contacts, compressor run status contacts, PWM input, and load limit input. Refer to section on UNIT OPERATION for a detailed description of operation concerning aforementioned contacts and inputs.

12

YORK INTERNATIONAL

EVAPORATOR PUMP START CONTACTS

Terminal block CTB2 - terminals 23 to 24, are normally open contacts that can be used to switch field supplied power to provide a start signal to the evaporator pump contactor. The contacts will be closed when any of the following conditions occur:

1.Low Leaving Chilled Liquid Fault

2.Any compressor is running.

3.Daily schedule is not programmed OFF and the Unit Switch is ON.

The pump will not run if the micropanel has been powered up for less than 30 seconds, or if the pump has run in the last 30 seconds, to prevent pump motor overheating. Refer to figure 5 and unit wiring diagram.

SYSTEM RUN CONTACTS

Contacts are available to monitor system status. Normally-open auxiliary contacts from each compressor contactor are wired in parallel with CTB2 - terminals 25 to 26 for system 1, and CTB2 - terminals 27 to 28 for system 2 (YCAL0040 - YCAL0080). Refer to Figure 5 and unit wiring diagram.

ALARM STATUS CONTACTS

Normally-open contacts are available for each refrigerant system. These normally-open contacts close when the system if functionally normally. The respective contacts will open when the unit is shut down on a unit fault, or locked out on a system fault. Field connections are at CTB2 terminals 29 to 30 (system 1), and terminals 31 to 32 (system 2 YCAL0040 - YCAL0080).

REMOTE START/STOP CONTACTS

To remotely start and stop the chiller, dry contacts can be wired in series with the flow switch and CTB1 - terminals 13 to 14. Refer to Figure 5 and unit wiring diagram.

FORM 150.62-NM1

REMOTE EMERGENCY CUTOFF

Immediate shutdown of the chiller can be accomplished by opening a field installed dry contact to break the electrical circuit between terminals 5 to L on terminal block CTB2. The unit is shipped with a factory jumper installed

between terminals 5 to L, which must be removed if 1 emergency shutdown contacts are installed. Refer to Figure 5 and unit wiring diagram.

PWM INPUT

The PWM input allows reset of the chilled liquid setpoint by supplying a “timed” contact closure. Field wiring should be connected to CTB1 - terminals 13 to 20. A detailed explanation is provided in the Unit Control section. Refer to Figure 5 and unit wiring diagram.

LOAD LIMIT INPUT

Load limiting is a feature that prevents the unit from loading beyond a desired value. The unit can be “load limited” either 33%, 50%, or 66%, depending on the number of compressors on unit. The field connections are wired to CTB1 - terminals 13 to 21, and work in conjunction with the PWM inputs. A detailed explanation is provided in the Unit Control section. Refer to figure 5 and unit wiring diagram.

When using the Load Limit feature, the PWM feature will not function - SIMULTANEOUS OPERATION OF LOAD LIMITING AND TEMPERATURE RESET (PWM INPUT) CANNOT BE DONE.

FLOW SWITCH INPUT

The flow switch is field wired to CTB1 terminals 13 - 14. See Figure 5 and unit wiring diagram.

YORK INTERNATIONAL

13

Installation

STANDARD POWER SUPPLY WIRING – (0014 - 0080)

Power Panel

 

Control Panel

 

 

 

 

2

 

 

 

 

 

L

 

Circuit # 1 *Circuit # 2

Micropanel

 

1L1 1L2 1L3

GRD

2L1 2L2 2L3

GRD

 

Flow Switch

CTB2

 

 

 

 

 

14

 

 

 

 

13

 

 

 

 

CTB1

 

 

 

 

 

Field 120-1-60 Micropanel

 

 

 

 

Power Supply if control

 

 

 

 

transformer not supplied

 

 

 

 

Field Unit Power

 

 

 

 

 

Supply

 

 

See electrical note 9

 

 

 

 

 

 

 

LD04483

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE CHILLED LIQUID FREEZING.

Electrical Notes and Legend located on Page 18 and 19.

FIG. 2 – MULTI POINT POWER SUPPLY WIRING

14

YORK INTERNATIONAL

FORM 150.62-NM1

OPTIONAL SINGLE POINT POWER SUPPLY WIRING – (0040 - 0080)

Power Panel

Control Panel

1

 

 

 

2

 

 

 

 

 

L

 

 

 

 

 

Micropanel

 

1L1

1L2

1L3

GRD

 

 

 

 

 

CTB2

 

Flow Switch

 

 

 

 

13

14

 

 

 

 

CTB1

 

 

 

 

 

Field 120-1-60 Micropanel

 

 

 

 

Power Supply if control

 

 

 

 

transformer not supplied

 

 

 

Field Unit

Power Supply

See electrical note 9

LD04484

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE CHILLED LIQUID FREEZING.

Electrical Notes and Legend located on Page 18 and 19.

FIG. 3 – OPTIONAL SINGLE POINT POWER SUPPLY WIRING

YORK INTERNATIONAL

15

Installation

OPTIONAL SINGLE-POINT POWER SUPPLY WIRING

N-F DISC SW OR CIRC BKR (0014 - 0080)

Power Panel

Control Panel

 

 

 

 

2

 

 

 

 

 

 

L

 

 

N-F Disconnect

 

 

Micropanel

 

Sw. OR Molded

 

 

 

 

 

 

 

Case Circuit

 

 

 

 

 

Bkr.

 

 

GRD

 

 

 

1L1

1L2

1L3

CTB2

 

Flow Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

13

14

 

 

 

 

 

CTB1

 

 

 

 

 

 

Field 120-1-60 Micropanel

 

 

 

 

 

Power Supply if control

 

 

 

 

 

transformer not supplied

 

 

 

 

Field Unit

Power

 

 

 

 

 

Supply

 

 

See electrical note 9

LD04485

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE CHILLED LIQUID FREEZING.

Electrical Notes and Legend located on Page 18 and 19.

FIG. 4 – OPTIONAL SINGLE POINT POWER WIRING

16

YORK INTERNATIONAL

York YCAL0014SC, YCAL0080SC User Manual

FORM 150.62-NM1

CONTROL WIRING

FLOW SW REMOTE START/STOP

13

1

14

 

PWM INPUT

13

20

LOAD LIMIT INPUT

13

21

CTB1

LD03819

 

*

* Factory wired with optional transformer.

LD03611

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC

POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN

RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE

CHILLED LIQUID FREEZING.

 

FIG. 5 – CONTROL WIRING

 

YORK INTERNATIONAL

17

Installation

ELECTRICAL NOTES

NOTES:

1.Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the Factory Mounted Control Transformer is provided, add the following to the system MCA values in the electrical tables for the system supplying power to the optional transformer. -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, - 46, add 1.3 amps; -58, add 1 amp.

2.The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440.

3.Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95 °F is anticipated.

4.Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22.

5.Circuit breakers must be U.L. listed and CSA certified and maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Exception: YCA0014 and YCAL0020 must have the optional factory overloads installed to use a standard circuit breaker. Otherwise, an HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6.The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.

7.A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C. Table 250-95. A control circuit grounding lug is also supplied.

8.The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

9.Field Wiring by others which complies to the National Electrical Code and Local Codes.

18

YORK INTERNATIONAL

FORM 150.62-NM1

ELECTRICAL NOTES

LEGEND

 

 

 

 

 

 

 

1

ACR-LINE

ACROSS THE LINE START

 

C.B.

CIRCUIT BREAKER

 

 

 

 

 

 

D.E.

DUAL ELEMENT FUSE

 

 

 

DISC SW

DISCONNECT SWITCH

 

 

 

FACT MOUNT CB

FACTORY MOUNTED CIRCUIT BREAKER

 

 

 

FLA

FULL LOAD AMPS

 

 

 

HZ

HERTZ

 

 

 

MAX

MAXIMUM

 

 

 

MCA

MINIMUM CIRCUIT AMPACITY

 

 

 

MIN

MINIMUM

 

 

 

MIN NF

MINIMUM NON FUSED

 

 

 

RLA

RATED LOAD AMPS

 

 

 

S.P. WIRE

SINGLE POINT WIRING

 

 

 

UNIT MTD SERV SW

UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT

 

 

 

SWITCH)

 

 

 

 

 

LRA

LOCKED ROTOR AMPS

 

 

 

VOLTAGE CODE

-17 = 200-3-60

-28 = 230-3-60

-40 = 380-3-60

-46 = 460-3-60

-58 = 575-3-60

LEGEND: Field Wiring

Factory Wiring

YORK INTERNATIONAL

19

Installation

ELECTRICAL DATA

TABLE 1 – MICROPANEL POWER SUPPLY

 

 

 

MCA

OVER CURRENT PROTECTION,

 

UNIT VOLTAGE

UNIT VOLTAGE

CONTROL POWER

 

SEE NOTE B

NF DISC Sw

 

 

 

 

 

NOTE A

MIN

 

MAX

 

MODELS w/o

 

115-1-60/50

15A

10A

 

15A

30 A / 240V

CONTROL TRANS

 

 

 

 

 

 

 

 

 

 

-17

200-1-60

15A

10A

 

15A

30 A / 240V

MODELS w/

-28

230-1-60

15A

10A

 

15A

30 A / 240V

-40

380-1-60

15A

10A

 

15A

30 A / 480V

CONTROL TRANS

 

-46

460-1-60

15A

10A

 

15A

30 A / 480V

 

 

 

-58

575-1-60

15A

10A

 

15A

30 A / 600V

 

 

 

 

 

 

 

 

A.Minimum #14 AWG, 75° C, Copper Recommended

B.Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE CHILLED LIQUID FREEZING.

20

YORK INTERNATIONAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FORM 150.62-NM1

 

 

 

 

ELECTRICAL DATA – STANDARD SINGLE POINT POWER

 

 

 

 

 

 

 

 

 

 

YCAL0014SC - YCAL0034SC

 

 

 

 

 

 

 

 

 

TABLE 2 – STANDARD SINGLE POINT POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE POINT FIELD SUPPLIED WIRING

 

 

 

SYSTEM #1 COMPRESSOR & FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

MODEL

 

 

 

MIN N/F

D.E. FUSE

CKT. BKR.5

INCOMING

COMPR. #1

 

COMPR. #2

COMPR. #3

 

FANS

 

VOLT

HZ

MCA1

WIRE

 

 

 

YCAL

DISC SW2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN3

MAX4

MIN

 

MAX

RANGE6

RLA

LRA

 

RLA

LRA

RLA

LRA

 

QTY

FLA (EA)

 

 

 

 

 

 

 

 

 

 

 

 

 

200

60

75

100

90

100

90

 

100

# 4 - # 1

26.0

195

 

26.0

195

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

70

100

80

90

80

 

90

# 4 - # 1

24.1

195

 

24.1

195

 

2

7.8

 

 

0014SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

42

60

45

50

45

 

50

# 8 - # 4

14.0

113

 

14.0

113

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

34

60

40

40

40

 

40

# 10 - # 6

11.5

98

 

11.5

98

 

2

3.8

 

 

 

575

60

27

30

30

35

30

 

35

# 10 - # 6

9.2

80

 

9.2

80

 

2

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

60

100

150

110

125

110

 

125

# 2 - 1/0

37.0

237

 

37.0

237

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

93

100

110

125

110

 

125

# 2 - 1/0

34.3

237

 

34.3

237

 

2

7.8

 

 

0020SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

52

60

60

60

60

 

60

# 6 - # 2

18.5

154

 

18.5

154

 

2

4.8

 

 

 

460

60

45

60

50

60

50

 

60

# 8 - # 4

16.3

130

 

16.3

130

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

36

60

40

45

40

 

45

# 8 - # 4

13.1

85

 

13.1

85

 

2

3.1

 

 

 

200

60

127

150

150

175

150

 

175

# 1 - 2/0

49.1

298

 

49.1

298

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

118

150

150

150

150

 

150

# 1 - 2/0

45.5

298

 

45.5

298

 

2

7.8

 

 

0024SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

76

100

90

100

90

 

100

# 4 - # 1

29.5

235

 

29.5

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

57

60

70

70

70

 

70

# 6 - # 2

21.7

170

 

21.7

170

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

46

60

50

60

50

 

60

# 8 - # 4

17.3

140

 

17.3

140

 

2

3.1

 

 

 

200

60

140

150

175

175

175

 

175

1/0 - 3/0

54.7

420

 

54.7

420

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

130

150

150

175

150

 

175

1/0 - 3/0

50.7

420

 

50.7

420

 

2

7.8

 

 

0030SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

75

100

90

100

90

 

100

# 4 - # 1

28.7

235

 

28.7

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

62

100

70

80

70

 

80

# 6 - # 2

24.1

175

 

24.1

175

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

50

60

60

60

60

 

60

# 6 - # 2

19.3

140

 

19.3

140

 

2

3.1

 

 

 

200

60

183

200

200

225

200

 

225

3/0 - 250

51.2

298

 

51.2

298

51.2

298

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

170

200

200

200

200

 

200

2/0 - 4/0

47.4

298

 

47.4

298

47.4

298

 

2

7.8

 

 

0034SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

103

150

110

125

110

 

125

# 2 - 1/0

28.7

235

 

28.7

235

28.7

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

81

100

90

100

90

 

100

# 4 - # 1

22.6

175

 

22.6

175

22.6

175

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

65

100

70

80

70

 

80

# 4 - # 1

18

140

 

18

140

18

140

 

2

3.1

 

 

See notes and legend on pages 18 and 19.

YORK INTERNATIONAL

21

Installation

ELECTRICAL DATA – STANDARD DUAL POINT POWER

YCAL0040SC - YCAL0080SC

TABLE 3 – STANDARD DUAL POINT POWER

 

 

 

SYSTEM #1 FIELD SUPPLIED WIRING

 

 

 

SYSTEM #1 COMPRESSOR & FAN

 

 

MODEL

 

 

 

 

 

D.E. FUSE

CKT. BKR.5

INCOMING

COMPR. #1

COMPR. #2

COMPR. #3

 

FANS

VOLT

HZ

 

MCA1

MIN N/F

WIRE

 

YCAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISC SW2

MIN3

MAX4

MIN

MAX

RANGE6

RLA

LRA

RLA

LRA

RLA

LRA

 

QTY

FLA (EA)

 

 

 

 

 

 

 

200

60

 

91

100

100

110

100

110

# 2 - 1/0

32.9

265

32.9

265

 

2

8.2

 

230

60

 

85

100

100

110

100

110

# 4 - # 1

30.5

265

30.5

265

 

2

7.8

0040SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

54

60

60

70

60

70

# 6 - # 2

19.4

155

19.4

155

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

41

60

45

50

45

50

# 8 - # 4

14.5

120

14.5

120

 

2

3.8

 

575

60

 

33

60

40

40

40

40

# 10 - # 6

11.6

80

11.6

80

 

2

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

60

 

130

150

150

175

150

175

# 1 - 2/0

50.2

298

50.2

298

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

 

121

150

150

150

150

150

# 1 - 2/0

46.5

298

46.5

298

 

2

7.8

0044SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

73

100

80

100

80

100

# 4 - # 1

28.1

235

28.1

235

 

2

4.8

 

460

60

 

58

60

70

70

70

70

# 6 - # 2

22.1

170

22.1

170

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

 

47

60

60

60

60

60

# 8 - # 4

17.7

140

17.7

140

 

2

3.1

 

200

60

 

146

200

175

200

175

200

1/0 - 3/0

57.4

420

57.4

420

 

2

8.2

 

230

60

 

136

150

150

175

150

175

1/0 - 3/0

53.1

420

53.1

420

 

2

7.8

0050SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

79

100

90

100

90

100

# 4 - # 1

30.8

235

30.8

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

65

100

80

80

80

80

# 4 - # 1

25.3

175

25.3

175

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

 

52

60

60

70

60

70

# 6 - # 2

20.2

140

20.2

140

 

2

3.1

 

200

60

 

141

150

175

175

175

175

1/0 - 3/0

55.0

420

55.0

420

 

2

8.2

 

230

60

 

131

150

150

175

150

175

1/0 - 3/0

50.9

420

50.9

420

 

2

7.8

0060SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

77

100

90

100

90

100

# 4 - # 1

29.6

235

29.6

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

63

100

70

80

70

80

# 6 - # 2

24.2

175

24.2

175

 

2

3.8

 

575

60

 

50

60

60

60

60

60

# 6 - # 2

19.4

140

19.4

140

 

2

3.1

 

200

60

 

187

200

200

225

200

225

3/0 - 250

52.4

298

52.4

298

52.4

298

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

 

174

200

200

200

200

200

2/0 - 4/0

48.6

298

48.6

298

48.6

298

 

2

7.8

0064SC

380

60

 

105

150

125

125

125

125

# 2 - 1/0

29.3

235

29.3

235

29.3

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

83

100

90

100

90

100

# 4 - # 1

23.1

170

23.1

170

23.1

170

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

 

67

100

80

80

80

80

# 4 - # 1

18.5

140

18.5

140

18.5

140

 

2

3.1

 

200

60

 

185

200

200

225

200

225

3/0 - 250

51.8

298

51.8

298

51.8

298

 

2

8.2

 

230

60

 

172

200

200

200

200

200

2/0 - 4/0

48.0

298

48.0

298

48.0

298

 

2

7.8

0070SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

104

150

125

125

125

125

# 2 - 1/0

29.0

235

29.0

235

29.0

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

82

100

90

100

90

100

# 4 - # 1

22.9

170

22.9

170

22.9

170

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

 

66

100

80

80

80

80

# 4 - # 1

18.3

140

18.3

140

18.3

140

 

2

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

60

 

208

250

225

250

225

250

4/0 - 300

58.9

420

58.9

420

58.9

420

 

2

8.2

 

230

60

 

193

250

225

225

225

225

3/0 - 250

54.5

420

54.5

420

54.5

420

 

2

7.8

0074SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

 

113

150

125

125

125

125

# 2 - 1/0

31.6

235

31.6

235

31.6

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

92

100

100

110

100

110

# 2 - 1/0

26.0

175

26.0

175

26.0

175

 

2

3.8

 

575

60

 

74

100

80

90

80

90

# 4 - # 1

20.8

140

20.8

140

20.8

140

 

2

3.1

 

200

60

 

207

250

225

250

225

250

4/0 - 300

58.6

420

58.6

420

58.6

420

 

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

 

192

250

225

225

225

225

3/0 - 250

54.2

420

54.2

420

54.2

420

 

2

7.8

0080SC

380

60

 

112

150

125

125

125

125

# 2 - 1/0

31.5

235

31.5

235

31.5

235

 

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

 

92

100

100

110

100

110

# 2 - 1/0

25.8

175

25.8

175

25.8

175

 

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

 

74

100

80

90

80

90

# 4 - # 1

20.7

140

20.7

140

20.7

140

 

2

3.1

See notes and legend on pages 18 and 19.

22

YORK INTERNATIONAL

FORM 150.62-NM1

ELECTRICAL DATA – STANDARD DUAL POINT POWER

YCAL0040SC - YCAL0080SC

 

SYSTEM #2 FIELD SUPPLIED WIRING

 

 

 

SYSTEM #2 COMPRESSOR & FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

MIN N/F

D.E. FUSE

CKT. BRK.5

INCOMING

COMPR. #1

 

COMPR. #2

COMPR. #3

 

FANS

 

MCA1

WIRE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISC SW2

MIN3

 

MAX4

MIN

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE6

RLA

LRA

 

RLA

LRA

RLA

LRA

QTY

FLA (EA)

 

 

91

100

100

 

110

100

 

110

# 2 - 1/0

32.9

265

 

32.9

265

2

8.2

 

 

85

100

100

 

110

100

 

110

# 4 - # 1

30.5

265

 

30.5

265

2

7.8

 

 

54

60

60

 

70

60

 

70

# 6 - # 2

19.4

155

 

19.4

155

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

60

45

 

50

45

 

50

# 8 - # 4

14.5

120

 

14.5

120

2

3.8

 

 

33

60

40

 

40

40

 

40

# 10 - # 6

11.6

80

 

11.6

80

2

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130

150

150

 

175

150

 

175

# 1 - 2/0

50.2

298

 

50.2

298

2

8.2

 

 

121

150

150

 

150

150

 

150

# 1 - 2/0

46.5

298

 

46.5

298

2

7.8

 

 

73

100

80

 

100

80

 

100

# 4 - # 1

28.1

235

 

28.1

235

2

4.8

 

 

58

60

70

 

70

70

 

70

# 6 - # 2

22.1

170

 

22.1

170

2

3.8

 

 

47

60

60

 

60

60

 

60

# 8 - # 4

17.7

140

 

17.7

140

2

3.1

 

 

130

150

150

 

175

150

 

175

# 1 - 2/0

49.5

298

 

49.5

298

2

8.2

 

 

121

150

150

 

150

150

 

150

# 1 - 2/0

45.9

298

 

45.9

298

2

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

73

100

80

 

100

80

 

100

# 4 - # 1

27.8

235

 

27.8

235

2

4.8

 

 

58

60

70

 

70

70

 

70

# 6 - # 2

21.8

170

 

21.8

170

2

3.8

 

 

47

60

60

 

60

60

 

60

# 8 - # 4

17.5

140

 

17.5

140

2

3.1

 

 

141

150

175

 

175

175

 

175

1/0 - 3/0

55.0

420

 

55.0

420

2

8.2

 

 

131

150

150

 

175

150

 

175

1/0 - 3/0

50.9

420

 

50.9

420

2

7.8

 

 

77

100

90

 

100

90

 

100

# 4 - # 1

29.6

235

 

29.6

235

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

100

70

 

80

70

 

80

# 6 - # 2

24.2

175

 

24.2

175

2

3.8

 

 

50

60

60

 

60

60

 

60

# 6 - # 2

19.4

140

 

19.4

140

2

3.1

 

 

128

150

150

 

150

150

 

150

# 1 - 2/0

34.2

265

 

34.2

265

34.2

265

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

119

150

150

 

150

150

 

150

# 1 - 2/0

31.6

265

 

31.6

265

31.6

265

2

7.8

 

 

76

100

90

 

90

90

 

90

# 4 - # 1

20.2

155

 

20.2

155

20.2

155

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

100

70

 

70

70

 

70

# 6 - # 2

15.1

120

 

15.1

120

15.1

120

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46

60

50

 

50

50

 

50

# 8 - # 4

12.0

80

 

12.0

80

12.0

80

2

3.1

 

 

185

200

200

 

225

200

 

225

3/0 - 250

51.8

298

 

51.8

298

51.8

298

2

8.2

 

 

172

200

200

 

200

200

 

200

2/0 - 4/0

48.0

298

 

48.0

298

48.0

298

2

7.8

 

 

104

150

125

 

125

125

 

125

# 2 - 1/0

29.0

235

 

29.0

235

29.0

235

2

4.8

 

 

82

100

90

 

100

90

 

100

# 4 - # 1

22.9

170

 

22.9

170

22.9

170

2

3.8

 

 

66

100

80

 

80

80

 

80

# 4 - # 1

18.3

140

 

18.3

140

18.3

140

2

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

181

200

200

 

225

200

 

225

3/0 - 250

50.5

298

 

50.5

298

50.5

298

2

8.2

 

 

168

200

200

 

200

200

 

200

2/0 - 4/0

46.8

298

 

46.8

298

46.8

298

2

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

102

150

110

 

125

110

 

125

# 2 - 1/0

28.3

235

 

28.3

235

28.3

235

2

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

100

90

 

100

90

 

100

# 4 - # 1

22.3

170

 

22.3

170

22.3

170

2

3.8

 

 

65

100

70

 

80

70

 

80

# 6 - # 2

17.8

140

 

17.8

140

17.8

140

2

3.1

 

 

207

250

225

 

250

225

 

250

4/0 - 300

58.6

420

 

58.6

420

58.6

420

2

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

192

250

225

 

225

225

 

225

3/0 - 250

54.2

420

 

54.2

420

54.2

420

2

7.8

 

 

112

150

125

 

125

125

 

125

# 2 - 1/0

31.5

235

 

31.5

235

31.5

235

2

4.8

 

 

92

100

100

 

110

100

 

110

# 2 - 1/0

25.8

175

 

25.8

175

25.8

175

2

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

100

80

 

90

80

 

90

# 4 - # 1

20.7

140

 

20.7

140

20.7

140

2

3.1

 

 

YORK INTERNATIONAL

23

Installation

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0014SC - YCAL0034SC

TABLE 4 – OPTIONAL SINGLE POINT POWER

SINGLE POINT FIELD SUPPLIED WIRING

MODEL

 

 

 

MIN N/F

D.E. FUSE

CKT. BKR.5

INCOMING WIRE RANGE6

VOLT

HZ

MCA1

FACTORY SUPPLIED OPTIONAL

YCAL

DISC SW2

 

 

 

 

 

 

 

MIN3

MAX4

MIN

MAX

DISCONNECT

BREAKER

 

 

 

 

 

 

200

60

75

100

90

100

90

100

# 4 - # 1

# 4 - # 1

 

230

60

70

100

80

90

80

90

# 4 - # 1

# 4 - # 1

0014SC

380

60

42

60

45

50

45

50

# 8 - # 4

# 8 - # 4

 

460

60

34

60

40

40

40

40

# 10 - # 6

# 10 - # 6

 

575

60

27

30

30

35

30

35

# 10 - # 6

# 10 - # 6

 

200

60

100

150

110

125

110

125

# 2 - 1/0

# 2 - 1/0

 

230

60

93

100

110

125

110

125

# 2 - 1/0

# 2 - 1/0

0020SC

380

60

52

60

60

60

60

60

# 6 - # 2

# 6 - # 2

 

460

60

45

60

50

60

50

60

# 8 - # 4

# 8 - # 4

 

575

60

36

60

40

45

40

45

# 8 - # 4

# 8 - # 4

 

200

60

127

150

150

175

150

175

# 1 - 2/0

# 1 - 2/0

 

230

60

118

150

150

150

150

150

# 1 - 2/0

# 1 - 2/0

0024SC

380

60

76

100

90

100

90

100

# 4 - # 1

# 4 - # 1

 

460

60

57

60

70

70

70

70

# 6 - # 2

# 6 - # 2

 

575

60

46

60

50

60

50

60

# 8 - # 4

# 8 - # 4

 

200

60

140

150

175

175

175

175

1/0 - 3/0

1/0 - 3/0

 

 

 

 

 

 

 

 

 

 

 

 

230

60

130

150

150

175

150

175

1/0 - 3/0

1/0 - 3/0

0030SC

380

60

75

100

90

100

90

100

# 4 - # 1

# 4 - # 1

 

 

 

 

 

 

 

 

 

 

 

 

460

60

62

100

70

80

70

80

# 6 - # 2

# 6 - # 2

 

 

 

 

 

 

 

 

 

 

 

 

575

60

50

60

60

60

60

60

# 6 - # 2

# 6 - # 2

 

200

60

183

200

200

225

200

225

3/0 - 250

3/0 - 250

 

 

 

 

 

 

 

 

 

 

 

 

230

60

170

200

200

200

200

200

2/0 - 4/0

2/0 - 4/0

0034SC

 

 

 

 

 

 

 

 

 

 

380

60

103

150

110

125

110

125

# 2 - 1/0

# 2 - 1/0

 

460

60

81

100

90

100

90

100

# 4 - # 1

# 4 - # 1

 

 

 

 

 

 

 

 

 

 

 

 

575

60

65

100

70

80

70

80

# 4 - # 1

# 4 - # 1

See notes and legend on pages 18 and 19.

24

YORK INTERNATIONAL

FORM 150.62-NM1

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0014SC - YCAL0034SC

 

 

SYSTEM #1 COMPRESSOR & FAN

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

COMPR. #1

COMPR. #2

COMPR. #3

 

 

FANS

 

 

 

 

 

 

 

RLA

LRA

RLA

LRA

RLA

LRA

 

QTY

 

FLA (EA)

26.0

195

26.0

195

 

2

 

8.2

 

 

 

24.1

195

24.1

195

 

2

 

7.8

 

 

 

14.0

113

14.0

113

 

2

 

4.8

 

 

 

11.5

98

11.5

98

 

2

 

3.8

 

 

 

9.2

80

9.2

80

 

2

 

3.1

 

 

 

37.0

237

37.0

237

 

2

 

8.2

 

 

 

34.3

237

34.3

237

 

2

 

7.8

 

 

 

18.5

154

18.5

154

 

2

 

4.8

 

 

 

16.3

130

16.3

130

 

2

 

3.8

 

 

 

13.1

85

13.1

85

 

2

 

3.1

 

 

 

49.1

298

49.1

298

 

2

 

8.2

 

 

 

45.5

298

45.5

298

 

2

 

7.8

 

 

 

29.5

235

29.5

235

 

2

 

4.8

 

 

 

21.7

170

21.7

170

 

2

 

3.8

 

 

 

17.3

140

17.3

140

 

2

 

3.1

 

 

 

54.7

420

54.7

420

 

2

 

8.2

 

 

 

50.7

420

50.7

420

 

2

 

7.8

 

 

 

28.7

235

28.7

235

 

2

 

4.8

 

 

 

24.1

175

24.1

175

 

2

 

3.8

 

 

 

19.3

140

19.3

140

 

2

 

3.1

 

 

 

51.2

298

51.2

298

51.2

298

 

2

 

8.2

 

 

 

47.4

298

47.4

298

47.4

298

 

2

 

7.8

 

 

 

28.7

235

28.7

235

28.7

235

 

2

 

4.8

 

 

 

22.6

175

22.6

175

22.6

175

 

2

 

3.8

 

 

 

18

140

18

140

18

140

 

2

 

3.1

 

 

 

YORK INTERNATIONAL

25

Installation

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0040SC - YCAL0060SC

TABLE 5 – OPTIONAL SINGLE POINT POWER

SINGLE POINT FIELD SUPPLIED WIRING

MODEL

 

 

 

MIN N/F

D.E. FUSE

CKT. BKR.5

INCOMING WIRE RANGE6

 

VOLT

HZ

MCA1

FACTORY SUPPLIED OPTIONAL

 

YCAL

DISC SW2

 

 

 

 

 

 

 

 

MIN3

MAX4

MIN

MAX

SINGLE POINT

DISCONNECT

BREAKER

 

 

 

 

 

 

200

60

173

200

200

200

200

200

2/0 - 4/0

2/0 - 4/0

2/0 - 4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

161

200

175

175

175

175

2/0 - 4/0

2/0 - 4/0

2/0 - 4/0

0040SC

 

 

 

 

 

 

 

 

 

 

 

380

60

102

150

110

110

110

110

# 2 - 1/0

# 2 - 1/0

# 2 - 1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

77

100

90

90

90

90

# 4 - # 1

# 4 - # 1

# 4 - # 1

 

575

60

62

100

70

70

70

70

# 6 - # 2

# 6 - # 2

# 6 - # 2

 

200

60

247

400

300

300

300

300

250 - 350

250

- 350

250

- 350

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

229

250

250

250

250

250

4/0 - 300

4/0 - 300

4/0 - 300

0044SC

 

 

 

 

 

 

 

 

 

 

 

380

60

139

200

150

150

150

150

1/0 - 3/0

1/0 - 3/0

1/0 - 3/0

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

110

150

125

125

125

125

# 2 - 1/0

# 2 - 1/0

# 2 - 1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

88

100

100

100

100

100

# 2 - 1/0

# 2 - 1/0

# 2 - 1/0

 

200

60

261

400

300

300

300

300

300 - 400

300

- 400

300

- 400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

243

400

300

300

300

300

250 - 350

250

- 350

250

- 350

0050SC

 

 

 

 

 

 

 

 

 

 

 

 

 

380

60

145

200

175

175

175

175

1/0 - 3/0

1/0

- 3/0

1/0

- 3/0

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

116

150

125

125

125

125

# 1 - 2/0

# 1 - 2/0

# 1 - 2/0

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

93

150

100

110

100

110

# 2 - 1/0

# 2 - 1/0

# 2 - 1/0

 

200

60

267

400

300

300

300

300

300 - 400

300

- 400

300

- 400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

248

400

300

300

300

300

250 - 350

250

- 350

250

- 350

0060SC

 

 

 

 

 

 

 

 

 

 

 

380

60

145

200

175

175

175

175

1/0 - 3/0

1/0 - 3/0

1/0 - 3/0

 

 

 

 

 

 

 

 

 

 

 

 

 

460

60

119

150

125

125

125

125

# 1 - 2/0

# 1 - 2/0

# 1 - 2/0

 

 

 

 

 

 

 

 

 

 

 

 

 

575

60

95

150

100

110

100

110

# 2 - 1/0

# 2 - 1/0

# 2 - 1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See notes and legend on pages 18 and 19.

26

YORK INTERNATIONAL

FORM 150.62-NM1

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0040SC - YCAL0060SC

 

 

SYSTEM #1 COMPRESSOR & FAN

 

 

 

 

 

SYSTEM #2 COMPRESSOR & FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPR. #1

COMPR. #2

COMPR. #3

 

 

FANS

COMPR. #1

COMPR. #2

COMPR. #3

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA

LRA

RLA

LRA

RLA

LRA

 

QTY

 

FLA (EA)

RLA

LRA

RLA

LRA

RLA

LRA

QTY

 

FLA (EA)

32.9

265

32.9

265

 

2

 

8.2

32.9

265

32.9

265

2

 

8.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30.5

265

30.5

265

 

2

 

7.8

30.5

265

30.5

265

2

 

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19.4

155

19.4

155

 

2

 

4.8

19.4

155

19.4

155

2

 

4.8

 

 

 

14.5

120

14.5

120

 

2

 

3.8

14.5

120

14.5

120

2

 

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.6

80

11.6

80

 

2

 

3.1

11.6

80

11.6

80

2

 

3.1

 

 

 

50.2

298

50.2

298

 

2

 

8.2

50.2

298

50.2

298

2

 

8.2

 

 

 

46.5

298

46.5

298

 

2

 

7.8

46.5

298

46.5

298

2

 

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28.1

235

28.1

235

 

2

 

4.8

28.1

235

28.1

235

2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22.1

170

22.1

170

 

2

 

3.8

22.1

170

22.1

170

2

 

3.8

 

 

 

17.7

140

17.7

140

 

2

 

3.1

17.7

140

17.7

140

2

 

3.1

 

 

 

57.4

420

57.4

420

 

2

 

8.2

49.5

298

49.5

298

2

 

8.2

 

 

 

53.1

420

53.1

420

 

2

 

7.8

45.9

298

45.9

298

2

 

7.8

 

 

 

30.8

235

30.8

235

 

2

 

4.8

27.8

235

27.8

235

2

 

4.8

 

 

 

25.3

175

25.3

175

 

2

 

3.8

21.8

170

21.8

170

2

 

3.8

 

 

 

20.2

140

20.2

140

 

2

 

3.1

17.5

140

17.5

140

2

 

3.1

 

 

 

55.0

420

55.0

420

 

2

 

8.2

55.0

420

55.0

420

2

 

8.2

 

 

 

50.9

420

50.9

420

 

2

 

7.8

50.9

420

50.9

420

2

 

7.8

 

 

 

29.6

235

29.6

235

 

2

 

4.8

29.6

235

29.6

235

2

 

4.8

 

 

 

24.2

175

24.2

175

 

2

 

3.8

24.2

175

24.2

175

2

 

3.8

 

 

 

19.4

140

19.4

140

 

2

 

3.1

19.4

140

19.4

140

2

 

3.1

 

 

 

YORK INTERNATIONAL

27

Installation

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0064SC - YCAL0080SC

TABLE 6 – OPTIONAL SINGLE POINT POWER

SINGLE POINT FIELD SUPPLIED WIRING

MODEL

 

 

 

MIN N/F

D.E. FUSE

CKT. BKR.5

 

INCOMING WIRE RANGE6

 

VOLT

HZ

MCA1

 

FACTORY SUPPLIED OPTIONAL

 

YCAL

DISC SW2

 

 

 

 

 

 

 

 

 

MIN3

MAX4

MIN

MAX

SINGLE POINT

DISCONNECT

BREAKER

 

 

 

 

 

 

 

 

200

60

306

400

350

350

350

350

350

- 500

350

- 500

350

- 500

 

 

230

60

284

400

300

300

300

300

300

- 400

300

- 400

300

- 400

0064SC

380

60

175

200

200

200

200

200

3/0 - 250

3/0 - 250

3/0 - 250

 

 

460

60

136

150

150

150

150

150

1/0 - 3/0

1/0 - 3/0

1/0 - 3/0

 

 

575

60

109

150

125

125

125

125

# 2 - 1/0

# 2

- 1/0

# 2

- 1/0

 

 

200

60

357

400

400

400

400

400

500 - (2) 4/0

500 -

(2) 4/0

500 -

(2) 4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

332

400

350

350

350

350

400

- 600

400

- 600

400

- 600

0070SC

380

60

201

250

225

225

225

225

4/0 - 300

4/0 - 300

4/0 - 300

 

 

460

60

159

200

175

175

175

175

2/0 - 4/0

2/0 - 4/0

2/0 - 4/0

 

 

575

60

127

150

150

150

150

150

# 1 - 2/0

# 1

- 2/0

# 1

- 2/0

 

 

200

60

376

600

400

400

400

400

500 - (2) 4/0

500 -

(2) 4/0

500 -

(2) 4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

60

349

400

400

400

400

400

500 - (2) 4/0

500 -

(2) 4/0

500 -

(2) 4/0

0074SC

380

60

207

250

225

225

225

225

4/0 - 300

4/0 - 300

4/0 - 300

 

 

460

60

167

200

175

175

175

175

2/0 - 4/0

2/0 - 4/0

2/0 - 4/0

 

 

575

60

134

150

150

150

150

150

1/0 - 3/0

1/0 - 3/0

1/0 - 3/0

 

 

200

60

399

600

450

450

450

450

600 - (2) 250

600 - (2) 250

600 - (2) 250

 

 

230

60

371

600

400

400

400

400

500 - (2) 4/0

500 -

(2) 4/0

500 -

(2) 4/0

0080SC

 

 

 

 

 

 

 

 

 

 

 

380

60

216

250

225

225

225

225

4/0 - 300

4/0 - 300

4/0 - 300

 

 

460

60

177

200

200

200

200

200

3/0 - 250

3/0 - 250

3/0 - 250

 

 

575

60

142

200

150

150

150

150

1/0 - 3/0

1/0 - 3/0

1/0 - 3/0

See notes and legend on pages 18 and 19.

28

YORK INTERNATIONAL

FORM 150.62-NM1

ELECTRICAL DATA – OPTIONAL SINGLE POINT POWER

YCAL0064SC - YCAL0080SC

 

 

SYSTEM #1 COMPRESSOR & FAN

 

 

 

 

 

SYSTEM #2 COMPRESSOR & FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

COMPR. #1

COMPR. #2

COMPR. #3

 

 

FANS

COMPR. #1

COMPR. #2

COMPR. #3

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA

LRA

RLA

LRA

RLA

LRA

 

QTY

 

FLA (EA)

RLA

LRA

RLA

LRA

RLA

LRA

QTY

 

FLA (EA)

52.4

298

52.4

298

52.4

298

 

2

 

8.2

34.2

265

34.2

265

34.2

265

2

 

8.2

 

 

48.6

298

48.6

298

48.6

298

 

2

 

7.8

31.6

265

31.6

265

31.6

265

2

 

7.8

 

 

29.3

235

29.3

235

29.3

235

 

2

 

4.8

20.2

155

20.2

155

20.2

155

2

 

4.8

 

 

23.1

170

23.1

170

23.1

170

 

2

 

3.8

15.1

120

15.1

120

15.1

120

2

 

3.8

 

 

18.5

140

18.5

140

18.5

140

 

2

 

3.1

12.0

80

12.0

80

12.0

80

2

 

3.1

 

 

51.8

298

51.8

298

51.8

298

 

2

 

8.2

51.8

298

51.8

298

51.8

298

2

 

8.2

 

 

48.0

298

48.0

298

48.0

298

 

2

 

7.8

48.0

298

48.0

298

48.0

298

2

 

7.8

 

 

29.0

235

29.0

235

29.0

235

 

2

 

4.8

29.0

235

29.0

235

29.0

235

2

 

4.8

 

 

22.9

170

22.9

170

22.9

170

 

2

 

3.8

22.9

170

22.9

170

22.9

170

2

 

3.8

 

 

18.3

140

18.3

140

18.3

140

 

2

 

3.1

18.3

140

18.3

140

18.3

140

2

 

3.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58.9

420

58.9

420

58.9

420

 

2

 

8.2

50.5

298

50.5

298

50.5

298

2

 

8.2

 

 

54.5

420

54.5

420

54.5

420

 

2

 

7.8

46.8

298

46.8

298

46.8

298

2

 

7.8

 

 

31.6

235

31.6

235

31.6

235

 

2

 

4.8

28.3

235

28.3

235

28.3

235

2

 

4.8

 

 

26.0

175

26.0

175

26.0

175

 

2

 

3.8

22.3

170

22.3

170

22.3

170

2

 

3.8

 

 

20.8

140

20.8

140

20.8

140

 

2

 

3.1

17.8

140

17.8

140

17.8

140

2

 

3.1

 

 

58.6

420

58.6

420

58.6

420

 

2

 

8.2

58.6

420

58.6

420

58.6

420

2

 

8.2

 

 

54.2

420

54.2

420

54.2

420

 

2

 

7.8

54.2

420

54.2

420

54.2

420

2

 

7.8

 

 

31.5

235

31.5

235

31.5

235

 

2

 

4.8

31.5

235

31.5

235

31.5

235

2

 

4.8

 

 

25.8

175

25.8

175

25.8

175

 

2

 

3.8

25.8

175

25.8

175

25.8

175

2

 

3.8

 

 

20.7

140

20.7

140

20.7

140

 

2

 

3.1

20.7

140

20.7

140

20.7

140

2

 

3.1

 

 

YORK INTERNATIONAL

29

Installation

OPERATIONAL LIMITATIONS (ENGLISH)

TABLE 7 – TEMPERATURES AND FLOWS

 

 

LEAVING WATER

COOLER FLOW (GPM3)

AIR ON CONDENSER (°F)

YCAL00

TEMPERATURE (°F )

 

 

 

 

 

 

MIN1

MAX2

MIN

MAX

MIN4

MAX5

14SC

40

55

30

60

25

125

20SC

40

55

30

60

25

125

24SC

40

55

35

70

25

125

30SC

40

55

45

75

25

125

34SC

40

55

75

110

25

125

40SC

40

55

75

250

25

125

44SC

40

55

75

250

25

125

50SC

40

55

75

250

25

125

60SC

40

55

75

250

25

125

64SC

40

55

130

390

25

125

70SC

40

55

130

390

25

125

74SC

40

55

130

390

25

125

80SC

40

55

120

430

25

125

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and operation beyond these limitations may cause serious damage to the compressor.

TABLE 8 – VOLTAGES

UNIT POWER

MIN.

MAX.

200-3-60

180

220

230-3-60

207

253

380-3-60

355

415

460-3-60

414

506

575-3-60

517

633

NOTES:

Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special care should be taken when multiple chillers are fed by a single pump.

1.Standard units cannot be operated below 40°F leaving chilled water temperature.

2.For leaving water temperature higher than 55°F, contact the nearest YORK Office for application guidelines.

3.The evaporator is protected against freeze-up to -20.0°F with an electrical heater as standard.

4.Operation below 25°F requires Optional Low Ambient Kit for operation to 0°F.

5.Operation above 115°F requires Optional High Ambient Kit for operation to 125°F.

30

YORK INTERNATIONAL

Loading...
+ 106 hidden pages